UL Report for Contactors 3RT103.pdf

File E31519
Project 97ME13811
Issued:
*Revised:
April 25, 1997
November 19, 1999
REPORT
on
MOTOR CONTROLLERS, MAGNETIC
Siemens AG
Amberg, Fed. Rep. Germany
Copyright © 1997, 1999 Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above-named company to reproduce
this Report provided it is reproduced in its entirety.
File E31519
Vol. 8
Sec. 1
and Report
Page 1
Issued: 1997-04-25
Revised: 2005-11-11
DESCRIPTION
PRODUCT COVERED
USL, CNL - Type No 3RT10, 3RT11, 3RT13, 3RT15 or 3RT16 followed by 33,
34, 35 or 36 followed by -1 or -3 followed by A, B, C, D, E, F, H, J, K, M, P,
Q, R, S or X followed by a character and a number followed by 0, 1, 2, 3, 4,
5, 6, 8 or 9, may be followed by -0LA2, -0GA0 or any Suffix Letters and/or
numbers.
USL, CNL - Accessory – terminal housing type 3RT1936-4EA2
GENERAL
These devices are open types 3 or 4 pole contactors for use in
industrial applications. Type 3RT1133 and 3RT1135 have additionally been
evaluated to IEC 60947-6, weld-free.
ENGINEERING CONSIDERATIONS (NOT FOR UL REPRESENTATIVE USE)
CNL - Indicates Investigated to Canadian National Standard(s) C22.2
No.14-M95
Note: CNL = Canadian National Standards - Listed.
USL = United States Standards - Listed.
RATINGS
Housepower 3RT1033
Voltage
115 V
200/208
230/240
460/480
575/600
V
V
V
V
1-ph
3-ph
FLA
LRA
2
3
5
---
-7.5
10
20
25
24 A
25.3 A
28 A
27 A
27 A
-210.5 A
225 A
225 A
225 A
1-ph
3-ph
FLA
LRA
2 hp
5 hp
5 hp
---
-10
10
25
30
24 A
32.2 A
28 A
34 A
32 A
-259
225
281
270
Horsepower 3RT1034
Voltage
115 V
200/208
230/240
460/480
575/600
V
V
V
V
hp
hp
hp
hp
A
A
A
A
File E31519 Vol. 8
Sec. 1
and Report
*Page 2
Issued: 4-25-97
Revised: 12-1-00
Horsepower 3RT1035
Voltage
115 V
200/208
230/240
460/480
575/600
V
V
V
V
1-ph
3-ph
FLA
LRA
3 hp
5 hp
7 1/2 hp
---
-10 hp
15 hp
30 hp
40 hp
34 A
32.2 A
42 A
40 A
41 A
-259
337
337
330
1-ph
3-ph
FLA
LRA
3 hp
7 1/2 hp
10 hp
---
-15 hp
15 hp
40 hp
50 hp
32 A
48.3 A
42 A
52 A
52 A
-388
337
412
412
A
A
A
A
FLA
22
22 A
21 A
22 A
LRA
183
183
169
180
A
A
A
A
A
A
A
A
Horsepower 3RT1036
Voltage
115 V
200/208
230/240
460/480
575/600
V
V
V
V
Horsepower 3RT1033 or 3RT1034 (Elevator Control)
Voltage
120 V
230/240 V
460/480 V
575/600 V
1ph,1 pole
1 1/2 hp
3 hp
-
2ph, 2pole
1 1/2 hp
3 hp
-
3-ph
7 1/2hp
15 hp
20 hp
Horsepower 3RT1035 (Elevator Control)
Voltage
120 V
230/240 V
460/480 V
575/600 V
1 ph, 1 pole
2 hp
3 hp
-
1 ph, 2 pole
2 hp
5 hp
-
3-ph
10 hp
20 hp
25 hp
FLA
28
28 A
27 A
27 A
LRA
225
225 A
225 A
225 A
3-ph
12 hp
25 hp
30 hp
FLA
336
33.6 A
34 A
32 A
LRA
270
270 A
281 A
270 A
Horsepower 3RT1036 (Elevator Control)
Voltage
120 V
230/240 V
460/480 V
575/600 V
1 ph, 1 pole
3 hp
5 hp
-
2 ph, 2 pole
3 hp
5 hp
-
Horsepower 3RT1133 (Weld-Free according to IEC 60947-6 Standard)
Voltage
3-ph
FLA
LRA
200/208 V
230/240 V
460/480 V
7.5 hp
7.5 hp
15 hp
25.3 A
22 A
21 A
210.5 A
183 A
169 A
File E31519
Vol. 8
Sec. 1
and Report
*Page 2A
Issued: 4-25-97
Revised: 9-29-00
Horsepower 3RT1135 (Weld-Free according to IEC 60947-6 Standard)
Voltage
3-ph
FLA
LRA
200/208 V
230/240 V
460/480 V
10 hp
10 hp
25 h
32.2 A
28 A
34 A
259 A
225 A
281 A
Horsepower 3RT1336 (4 NO Main Contacts)
Voltage
3-ph
FLA
LRA
200/208 V
230/240 V
460/480 V
5 hp
7.5 hp
15 hp
17.5 A
22 A
21 A
140 A
183 A
169 A
Horsepower 3RT1535 (2 NO + 2 NC Main Contacts)
Voltage
3-ph
FLA
LRA
200/208 V
230/240 V
460/480 V
10 hp
15 hp
25 hp
32.2 A
42 A
34 A
259 A
337 A
281 A
3-ph
13 kVar
15 kVar
30 kVar
37 kVar
Current
36 A
36 A
36 A
36 A
Capacitive Switching 3RT1636
Voltage
200/208
230/240
460/480
575/600
V
V
V
V
1-ph
7.5 kVar
8.5 kVar
17 kVar
21 kVar
Main contacts: General Purpose
- type
- type
- type
- type
Rating
3RT1033,
3RT1034,
3RT1035,
3RT1036,
600
600
600
600
V
V
V
V
AC,
AC,
AC,
AC,
45
45
55
50
A
A
A
A
Auxiliary contacts: 1-, 2- or 4-pole auxiliary contact blocks Type
3RH1921 are top or side mounted, for ratings refer to File E44653 Vol. 11,
Sec. 2 or Vol. 12 Sec. 3. The auxiliary contact blocks are available as
factory assembled (removable or not removable design) or available as separate
devices for individual arrangements.
Coil Ratings: 24 through 600 V ac
12 through 250 V dc
Definite Purpose:
AC Resistance:
Electric Heating,
- type 3RT1033 45
- type 3RT1034 45
- type 3RT1035 55
- type 3RT1036 50
600 V ac, 250,000 c.
A
A
A
A
- type 3RT1336 600 V, 60 A
- type 3RT1535 600 V, 55 A
File E31519
Vol. 8
Sec. 1
and Report
Short Circuit Ratings:
Type No.
Fuse
3RT1033
3RT1034
3RT1035/3RT1535
3RT1036/3RT1336
3RT1133/3RT1135
3RT1636
1
2
Note:
Note:
max
max
max
max
max
max
125
125
150
200
125
125
A
A
A
A
A
A
Bkr
max
max
max
max
-
Circuit
TM1
125 A
125 A
150 A
200 A
Page 2B
Breaker
Bkr I2
max 10 A
max 10 A
max 50 A
max 100 A
-
Issued: 1997-04-25
Revised: 2005-05-10
Short
Circuit
5 kA
5 kA
5 kA
5 kA
5 kA
10 kA
Voltage
600
600
600
600
480
600
V
V
V
V
V
V
UL Listed inverse time circuit breakers
UL Recognized instantaneous trip circuit breakers manufactured by
Siemens, Type ED63A...
High Capacity Short Circuit Ratings:
Type No.
Fuse Rating
CB Rating (Bkr TM)
Size
Volt. Short Size
Volt. Short
[A]
[V]
[kA]
[A]
[V]
[kA]
3RT1033
60
600
100
60
480
65
600
60
600
25
3RT1034
60
600
100
60
480
65
600
60
600
25
3RT1035
80
600
100
80
480
65
600
80
600
25
3RT1036
100
600
100
125
480
65
600
125
600
25
3RV103/Size
Size
Volt.
[A]
[V]
25
480
25
600
32
480
32
600
40
480
40
600
50
480
50
600
S23
Short
[kA]
65
25
65
25
65
25
65
25
3
Note: For Siemens UL Listed Combination Motor Controller Type 3RV103 (Size
S2) covered in File E156943.
NEMA Ratings:
*
3RT1036 meets ratings for NEMA Size 2.
File E31519
Vol. 8
Sec. 1
and Report
Page 2C
Issued: 1997-04-25
Revised: 2005-05-10
Short Circuit Rating for Contactor, Fuse, Overload Relay combination according
To UL 60947-4-1, for type “2” co-ordination.
Contactor
Overload
Relay
Fuse
Class
LPJ
[A]
Voltage
for High
Fault
Current
High Fault
Current [kA]
according to
UL60947-4-1
Standard Fault
Current [kA]
according to
UL60947-4-1 at
600V
3RT1033
3RT1034
3RT1035
3RU1136-4E
3RU1136-4F
3RU1136-4G
60
60
70
600
600
600
100
100
100
5
5
5