EPCOS B84299K0067

EMC filters
2-line filters
for installations and systems
Rated current 2 to 36 A
Series/Type:
B84299K0061 … K0067
Date:
January 2006
 EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the
information contained therein without EPCOS’ prior express consent is prohibited.
2-line filters
B84299K0061 … K0067
for installations and systems
Power line filters for 1-phase systems
with additional LF suppression
Rated voltage 250 V DC/AC, 50/60 Hz
Rated current 2 to 36 A
Construction
■ 2-line filter
■ Metal case
■ Polyurethane potting (UL 94 V-0)
Features
■ Especially high differential-mode
insertion loss from 20 kHz upwards
■ Safe mounting by press-in nuts
■ Space-saving design
■ ENEC10 and UL approval
Applications
■ Switch-mode power supplies for traction,
safety systems, automation engineering
■ Power supplies
■ Industrial electronics
■ DC applications
Terminals
■ Litz wires
Marking
Marking on component:
Manufacturer’s logo, ordering code, rated voltage,
rated current, climatic category, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
Typical circuit diagram
LINE
Blue
L
LOAD
Blue
L’
N
Black
Please read Cautions and warnings and
Important notes at the end of this document.
N’
Black
2
SSB0591-E-E
01/06
2-line filters
B84299K0061 … K0067
for installations and systems
Technical data and measuring conditions
Rated voltage VR
250 V DC/AC, 50/60 Hz
Rated current IR
Referred to 40 °C ambient temperature
Test voltage Vtest
1414 V DC, 2 s (line/line)
2830 V DC, 2 s (lines/case)
Overload capability (thermal)
1.5 · IR for 3 min per hour or
2.5 · IR for 30 s per hour
Leakage current lleak
At 230 V AC, 50 Hz
Climatic category (IEC 60068-1)
For K0061 and K0062:
25/100/21 (–25 °C/+100 °C/21 days damp heat test)
For K0063 ... K0067:
25/085/21 (–25 °C/+85 °C/21 days damp heat test)
Approvals
EN 133200, UL 1283
Characteristics and ordering codes
VR
AC/DC
V
250
IR
Approvals
mΩ
Approx. Ordering code
weight
kg
530
0.35
B84299K0061C000
×
—
< 3.5
150
0.37
B84299K0062C000
×
—
< 3.5
100
0.82
B84299K0063
—
×
16
< 3.5
45
1.0
B84299K0064C000
—
×
2.5
14
< 3.5
35
1.8
B84299K0065
—
—
25
4.0
12
< 3.5
25
2.9
B84299K0066
—
—
36
6.0
10
< 10
10
2.9
B84299K0067
—
—
Terminal
cross section
mm2
AWG
mA
2
1.0
18
< 3.5
4
1.0
18
6
1.0
18
10
1.5
16
A
lleak
Rtyp
× = approval granted
Please read Cautions and warnings and
Important notes at the end of this document.
3
01/06
2-line filters
B84299K0061 … K0067
for installations and systems
Dimensional drawings
B84299K0061C000, B84299K0062C000 (2 and 4 A)
45
30±0.4
M4 x 6
3 x litz wires AWG 18
(BU, BK, GNYE)
350±15
7
Line
Load
7
300±15
51
2 x litz wires
AWG 18 (BU, BK)
Marking
Type
Length
B84299K0061C000
B84299K0062C000
65 mm
75 mm
SSB2097-8-E
B84299K0063 (6 A)
M4 x 6
67
46±0.4
64±0.4
7
350±15
Line
Load
2 x litz wires
AWG 18 (BU, BK)
50
7.5
7
300±15
3 x litz wires AWG 18
(BU, BK, GNYE)
Marking
25.9
Ground terminal M4 x 6
for shielding braid
or fixing stud
for cable clamp
84.5
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2098-G-E
4
01/06
2-line filters
B84299K0061 … K0067
for installations and systems
B84299K0064C000 (10 A)
28
8
7
350±15
Ground terminal M4 x 8
for shielding braid
or fixing stud
for cable clamp
Marking
ø10
1
55
Load
2 x litz wires
AWG 16 (BU, BK)
Line
7
300±15
3 x litz wires AWG 16
(BU, BK, GNYE)
67
M4 x 8
47±0.4
80±0.4
68.5
100.5
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2099-P-E
5
01/06
2-line filters
B84299K0061 … K0067
for installations and systems
B84299K0065 (16 A)
28
2 x litz wires
AWG 14 (BU, BK)
Marking
7
300±15
9
Ground terminal M4 x 8
for shielding braid
or fixing stud
for cable clamp
71
Load
Line
450±15
7
3 x litz wires AWG 14
(BU, BK, GNYE)
68
M4 x 6
43±0.4
107±0.4
100
132
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2100-W-E
6
01/06
2-line filters
B84299K0061 … K0067
for installations and systems
B84299K0066 (25 A)
28
2 x litz wires
AWG 12 (BU, BK)
800±20
Load
Line
7
68.5
300±15
7
3 x litz wires AWG 12
(BU, BK, GNYE)
85
M5 x 7
73±0.4
130±0.4
8
Ground terminal M4 x 6
for shielding braid
or fixing stud
for cable clamp
Marking
15±3
183
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2101-5-E
7
01/06
2-line filters
B84299K0061 … K0067
for installations and systems
B84299K0067 (36 A)
28
2 x litz wires
AWG 10 (BU, BK)
800±15
Load
Line
7
68.5
240±15
7
3 x litz wires AWG 10
(BU, BK, GNYE)
85
M5 x 7
73±0.4
130±0.4
8
Ground terminal M4 x 6
for shielding braid
or fixing stud
for cable clamp
Marking
15±3
183
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2102-D-E
8
01/06
2-line filters
B84299K0061 … K0067
for installations and systems
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 2 A
Filters for 4 A
SSB0323-3
100
SSB0324-B
100
B84299K0062C000
B84299K0061C000
α
dB
α
dB
80
80
60
60
40
40
20
20
0
10 4
10 5
10 6
10 7
0
10 4
Hz 10 8
f
Filters for 6 A
10 5
10 6
10 7
Hz 10 8
f
Filters for 10 A
SSB0325-J
100
SSB0326-S
100
B84299K0064C000
α
dB
α
dB
80
80
60
60
40
40
20
20
B84299K0063
0
10 4
10 5
10 6
Hz
f
Please read Cautions and warnings and
Important notes at the end of this document.
0
10 4
10 7
9
01/06
10 5
10 6
Hz
f
10 7
2-line filters
B84299K0061 … K0067
for installations and systems
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 16 A
Filters for 25 A
SSB0327-1
100
α
SSB0328-9
100
dB
α
dB
80
80
60
60
40
40
20
20
B84299K0066
B84299K0065
0
10 4
10
5
10
6
Hz
f
10
0
10 4
7
Filters for 36 A
SSB0329-H
100
α
dB
80
60
40
20
B84299K0067
0
10 4
10 5
10 6
Hz
f
Please read Cautions and warnings and
Important notes at the end of this document.
10 7
10
01/06
10
5
10 6
Hz
f
10 7
EMC filters
Cautions and warnings
Important information
Please read all safety and warning notes carefully before installing the EMC filter and putting it into
operation (see
). The same applies to the warning signs on the filter. Please ensure that the signs
are not removed nor their legibility impaired by external influences.
Death, serious bodily injury and substantial material damage to equipment may occur if the appro­
priate safety measures are not carried out or the warnings in the text are not observed.
Using according to the terms
The EMC filters may be used only for their intended application within the specified values in low­
voltage networks in compliance with the instructions given in the data sheets and the data book.
The conditions at the place of application must comply with all specifications for the filter used.
Warnings
■ It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
■
■
■
■
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge. Danger­
ous voltages can continue to exist at the filter terminals for longer than five minutes even after
the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is installed and
the last to be disconnected. Depending on the magnitude of the leakage currents, the particular
specifications for making the protective-earth connection must be observed.
Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequen­
cies that may cause resonances etc. can lead to destruction of the filter housing.
EMC filters must be protected in the application against impermissible exceeding of the rated
currents by suitable overcurrent protective.
11
01/06
EMC filters
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application. As
a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them
than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of passive electronic components
or failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications
requiring a very high level of operational safety and especially in customer applications in which
the malfunction or failure of a passive electronic component could endanger human life or health
(e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of
suitable design of the customer application or other action taken by the customer (e.g.
installation of protective circuitry or redundancy) that no injury or damage is sustained by third
parties in the event of malfunction or failure of a passive electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as “hazardous”). Useful information on this will be found in our
Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more
detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products.
Consequently, we cannot guarantee that all products named in this publication will always be
available.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, EPCOS-Jones, Baoke, CeraDiode, CSSP, MLSC, PhaseCap,
PhaseMod, SIFI, SIKOREL, SilverCap, SIMID, SIOV, SIP5D, SIP5K, UltraCap, WindCap are
trademarks registered or pending in Europe and in other countries. Further information will be
found on the Internet at www.epcos.com/trademarks.
12
01/06