UL Report for MSP 3RV1031 Type E Combo.pdf

File E156943
Project 97ME21192
January 19, 1998
REPORT
on
INDUSTRIAL CONTROL EQUIPMENT - COMBINATION MOTOR CONTROLLERS
Siemens Energy and Automation Inc.
Canton, GA
Copyright © 1998 Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above-named company to reproduce
this Report provided it is reproduced in its entirety.
File E156943
Vol. 1
Sec. 12
and Report
Page 1
Issued:
Revised:
1998-01-19
2003-06-05
DESCRIPTION
PRODUCT COVERED:
USL, CNL - Open Type Self-Protected Combination Motor Controllers, Cat.
No. 3RV1031 followed by combination of 4 and the letter A, B, D, E, F, G or H,
followed by A1 or A3, followed by 0, 1, 2, 3, 4, 5 or 8, may be followed by
additional numbers and letters.
GENERAL:
These device are open type manual combination motor controllers. They
are intended to provide motor disconnection means, motor branch-circuit shortcircuit and ground fault protection, motor control, and motor overload
*protection. These devices are suitable for use as Service Equipment.
These devices may also be used with Siemens Listed type 3RT contactors and 3RW
*solid state controllers. When used, the contactors and solid state
controllers have the same horsepower rating as the 3RV1031 devices with which
they may be used.
ENGINEERING CONSIDERATIONS (NOT FOR UL REPRESENTATIVE USE):
CNL - Indicates investigated to Canadian National Standard(s) C22.2
No. 14-M91.
Note:
CNL = Canadian National Standards - Listed
USL = United States Standards - Listed
RATINGS:
Maximum HP ratings
Voltage 50/60 Hz
1-phase
2-poles
3-phase
3-poles
115-120
200-208
230-240
460-480
575-600
5 @
10 @
10 @
-----
--15 @
20 @
40 @
50 @
These devices are suitable for Design E motors.
@ Suitable for controlling motors with a maximum motor nameplate full
load current of 50 Amps.
These devices are suitable for use on circuits capable of delivering the
following maximum short-circuit currents.
RMS Symmetrical Amperes
Voltage
25 kA
65 kA
65 kA
600 Y/347 V ac
480 Y/277 V ac
240 V ac
The trip rating is 125% of the dial setting (thermal range)