SynQor UPS Terminal Commands Command Summary

SynQor UPS Terminal Commands
Rev D, 14 April 2014
The UPS external serial port uses 115.2kbaud, 8 data bits, no parity, and one stop bit. Commands can be sent, and
output viewed, with any standard terminal emulator. To view user text, set the terminal emulator for local echo. All
transmitted commands must be terminated with a line feed character (ASCII 10). The interface is not case sensitive.
The UPS will transmit a prompt "SynQor>" to the terminal after each command. To execute a command, simply
transmit the required ASCII text, terminated by a line feed character. Note that only the first 8 characters for any
command are required to recognize and launch the command.
Command Summary
Command
Description
?
Display list of available terminal commands.
ALARM DISABLE
Disable audible alarm output. (Updates non-volatile memory.)
ALARM ENABLE
Enable audible alarm output. (Updates non-volatile memory.)
ALARM SILENCE
Silence currently active audible alarms.
ANALOG IN?
Display control board analog signal levels.
ASTART DISABLE
Disable auto-start mode (default factory setting).
ASTART ENABLE
Enable auto-start mode.
BATT INFO
Display manufacturer data and code revisions for installed battery pack.
BATTERY?
Display internal measurements and status for installed battery pack.
CODE?
Output code revision information for internal components.
DEBUG OFF
Disable automatic output of source data on startup (default factory setting).
DEBUG ON
Enable output of "SOURCE LOG" output on initial power application.
DIGITAL IN?
Display state of internal digital inputs of UPS control board.
DIS AC1
Set AC Output inactive.
DIS DC1
Set DC1 Output inactive.
DIS DC2
Set DC2 Output inactive
EMAIL RESTORE
Restore Email alert notifications to factory default settings.
ENA AC1
Set AC Output active.
ENA DC1
Set DC1 Output active.
ENA DC2
Set DC2 Output active.
FAN SERVICE
Execute fan service sequence immediately (cycles through fan speed settings).
FAN SET x
Manually set fan speed, x=0 to 4.
FAN STATUS?
Display inputs to fan controller.
065-0000020 Rev D
Page 1 of 18
SynQor UPS Terminal Commands
Command
Description
FAND DISABLE
Disable execution of fan diagnostics every 24 hours.
FAND ENABLE
Enable execution of fan diagnositcs every 24 hours (default factory setting).
FANS?
Display fan speeds and input voltage.
FOUT 400
Set AC Output frequency to 400 Hz.
FOUT 50
Set AC Output frequency to 50 Hz.
FOUT 60
Set AC Output frequency to 60 Hz.
INPUTS?
Display status of inputs to UPS system.
NET RESTORE
Restore network configuration settings to factory defaults.
NETWORK?
Display Ethernet IP address and MAC address.
OUTPUT DISABLE
Shutdown AC and DC outputs of UPS system, reverting to standby or off state.
OUTPUT ENABLE
Enable AC and DC outputs of UPS system.
OUTPUTS?
Display status of outputs from UPS system.
RESTART x
Shutdown output immediately, re-enable output after x seconds.
RUNTEST x
Run internal built-in test routine.
SHUTDOWN x
Shutdown output after x seconds.
SNMP RESTORE
Restore SNMP configuration to factory defaults.
SOURCE LOG
Begin real-time output of power source status and switchover events.
SOURCES?
Display status of each defined source for the UPS system (AC, DC, and battery).
STARTUP x
Enable outputs after x seconds.
TEMPS?
Display reported temperatures for internal subsystems.
Command Details
Command: ?
Description: Display list of available terminal commands.
Sample Output: SynQor>?
?
ALARM DISABLE
ALARM ENABLE
ALARM SILENCE
‫׃‬
SynQor>
Discussion: Output response format is a single row for each command available to the user.
065-0000020 Rev D
Page 2 of 18
SynQor UPS Terminal Commands
Command: ALARM DISABLE
Description: Disable audible alarm output. (Updates non-volatile memory.)
Sample Output: SynQor>ALARM DISABLE
Flash Updated.
SynQor>
Discussion: This command will prevent the audible beeper from ever activating for any condition. Setting
will be saved in non-volatile memory, and will persist until reversed with the "ALARM ENABLE"
command.
Command: ALARM ENABLE
Description: Enable audible alarm output. (Updates non-volatile memory.)
Sample Output: SynQor>ALARM ENABLE
Flash Updated.
SynQor>
Discussion: This command will allow the audible beeper to sound during alarm conditions. This is the
default factory state. See User Guide, "Fault Conditions" section for a description of audible
alarms. The setting will be saved in non-volatile memory, and will persist until reversed with the
"ALARM DISABLE" command.
Command: ALARM SILENCE
Description: Silence currently active audible alarms.
Sample Output: SynQor>ALARM SILENCE
Alarms Silenced.
SynQor>
Discussion: When there are current active alarms, issuing this command will silence the beeper. New alarm
states that occur after the silence command will re-activate the audible beeper. This command
is equivalent to holding up the front panel switch during operation. The beeper generates a
brief two-toned signal when the silence command is issued.
065-0000020 Rev D
Page 3 of 18
SynQor UPS Terminal Commands
Command: ANALOG IN?
Description: Display control board analog signal levels.
Sample Output: SynQor>ANALOG IN?
5V Supply = 5.16 V
External DC Input = 0.5 V
Cold-start Voltage = 29.2 V
Main Bus Voltage = 29.4 V
Fan Current = &H0000
Fan Voltage = 0.0 V
Battery Voltage = 0.5 V
Motherboard Temperature = 24 C
Charger Current = &H01F7
DC Out Readback = 0.11 V
SynQor>
Discussion: Command displays translated values from ADC measurements on UPS control board. No user
action based on these outputs should taken. Note that Fan Current and Charger Current are
not directly translateable to actual current readings. The DC Out Readback represents the
output of a current amplifier; it does not represent the DC output voltage. An analog
representation of the DC output voltage is not available.
Command: ASTART DISABLE
Description: Disable auto-start mode (default factory setting).
Sample Output: SynQor>ASTART DISABLE
Flash Updated.
SynQor>
Discussion: Command disables auto-start mode. This is the default factory configuration. With auto-start
disabled, when the UPS receives AC or DC input power, it will enter standby mode. In standby
mode, the battery will charge and the terminal interface is active, but the output will not
enable until the user takes action to enable the output, either through a terminal command,
the front panel switch, or a rear panel I/O signal.
Command: ASTART ENABLE
Description: Enable auto-start mode.
Sample Output: SynQor>ASTART ENABLE
Flash Updated.
SynQor>
Discussion: Command enables auto-start mode. In auto-start mode, when the UPS first receives AC or DC
input power from an off state, it will automatically enable the AC and DC outputs after a brief
delay. This is not the default factory setting. Once the autostart mode is set, it will persist until
disabled with the "ASTART DISABLE" command. Note that autostart will only enable the output
from a powered down state; if the output disables due to a fault or user action, but input
power is still present, the output will not automatically re-enable.
065-0000020 Rev D
Page 4 of 18
SynQor UPS Terminal Commands
Command: BATT INFO
Description: Display manufacturer data and code revisions for installed battery pack.
Sample Output: SynQor>BATT INFO
Manufacturer: SynQor, Inc.
Device Type: 8SnP UPS Battery
Chemistry: LiPo
Serial Number: 1
Manufacture Date: 2009/9/1
Num ID Code Rev
0 &HFFFF 43, 32
1 &H6666 32, 17
2 &H3333 32, 17
3 &H1111 32, 17
4 &H7777 32, 17
5 &H4444 32, 17
6 &H5555 32, 17
7 &H2222 32, 17
SynQor>
Discussion: Command displays data and code revisions read from an installed battery pack. No user action
based on these outputs should be taken. The code revision data gives one row (Row 0) for the
front panel board, and then an additional row for each detected battery string.
Command: BATTERY?
Description: Display internal measurements and status for installed battery pack.
Sample Output: SynQor>BATTERY?
Num Strings = 7
Voltage = 33342 mV
Current = 480 mA
SBS Status = &H4000
Battery Temperature = 24.8 C
Temp Severity = 2
Requested Chg V = 33200 mV
Requested Chg I = 250 mA
Charge vs. Full = 99 %
Charge vs. Designed = 99 %
Battery Flags = 0x0000
Comm Fault = &H0000
Min to Empty = >65535 min
Min to Full = 12 min
Min at Present Power = 366 min
Charge Cycles = 11
SynQor>
065-0000020 Rev D
Page 5 of 18
SynQor UPS Terminal Commands
Discussion: Displays summary of telemetry data from installed battery pack. All measurements are as
reported or estimated by the internal battery monitoring circuitry. Notes on data values:
Current values are positive for charging current, negative for discharge currents.
SBS Status is compliant with the SBS Standard.
Temp Severity: 0 = Too cold to discharge, 1 = Too cold to charge, 2 = Normal, 3 = Too hot to
charge, 4 = unused, 5 = Too hot to discharge
"vs. Full" is measured relative to the current charge capacity of available strings in the battery
pack; "vs. Designed" is relative to the designed capacity of the battery pack.
The "Min to Empty" and "Min to Full" parameters are based on the current charge or discharge
current and estimated pack capacity. The "Min at Present Power" shows the predicted runtime
based on the present delivered power and battery capacity if the AC and DC inputs failed.
[Note that for Communication Board code Revs prior to 2.0, there were minor differences in the
BATTERY? query output.]
Command: CODE?
Description: Output code revision information for internal components.
Sample Output: SynQor>CODE?
AC/DC Rev 1 = &H0072
AC/DC Rev 2 = &H006A
DC/AC Rev = &H0071
Control Rev = 78, 62
Comm Code Rev = 2, 0
SynQor>
Discussion: Outputs reported code revision of internal modules. Note that modules which are not active
will not report a valid value. For example, with no AC power applied, the AC/DC revisions will
not be valid. If the AC output is not active, the DC/AC revision will not be valid.
Command: DEBUG OFF
Description: Disable automatic output of source data on startup (default factory setting).
Sample Output: SynQor>DEBUG OFF
Flash Updated.
SynQor>
Discussion: Disables automatic output of "SOURCE LOG" command after intial power application. This is
the default factory setting. This command will reverse the action of the "DEBUG ON" command.
065-0000020 Rev D
Page 6 of 18
SynQor UPS Terminal Commands
Command: DEBUG ON
Description: Enable output of "SOURCE LOG" output on initial power application.
Sample Output: SynQor>DEBUG ON
Flash Updated.
SynQor>
Discussion: Enables automatic output of "SOURCE LOG" command after intial power application for
debugging purposes. Issuing the "DEBUG OFF" command will revert to standard operation.
Command: DIGITAL IN?
Description: Display state of internal digital inputs of UPS control board.
Sample Output: SynQor>DIGITAL IN?
DC Out 0 Fault = High
DC Out 1 Fault = Low
AC input Alarm = Low
External Input Alarm = High
Front Switch UP = Low
Remote Start = Low
Front Switch DOWN = Low
SynQor>
Discussion: Command displays translated values from digital inputs UPS control board. No user action
based on these outputs should taken. Note that the presence of DC Out 0 & DC Out 1 inputs
does not imply that DC outputs are or are not available on a given system.
Command: DIS AC1
Description: Set AC Output inactive.
Sample Output: SynQor>DIS AC1
Flash Updated.
SynQor>
Discussion: Command sets the AC Output to remain disabled and not follow the enable state of the UPS
output. This is a non-volatile setting. Once set, the AC Output will remain disabled until the
"ENA AC1" command is transmitted. [Command available for Communication Board Code Rev
2.0 and later.]
065-0000020 Rev D
Page 7 of 18
SynQor UPS Terminal Commands
Command: DIS DC1
Description: Set DC1 Output inactive.
Sample Output: SynQor>DIS DC1
Flash Updated.
SynQor>
Discussion: Command sets the DC1 Output to remain disabled and not follow the enable state of the UPS
output. This is a non-volatile setting. Once set, the DC1 Output will remain disabled until the
"ENA DC1" command is transmitted. [Command available for Communication Board Code Rev
2.0 and later. This command is only available if the DC1 Output Option is installed.]
Command: DIS DC2
Description: Set DC2 Output inactive
Sample Output: SynQor>DIS DC2
Flash Updated.
SynQor>
Discussion: Command sets the DC2 Output to remain disabled and not follow the enable state of the UPS
output. This is a non-volatile setting. Once set, the AC Output will remain disabled until the
"ENA DC2" command is transmitted. [Command available for Communication Board Code Rev
2.0 and later. This command is only available if the DC2 Output Option is installed.]
Command: EMAIL RESTORE
Description: Restore Email alert notifications to factory default settings.
Sample Output: SynQor>EMAIL RESTORE
Factory Email Defaults Restored.
SynQor>
Discussion: Command restores settings for Email alerts to factory defaults (no alerts transmitted). [This
command is only available with the Ethernet Option installed.]
Command: ENA AC1
Description: Set AC Output active.
Sample Output: SynQor>ENA AC1
Flash Updated.
SynQor>
Discussion: Command sets the AC Output to activate with the enable state of the UPS output. This is a nonvolatile setting. Sending this command will not immediately activate the AC Output unless the
UPS Output is already enabled with the front panel switch or "OUTPUT ENABLE" command.
[This command is only available for Communication Board Code Rev 2.0 and later.]
065-0000020 Rev D
Page 8 of 18
SynQor UPS Terminal Commands
Command: ENA DC1
Description: Set DC1 Output active.
Sample Output: SynQor>ENA DC1
Flash Updated.
SynQor>
Discussion: Command sets the DC1 Output to activate with the enable state of the UPS output. This is a
non-volatile setting. Sending this command will not immediately activate the DC1 Output
unless the UPS Output is already enabled with the front panel switch or "OUTPUT ENABLE"
command. [This command is only available for Communication Board Code Rev 2.0 and later.
This command is only available if the DC1 Option is installed.]
Command: ENA DC2
Description: Set DC2 Output active.
Sample Output: SynQor>ENA DC2
Flash Updated.
SynQor>
Discussion: Command sets the DC2 Output to activate with the enable state of the UPS output. This is a
non-volatile setting. Sending this command will not immediately activate the DC2 Output
unless the UPS Output is already enabled with the front panel switch or "OUTPUT ENABLE"
command. [This command is only available for Communication Board Code Rev 2.0 and later.
This command is only available if the DC2 Option is installed.]
Command: FAN SERVICE
Description: Execute fan service sequence immediately (cycles through fan speed settings).
Sample Output: SynQor>FAN SERVICE
Fan service initiated
SynQor>
Discussion: The fan service sequence cycles the fans through their different speed ranges, and compares
the measured fan RPM to the factory-new levels. Significant speed degradation will be
indicated by a "fan service required" LED on the front panel. Note that the fan service
sequence will not slow the fans down below the speed dictated by the internal temperatures.
The fan service sequence normally runs automatically after every 24 hours of continuous
operation, or more frequently if a fan speed degradation condition is detected. Fan service
sequence will not run on battery power.
065-0000020 Rev D
Page 9 of 18
SynQor UPS Terminal Commands
Command: FAN SET x
Description: Manually set fan speed, x=0 to 4.
Sample Output: SynQor>FAN SET 1
Fan speed set.
SynQor>
Discussion: Manually increase the fan speed. Fans will not slow to a speed below that dictated by internal
temperatures. Manually setting a higher fan speed will modify the UPS Cooling System
Indicator LED (F0) as indicated in the User Guide.
Command: FAN STATUS?
Description: Display inputs to fan controller.
Sample Output: SynQor>FAN STATUS?
Current Speed: 0
Last Trigger Up: Manual Control
Decel Timer: &H0000 &H0000
Var:
value / thresh_down / thresh_up / type
Manual Control: &H0000 / &H0000 / &H0000 / higher value -> speed up
Diag Timer: &H0003 / &H4381 / &H4380 / higher value -> speed up
AcuQor Prim: &H00F5 / &H0000 / &H0136 / higher value -> speed up
AcuQor Sec: &H00F1 / &H0000 / &H0136 / higher value -> speed up
Control PCB: &H0134 / &H0000 / &H01AD / higher value -> speed up
Battery: &H0BA2 / &H0000 / &H0C08 / higher value -> speed up
SynQor>
Discussion: Displays inputs and status of the fan speed controller. The Last Trigger Up reflects which input
to the controller last caused an increase in the fan speed. The list of fan controller inputs
indicates which modules are online and providing triggers to control the fan speed. For each
input, the present value is listed, as well as the thresholds applied to that value to cause a
trigger to a higher or lower fan speed. Manual Control is the terminal interface and Diag
Timer is the interval counter for the fan service sequence. Some inputs may be omitted from
the list. For example, if there is no AC input power present then the ACuQor inputs will not be
returned.
Command: FAND DISABLE
Description: Disable execution of fan diagnostics every 24 hours.
Sample Output: SynQor>FAND DISABLE
Flash Updated.
SynQor>
Discussion: Disables automatic execution of the fan diagnostic sequence after every 24 hours of operation.
If the fan diagnositic sequence is disabled, a transient fan speed fault may not be cleared
automatically.
065-0000020 Rev D
Page 10 of 18
SynQor UPS Terminal Commands
Command: FAND ENABLE
Description: Enable execution of fan diagnositcs every 24 hours (default factory setting).
Sample Output: SynQor>FAND ENABLE
Flash Updated.
SynQor>
Discussion: Allows execution of the fan diagnostics automatically based on internal timing intervals. The
fan diagnostics cycle the fan through the various speeds and compares detected fan RPM to
factory-new values.
Command: FANS?
Description: Display fan speeds and input voltage.
Sample Output: SynQor>FANS?
Fan0 RPM = 10699
Fan1 RPM = 10344
Fan Voltage = 11.9 V
Fan Status / State = &H2100
Fan Diag Timer [h:mm] = 23:59
SynQor>
Discussion: Reports measure fan speed and applied voltage. The Fan Status / State variable provides
additional information about the fan status. Fan Status bit decoding:
b15-13: Fan speed value from 0-4. In sample, speed b15-13=001, indicating speed 1
b11: Machine status is Faulted
b10: Machine status is Starting
b9: Machine status is Running
b8: Machine status is Standby (indicated in sample)
b7: Fan service is required
b6: Fan diagnostics mode active
The Fan Diag Timer variable displays the time until the next scheduled fan diagnostics routine.
Command: FOUT 400
Description: Set AC Output frequency to 400 Hz.
Sample Output: SynQor>FOUT 400
Flash Updated.
SynQor>
Discussion: Command sets UPS AC Output frequency to 400Hz. WARNING: This setting may damage
connected AC loads if the loads are not rated for 400Hz operation. [This command is only
available for Communication Board Code Rev 2.0 and later.]
065-0000020 Rev D
Page 11 of 18
SynQor UPS Terminal Commands
Command: FOUT 50
Description: Set AC Output frequency to 50 Hz.
Sample Output: SynQor>FOUT 50
Flash Updated.
SynQor>
Discussion: Command sets UPS AC Output frequency to 50Hz. WARNING: This setting may damage
connected AC loads if the loads are not rated for 50Hz operation. [This command is only
available for Communication Board Code Rev 2.0 and later.]
Command: FOUT 60
Description: Set AC Output frequency to 60 Hz.
Sample Output: SynQor>FOUT 60
Flash Updated.
SynQor>
Discussion: Command sets UPS AC Output frequency to 60Hz. WARNING: This setting may damage
connected AC loads if the loads are not rated for 60Hz operation. [This command is only
available for Communication Board Code Rev 2.0 and later.]
Command: INPUTS?
Description: Display status of inputs to UPS system.
Sample Output: SynQor>INPUTS?
AC In Voltage = 113 V
AC In Current = 1990 mA
AC In Frequency = 60.3 Hz
Ext DC In Voltage = 0.5 V
Fault Register = &H0000
Multi-unit Config = &H000F
Non-volatile Config = &H1D01
SynQor>
065-0000020 Rev D
Page 12 of 18
SynQor UPS Terminal Commands
Discussion: Reports status of inputs to UPS system. The Fault Register decoding is as follows:
b15: Internal Bus Average Voltage Low
b14: Remote Shutdown requested from back panel
b13: Remote start requested from back panel
b12: Front panel switch pressed down (off)
b11: External DC Input Fault
b10: Software Disable Command
b9: Software Enable Command
b8: DCOUT2 Fault
b7: DCOUT1 Fault
b6: Internal Bus High
b5: Internal Bus Low
b4: Front panel switch pressed up (on / cold-start)
b3: Internal 5V supply High
b2: Internal 5V supply Low
b1: Over-temperature Warning
b0: Over-temperature condition
[Revisions of Communication Board Code before Rev 2.0 report 'Switch Status' instead of 'Fault
Register'.]
The Multi-unit Config register is determined by the connection of a paralleling cable on the rear
panel male DB15 connector. The Non-volatile Config register gives the FLASH memory options
as follows:
b12: AC Output Active
b11: DC2 Output Active
b10: DC1 Output Active
b9: External DC Input Option Installed
b8: AC Output Option Installed
b7: DC2 Output Option Installed
b6: Ungrounded Output Option
b5: AC Output Autostart Enabled
b4: DC1 Output Option Installed
b3: Fan Diagnostics Disabled
b2: Audible Alarm Disabled
b1: Debug Mode on Startup Enabled
b0: Fan Calibration Done
Command: NET RESTORE
Description: Restore network configuration settings to factory defaults.
Sample Output: SynQor>NET RESTORE
Factory Networking Defaults Restored.
SynQor>
Discussion: Command restores settings for network configuration to factory defaults. [This command is
only available with the Ethernet Option installed.]
065-0000020 Rev D
Page 13 of 18
SynQor UPS Terminal Commands
Command: NETWORK?
Description: Display Ethernet IP address and MAC address.
Sample Output: SynQor>NETWORK?
IP Address = 10.2.6.8
MAC Address = 00:04:A3:B5:73:AC
SynQor>
Discussion: Command displays the device pre-set MAC address and currently active IP address. [This
command is only available with the Ethernet Option installed.]
Command: OUTPUT DISABLE
Description: Shutdown AC and DC outputs of UPS system, reverting to standby or off state.
Sample Output: SynQor>OUTPUT DISABLE
Output Disabled.
SynQor>
Discussion: Disables output on AC and DC outputs if currently active. This terminal command is equivalent
to holding down the front panel switch.
Command: OUTPUT ENABLE
Description: Enable AC and DC outputs of UPS system.
Sample Output: SynQor>OUTPUT ENABLE
Output Enabled.
SynQor>
Discussion: Enables output on AC and DC outputs. This terminal command is equivalent to pushing the
front panel switch upwards.
065-0000020 Rev D
Page 14 of 18
SynQor UPS Terminal Commands
Command: OUTPUTS?
Description: Display status of outputs from UPS system.
Sample Output: SynQor>OUTPUTS?
Total Power Out =9W
AC Out Power = 2W
DC Out Power = 7W
AC Out Voltage RMS = 115650 mV
AC Out Current RMS =633 mA
AC Out Frequency = 60 Hz
Alarm Status = &H0400
Fan Status / State = &H2400
BIT Result = &H1002
SynQor>
Discussion: Reports telemetry data on AC and DC outputs. DC output power will appear even if DC output
option is not installed. The Alarm Status variable details the state of the audible alarms:
b7 : Audible alarm is muted (not disabled)
b3 : Four beep alarm active
b2 : Three beep alarm active
b1 : Two beep alarm active
b0 : One beep alarm active
The "FANS?" Command description details the Fan Status / State register. The BIT Result
variable displays the last result from a built-in test routine, if applicable.
Command: RESTART x
Description: Shutdown output immediately, re-enable output after x seconds.
Sample Output: SynQor>RESTART 5
Timed reboot started.
SynQor>
Discussion: If outputs are enabled, they will be immediately disabled. After the requested delay, outputs
will enable. Outputs will enable whether or not they were in an enabled state when the
command was first issued. Maximum permissible value for restart time is 10,737,418 seconds,
approximately 4 months.
065-0000020 Rev D
Page 15 of 18
SynQor UPS Terminal Commands
Command: RUNTEST x
Description: Run internal built-in test routine.
Sample Output: SynQor>RUNTEST 3
General System Test Started.
SynQor>Test Complete. Result=&H1002
Test Passed.
SynQor>
Discussion: Runs internal built-in test routine. Legal values for x:
x=0 or 2 : Abort test in progress.
x=3 : Run General Systems Test; verifies internal bias voltages, fans, voltage inputs and outputs.
x=4 : Quick Battery Test; verifies proper battery operation.
x=5 : Deep Battery Test; switches to battery power and runs battery down to 20% charge to
test battery runtime. [Test time depends strongly on output load.]
[This command is only available for Communication Board Code Rev 2.0 and later.]
Command: SHUTDOWN x
Description: Shutdown output after x seconds.
Sample Output: SynQor>SHUTDOWN 5
Timed shutdown started.
SynQor>
Discussion: Outputs will be disabled after the requested delay time. Maximum permissible value for
shutdown delay is 10,737,418 seconds, approximately 4 months.
Command: SNMP RESTORE
Description: Restore SNMP configuration to factory defaults.
Sample Output: SynQor>SNMP RESTORE
Factory SNMP Defaults Restored.
SynQor>
Discussion: Command restores SNMP configuration to factory defaults (SNMP disabled). [This command is
only available with the Ethernet Option installed.]
Command: SOURCE LOG
Description: Begin real-time output of power source status and switchover events.
Sample Output: SynQor>SOURCE LOG
SynQor>[…continuous debug output will follow]
Discussion: Source log output is useful to monitor input source switching and detected faults with
supervision from SynQor factory personnel. To terminate source logging, send several newline
characters through the terminal interface.
065-0000020 Rev D
Page 16 of 18
SynQor UPS Terminal Commands
Command: SOURCES?
Description: Display status of each defined source for the UPS system (AC, DC, and battery).
Sample Output: SynQor>SOURCES?
AC Input Module
- Faults: &H0000
- Ok for load: YES
- Ready for load: YES
- Loaded: YES
- Fault Count: 0
External DC Input
- Faults: &H0101
- Ok for load: NO
- Ready for load: NO
- Loaded: NO
- Fault Count: 0
Internal Battery
- Faults: &H0000
- Ok for load: YES
- Ready for load: YES
- Loaded: NO
- Fault Count: 0
SynQor>
Discussion: Displays summary of each available input source and whether they appear ready to accept load
power. Note that External DC Input will be listed even if the DC input is not installed.
Command: STARTUP x
Description: Enable outputs after x seconds.
Sample Output: SynQor>STARTUP 5
Timed startup begun.
SynQor>
Discussion: Outputs will be enabled after the requested delay time. Maximum permissible value for enable
delay is 10,737,418 seconds, approximately 4 months. [This command is only available for
Communication Board Code Rev 2.0 and later.]
065-0000020 Rev D
Page 17 of 18
SynQor UPS Terminal Commands
Command: TEMPS?
Description: Display reported temperatures for internal subsystems.
Sample Output: SynQor>TEMPS?
AC/DC Temperature 1 = 30 C
AC/DC Temperature 2 = 29 C
Control Brd Temp = 25 C
DC/AC Temperature = -50 C
Battery Temperature = 24.8 C
SynQor>
Discussion: Displays measured temperature for installed components. Note that unpowered components
will display invalid results. For example, in the sample above, the output voltage is disabled, so
the DC/AC readback temperature is invalid.