TELEDYNE MX3P46D4S-02

Series MX
2-Pole or 3-Pole 4A 460 Vac
DIN-Rail SSR
Part Number
Description
MX2P46D4T-02
4A, 460 Vac
MX3P46D4S-02
4A, 460 Vac
Part Number Explanation
MX
46
2P
D
T
4
-02
FEATURES/BENEFITS
• New generation of solid-state relays for DIN-rail
mounting
• Two- or three-pole output with single control
• Tight zero-cross window for low EMI
• Control visualization by LED
• Integrated clamping voltage
• High immunity to surges
NOTES
1) Poles: 2P = 2 pole; 3P = 3 pole
2) Line Voltage: 46 = 460 Vac
3) Switch Type: D = Zero-cross turn-on
4) Control Range: T = 15–40 Vdc; S = 12–35 Vdc
5) Options: 02 = With LED
MECHANICAL SPECIFICATION
L3
L1
input
output
6-30Vdc 400Vac 4A
L2
A1+
4- 3+
T1 T2
Input
24-460Vac
12-35Vdc
4A AC3
3.01 (76.4)
L1 L2
A1+
A1-
±0.4
3.01 (76.4) ±0.4
2
1
L1 L2
T1 T2
A1-
A2- A1+
T2
T3
input
10-35VDC
T1
±0.2
1.14
2.09
±0.2
(29)
±0.1
.98 (25)
(53)
WEIGHT: 1.06 oz (30g)
1.87
MX2P46D4T-02
±0.1
DESCRIPTION
The Series MX relays are a new generation of solidstate relays for DIN-rail fixation. The MX relays are
internally wired to provide a common control. The
relays are placed on a single DIN-rail fixture, saving
designers time and space. The Series MX relays
provide a control status LED and internal output
protection.
(47.5)
MX3P46D4S-02
Figure 1 — MX relays; dimensions in inches (mm)
INPUT (CONTROL) SPECIFICATION
Min
Max
Units
MX2P46D4T-02
15
40
V
MX3P46D4S-02
12
35
V
MX2P46D4T-02
4.4
17
mA
MX3P46D4S-02
7.5
30
mA
APPLICATIONS
• Interface applications
• Vending machines
• Light/lamp control
• Contactor driver
• Fan speed control
• HVAC controls
• Heating control
Control Range
Input Current Range
BLOCK DIAGRAM
A1 +
A1 +
Rc
Must Turn-Off Voltage
Rc
L1
L1
T1
MX2P46D4T-02
8
V
MX3P46D4S-02
6
V
T1
L2
T2
L2
L3
Input Resistance (Typical)
A1 -
MX2P46D4T-02
2000
Ohms
MX3P46D4S-02
1000
Ohms
© 2003 TELEDYNE RELAYS
T2
Figure 2a — MX2P relay
(800) 284-7007 • www.teledynerelays.com
A1 -
T3
Figure 2b — MX3P relay
MX 1
MX\032003\Q1
Series MX
CONTROL CHARACTERISTICS
OUTPUT (LOAD) SPECIFICATION
Min
18
Input Current (mA)
16
Operating Range
14
24
Peak Voltage
12
Max
Unit
460
Vrms
1200
V
4
Arms
2.5
Arms
Load Current
10
8
Range (Resistive)
.005
6
4
Inductive Load Current
2
Maximum Surge Current Rating (Non-Repetitive)
0
0
5
10
15
20
25
30
35
40
Control Voltage (V)
Figure 3a — MX2P relay
30
(See Figure 5)
120
A
On-State Voltage Drop
1.6
V
Zero-Cross Window
±12
V
Off-State Leakage Current (60Hz)
0.3
mA
Turn-On Time (60Hz)
8.3
ms
Turn-Off Time (60Hz)
8.3
ms
Input Current (mA)
25
20
Off-State dv/dt
15
Operating Frequency
10
2
I t for match fusing (<8.3ms)
10
500
V/µs
440
Hz
50
A2S
5
ENVIRONMENTAL SPECIFICATION
0
0
5
10
15
20
25
30
35
Min
Control Voltage (V)
Figure 3b — MX3P relay
TYPICAL APPLICATIONS
Max
Unit
Operating Temperature
–40
80
°C
Storage Temperature
–40
150
°C
Input-Output Isolation
4000
Vrms
Input-Output Capacity
3
pF
3 phases
200 up to 480 Vac
L1 L2 L3
SURGE CURRENT
Y wiring
150
∆ wiring
Apeak
Non-Repetitive
100
50
Repetitive with initial Tj = 70°C
0
single
phase
0.01
0.1
1
10
t(s)
Figure 5 — MX relays
Figure 4a — MX2P relay
LOAD
L1 L2 L3
Figure 4b — MX3P relay
MX 2
NOTES:
1. Electrical parameters at 25°C unless otherwise specified.
2. For 800Hz applications, contact factory.
3. For additional/custom options, contact factory.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
© 2003 TELEDYNE RELAYS
MX\032003\Q1