PIBR-0A930-1014-SITRANS-T.pdf

More information:
www.siemens.com/sitranst
www.siemens.com/processinstrumentation
siemens.com/sitranst
Siemens Industry, Inc.
3333 Old Milton Parkway
Alpharetta, GA 30005
1-800-241-4453
[email protected]
Subject to change without prior notice
Order No.: PIBR-0A930-1014
All rights reserved
Printed in USA
© 2014 Siemens Industry, Inc.
The information provided in this brochure contains merely
general descriptions or characteristics of performance which
in actual case of use do not always apply as described or which
may change as a result of further development of the products. An obligation to provide the respective characteristics
shall only exist if expressly agreed in the terms of contract.
All product designations may be trademarks or product names
of Siemens AG or supplier companies whose use by third
parties for their own purposes could violate the rights of the
owners.
Intelligent sensing for every temperature
and condition
SITRANS T: highly accurate temperature sensors and transmitters
with unique communication capabilities
Answers for industry.
Meeting all of process industry‘s demands:
The SITRANS T family for
temperature measurement
Whether you seek faster processes, higher product quality or quality
control, optimized plant availability and safety, more efficient workflow
or lower costs – process industries need to master a variety of demands
for competitive advantage. Devices for measuring temperature are one
essential part to achieving these goals. With the product family SITRANS T,
Siemens offers you a complete spectrum of temperature sensors and
transmitters including comprehensive services – from a single source.
Your application requires individual components or complete solutions? No problem with SITRANS T. For every
application in the process industry: general purpose,
intrinsically safe or explosion-proof, SITRANS T delivers
highly accurate temperature sensors and transmitters
with globally recognized certificates. They are as easily
integrated in different control systems as configured.
They offer you flexibility as they are available as a complete measuring point with a widespread portfolio or as
transmitter for head-, rail- or field-mount installation.
Furthermore, they extend the offer with communications
capability and unique features as diagnostics displays.
And to make the portfolio perfect, Siemens supports you
with application and process know-how from worldwide
technical support to on-site servicing.
2
It’s all about communication – easy integration and
configuration of SITRANS T
With SITRANS T you benefit from continuous ease of use
and highest transparency – thanks to powerful software
and a range of communications capabilities that allow the
ultimate integration of field devices into the overall plant.
So the new WirelessHART temperature transmitter can
also be operated with SIMATIC PDM, based on a modern
EDD. Most devices are also integrated in third-party tools
like HART Communicator or AMS.
Most of our temperature transmitters use a communication based on industrial standards like HART, PROFIBUS PA
or FOUNDATION Fieldbus. The EDD (Enhanced Device
Description) technology is used to integrate these devices
in different process control systems like SIMATIC PCS 7.
For FOUNDATION Fieldbus, AMS offers easy integration.
For 4 - 20 mA devices without HART a special tool SIPROM
T is available for point-to-point communications. This tool
reflects the advanced operating philosophy and look and
feel of SIMATIC PDM, so that it is also familiar to the PDM
user.
SIMATIC PDM (Process Device Manager) is a consistent,
vendor-independent tool for operation, setup, maintenance and diagnostics of intelligent field devices. It uses
exactly these EDDs to operate devices with HART and
PROFIBUS PA communication.
3
Precision where the temperature takes place:
Intelligence on-site:
SITRANS TS temperature sensors
SITRANS T temperature transmitters
SITRANS TS temperature sensors are the perfect base for
accurate and secure temperature measurement. They support a very broad scope of different applications in the
process industries. Equipped with our head-mount transmitters, they provide easy system integration. With the
optional display a comfortable readout of the process
variable supports local operation and monitoring.
4
Benefits at a glance
• Broad portfolio support of all main applications
• Secure use in intrinsically safe and Ex d instrumented
plants
• Modular system for easy configuration
• Support with 4 - 20 mA, HART, PROFIBUS PA and
FOUNDATION Fieldbus
SITRANS T temperature transmitters are the first choice to
bring intelligence to your temperature sensor. The status
of your measurement is easy to monitor remotely or
locally. Unique support of maintenance such as two-color
diagnostics LED and test pins let you detect – with one
glance – suspect measurements and – with one touch –
you measure the current loop without interruption of the
measuring.
Benefits at a glance
• Support of various designs: head-, rail-, field-mount
• Easy integration in your system with 4 - 20 mA, HART,
PROFIBUS PA, FOUNDATION Fieldbus as well as
WirelessHART
• Extended diagnostics
• Maintenance benefits
5
The complete range
SITRANS TS temperature sensors
SITRANS T temperature transmitters
SITRANS TS500
SITRANS TS300
SITRANS TH
SITRANS TW
The industry temperature sensor series supports a wide
field of measurements, from simple applications up to
solutions for harsh environments. Designed as a modular
system of tubular or barstock thermowell, extension, connection head and optional transmitter and display, the
customers profit from the use of standard components for
individual applications. Intrinsic safe versions are available
as well as Ex d.
Our TS300 food and pharma temperature sensor product
series is featured with a wide range of appropriate process
connections – the classical method. With the clamp-on
temperature sensor Siemens strikes a new path. Comparable with built-in measurement regarding response time
and accuracy, the advantages – especially at small pipe
diameters – are obvious. No welding and welding validation, no process disturbance and easy dismantling for
recalibration.
Weak sensor signal, expensive compensation cables,
various I/O for each sensor type? The use of our SITRANS
TH for mounting in the connection head of the temperature sensor makes you forget that trouble. The sensor
signal is amplified and transmitted noise EMI-resistant to
the control system. With the full range of outputs 4 - 20
mA, HART, PROFIBUS PA, FOUNDATION Fieldbus you will
profit from easy integration in your process control
system. The galvanic insulation and the fault detection
provide a proper operation. Further benefits are the
outstanding maintenance options: extended diagnostics
and unique diagnostics displays that show the device
status at a glance. The technician simply connects an
ammeter via the test sockets and can then read the
output current without opening the measuring circuit.
International engineering is no problem with the broad
range of approvals e.g. for Europe, USA, Canada and
Brazil. Functional safety is certified for SIL 2/3
applications.
Looking for a Swiss army knife in temperature measurement? This real universal device is your choice. Multivoltage power supply, 4 - 20 mA, 2 - 10 V, HART,
relay output and individual curves are only an extract of
the features of that device.
SITRANS TR
You want to use the excellent features of the SITRANS TH
family but prefer centralized access to all connected measurement points in junction boxes or in the control room
close to the process? SITRANS TR family, the two-wire railmount transmitters, support this strategy in a perfect way.
6
SITRANS TF
You have extreme environmental conditions? Temperature
sensor mounted in an inconvenient location? With the rugged-built field device SITRANS TF, available in die-cast aluminum or durable stainless steel housing, harsh conditions are no problem. Mount your transmitter near the
sensor, but out of a hot zone of heat or vibration. Direct
on the plant floor easy readout of the metering is your
benefit.
SITRANS TF280
The SITRANS TF280 is a WirelessHART temperature transmitter that provides all measured process values as well as
diagnostics information, parameters and functions via
radio. The device is powered by an internal battery and
designed for ultra-low power consumption. Its compact
and rugged design makes it especially suitable for direct
mounting on tanks and pipes in remote parts of plants,
and on moving or rotating equipment for process monitoring or asset management applications.
7
SITRANS TS at a glance
SITRANS TH, TR, TW and TF at a glance
Installation
Type
SITRANS TS Insert
Measuring inser spares
Mineral-insulated execution (MIC)
SITRANS TS100
SITRANS TS200
SITRANS TS300
SITRANS TS500
SITRANS TS500
Wireless
SITRANS TH400
SITRANS TR200
SITRANS TR300
SITRANS TW
SITRANS TF
SITRANS TF280
Temperature Sensors with barstock
thermowell for high process load
Input
(connectable
sensors)
Pt100 resistance
thermometers
Resistance thermometers
Thermocouples
Resistance-type sensors
DC sources
Resistance thermometers
Thermocouples
Resistance-type sensors
DC sources
Resistance thermometers
Thermocouples
Resistance-type sensors
DC sources
Resistance thermometers
Thermocouples
Resistance-type sensors
DC sources
Resistance
thermometers
Thermocouples
Resistance-type sensors
DC sources
Resistance
thermometers
Thermocouples
Resistance-type sensors
DC sources
Resistance thermometers
Thermocouples
Resistance-type sensors
DC sources
Current sources
Pt100 resistance
thermometer
Output
4 - 20 mA
4 - 20 mA
4 - 20 mA, HART
PROFIBUS PA version
FOUNDATION Fieldbus
version
4 - 20 mA
4 - 20 mA, HART
0/4 - 20 mA, HART
0/2 - 10 V, HART
4 - 20 mA
4 - 20 mA, HART
PROFIBUS PA
FOUNDATION Fieldbus
WirelessHART
Local display
N/A
N/A
N/A
N/A
LCD (with version
4 - 20 mA and 4 - 20 mA,
HART)
back-lighted LCD
Power supply
8.5 - 36 V DC
(30 V for Ex)
11 - 35 V DC
(30 V for Ex)
11 - 35 V DC
(30 V for Ex)
9 - 32 V DC
(30 V for Ex and
17.5 V for FISCO)
11 - 35 V DC
(30 V for Ex ia)
11 - 35 V DC
(30 V for Ex ia)
115/230 V UC
or 24 V UC
DC 11/13,5 - 35V
(30 V for Ex ia and
17.5 V for FISCO)
Lithium thionyl battery
D-cell 3.6 V
Housing material
Molded plastic,
embedded electronics
Molded plastic,
embedded electronics
Molded plastic,
embedded electronics
Molded plastic,
embedded electronics
Molded plastic
Molded plastic
Molded plastic
Varnished die-cast
aluminum
or stainless steel
Varnished die-cast
aluminum
Ambient
temperature
–40...+85 °C
–40...+85 °C
–40...+85 °C
–40...+85 °C
–40 - +85 °C
–40 - +85 °C
–25 - +70 °C
–40 - +85 °C
–40 - +80 °C
Degree of
protection
IP40
IP40
IP40
IP40
IP20
IP20
IP20
IP67
IP65
Certificates
Europe (ATEX): Ex ia, ib, ic,
Ex n
USA (cFMus): IS, NI
Canada (cFMus): IS, NI
other certificates:
GOST,NEPSI,PESO
Europe (ATEX): Ex ia, ib, ic,
Ex n
USA (cFMus): IS, NI
Canada (cFMus): IS, NI,
NiFW, DIP
SIL 2 und SIL2/3
other certificates:
GOST,NEPSI,PESO,EXPLABS
Europe (ATEX): Ex ia, ib, ic
Ex n
USA (cFMus): IS, NI
Canada (cFMus): IS, NI,
NiFW, DIP
SIL 2 und SIL2/3
other certificates:
GOST,NEPSI,PESO,EXPLABS
Europe (ATEX): Ex ia, Ex n
Ex ib, Ex n
USA (cFMus): IS, NI
Canada (cFMus): IS, NI
other certificates:
GOST, PESO
Europe (ATEX): Ex ia or
Ex ib, Ex n
SIL 2 und SIL2/3
other certificates:
NEPSI
Europe (ATEX): Ex ia or
Ex ib, Ex n
SIL 2 und SIL2/3
other certificates:
NEPSI
Europe (ATEX): Ex (ia) or
Ex (ib)
SIL 1
other certificates:
GOST
Europe (ATEX): Ex ia,
Ex d, Ex n
USA: XP/DIP/NI/S
SIL 2 und SIL2/3 (4...20
mA/HART)
other certificates:
GOST,INMETRO,
NEPSI,KOSHA
R&TTE, FCC
SIMATIC PDM
•
PROFIBUS PA
FOUNDATION Fieldbus
•
•
HART / PROFIBUS PA/
FOUNDATION Fieldbus
•
Mineral-insulated version
In-pipe or clamp-on
Suitable for thermowells according
to DIN 43772 as well as
ASME B40.9-2001
Plant and machinery construction,
bearing temperature, surface
measurement
Plant and machinery construction,
bearing temperature, surface
measurement
For advanced hygienic
requirements
Vessel and pipes
Vessel and pipes
Vessel and pipes
Compression or soldering fittings:
G [1/4, 1/2]“; 1/2“NPT; M8x1;
M18x1.5
Surface mounting adapter for installation on flat surfaces pipes
Compression or soldering fittings:
G [1/4, 1/2]“; 1/2“NPT; M8x1;
M18x1.5
Surface mounting adapter for installation on flat surfaces pipes
In-pipe:
Clamp-flange; DIN 11851;
Varivent; BioControl; Neumo;
Ingold; spherical-welding-sleeve
Clamp-on:
collar 4…57 mm
strap up to 200 mm
Connection to thermowell:
G1/2“, 1/2“NPT
Compression fitting G1/2“; 1/2“NPT;
welded thread
G1/2“; G1“; 1/2“NPT;
welded flange
DN25PN40; 1RF150; 1.5RF150;
1.5RF300
1RF300; 1.5RF150; 1.5RF300
1/2” NPT
Europe+IEC EX:
• intrinsic safety “ia”, “ic”
• for flameproof enclosure “d”;
for dust protection by enclosure “t”
Europe+IEC EX:
• intrinsic safety “ia”, “ic”
Europe+IEC EX:
• intrinsic safety “ia”, “ic”
Output
Direct sensor signal
4...20 mA (TH100/TH200)
HART (TH300)
PA (TH400)
FF (TH400)
Direct sensor signal
Direct sensor signal
Direct sensor signal
4 - 20 mA (TH100/TH200)
HART (TH300)
PA (TH400)
FF (TH400)
Direct sensor signal
4 - 20 mA (TH100/TH200)
HART (TH300)
PA (TH400)
FF (TH400)
Direct sensor signal
4 - 20 mA (TH100/TH200)
HART (TH300)
PA (TH400)
FF (TH400)
316 SS Standard
Other materials available
Wetted material
SS similar 1.4404 (RTD),
2.4816 (Thermocouple)
(SS sim. 316L, Alloy 600)
SS similar 1.4404 (RTD),
2.4816 (Thermocouple)
(SS sim. 316L, Alloy 600)
SS similar 1.4404 (RTD),
2.4816 (Thermocouple)
(SS sim. 316L, Alloy 600)
In-pipe:
1.4404/316L
Clamp-on: no wetted parts
no wetted parts
1.4404; 1.4571
(316L; 316TI)
Form 4F: 1.4404; 1.4571
(316L; 316TI)
Form 4 additionally 1.7335; 1.5415
(A 182 F11; A 204 Gr.A)
Thermowell Form 2 or Form 3
(tapered) according to DIN 43772
and Form 2N; with thread, flange
or without process connection
Europe+IEC EX:
• intrinsic safety “ia”, “ic”
• flameproof enclosure “d”;
dust protection by enclosure “t”
• non-sparking “n”
Technical data
Operator input
Pt100 Basic: –30...+400 °C
Pt100 Extend: –196...+600 °C
Thermocouple: –196...+1100 °C
(depends on type)
Pt100 Basic: –30...+400 °C
Pt100 Extend: –196...+600 °C
Thermocouple: –196...+1100 °C
(depends on type)
Pt100 Basic: –30...+400 °C
Pt100 Extend: –196...+600 °C
Thermocouple: –196...+1100 °C
(depends on type)
In-pipe:
–30…+300 °C
Clamp-on:
–20…+160 °C
Pt100 Basic: –30...+400 °C
Pt100 Extend: –196...+600 °C
Thermocouple: –196...+1100 °C
(depends on type)
Pt100 Basic: –30...+400 °C
Pt100 Extend: –196...+600 °C
Thermocouple: –196...+1100 °C
(depends on type)
Pt100 Basic: –30...+400 °C
Pt100 Extend: –196...+600 °C
Thermocouple: –196...+1100 °C
(depends on type)
Handheld 375
•
FF version
•
•
HART / FOUNDATION
Fieldbus
AMS
•
FF version
•
•
Minimum response
time t0,5
2...6s
2...6s
2...6s
5s
Depends on type of thermowell
7...45s
20...45s
HART / FOUNDATION
Fieldbus
Ingress Protection
IP54
IP54
IP54
(some connetors lower)
IP65 (IP54 at some head types)
IP65 (IP54 at some head types)
IP65 (IP54 at some head types)
IP65 (IP54 at some head types)
SIPROM T and
special modem
Temperature limits*
8
Two-wire
SITRANS TH300
Mineralinsulated version
Certificates
Four-wire
SITRANS TH200
Temperature Sensors for installation
in without thermowells
Process connection
Two-wire
SITRANS TH100
Temperature Sensors for
Food&Beverage/Pharma
Spares
Two-wire
Field device
Type
Temperature Sensors in compact
version
Application
On DIN rail
SITRANS TS500
Temperature Sensors in cable
version
Temperature Sensors with tubular
thermowell for low to middle
process load
In the connection head
* Combination of loads (temperature, flow, vibration, pressure) lower this values partly extensive.
Further temperature limits are a result of the used thermowell materials
(e.g. 1.4571 / 316Ti resistant to compression stress until 450...550 °C, material limit 800 °C.)
9
•
•
•
Local configuration using
3 push buttons
4...20 mA
•
10
11