DELTA DIN RAIL Jan 2014_Australia cata.qxd

AC/DC DIN RAIL MOUNTABLE
Delta DRP024V060W1BA
24V 60W - CLIQ 11 DIN RAIL POWER SUPPLY
FEATURES
•
•
•
•
•
•
•
•
Universal AC input voltage without power de-rating
High efficiency > 90.0% @ 230Vac
Power Boost of 150% for 5 seconds (480W: 200% for 2
seconds)
Full corrosion resistant Aluminium chassis
Conforms to harmonic current IEC/EN 61000-3-2, Class A
Extreme low temperature cold start at -40°C
Conformal coating on PCBA to protect against chemical
and dust pollutants
Hazardous Locations approval to ATEX and Class I, Div 2
SPECIFICATIONS
INPUT
Input Voltage Range
MECHANICAL
85-264Vac (DC input range 120-375Vdc)
Case Cover
Plastic
47-63Hz
< 1.50A @ 115Vac,
Input Current
< 0.80A @ 230Vac
> 88.0% @ 115Vac,
Efficiency 1) at 100% Load
> 89.0% @ 230Vac
< 40A @ 115Vac,
Max Inrush Current
< 80A @ 230Vac
Power Factor
Conform to EN 61000-3-2
Dimensions (L x W x D)
120.6 x 32 x 119.3 mm
Unit Weight
0.33 kg
Cooling System
Convection
Input Terminal
3 Pins (Rated 300V/30A)
Output Terminal
2 Pins (Rated 300V/30A)
Input / Output Wire
AWG 22-10
Leakage Current
< 1mA @ 240Vac
MTBF 2)
> 800,000 hrs
Output Voltage
24V
Operating Temperature
-25°C to +80°C
Output Voltage Range
24-28V
Storage Temperature
Output Current
2.50A
Power De-rating
Output Power
60W
Operating Humidity
-25°C to +85°C
> 50°C (2.5% / °C);
> 70°C (4% / °C)
< 95% RH (Non-Condensing)
Line Regulation
< 0.5% typ. (@ 85-264Vac input, 100% load)
Operating Altitude
2,500m
Load Regulation
< 1% typ. (@ 85-264Vac input, 0-100% load)
PARD (20MHz)
< 240mVpp
> 20ms @ 115Vac,
> 125ms @ 230Vac
Input Frequency
OUTPUT
Hold-up Time
ENVIRONMENTAL
NOTES:
1) Efficiency: O/P 100% load, Ta: 25°C at Vertical Mounting Orientation
2) MTBF as per Telcordia SR-332 (Confidential level: 90%, I/P: 115Vac,
O/P: 100% load) at Vertical Mounting Orientation
3) All parameters are specified at 25°C ambient unless otherwise noted
MECHANICAL DRAWINGS
6
Powering Progress – www.powerbox.com.au
Doc. No. PBC9-Delta Rev.G 3-2-14