Operation for E5@N/E5@N-H/E5@N-HT
Operation for E5@N/E5@N-H/E5@N-HT
CSM_E5_N_E5_N-H_operation_TG_E_4_3
Operation
Setting Levels Diagram
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.
Control stops when you move from the operation level to the initial setting level.
Basic Type
E5CN/E5CN-U/E5AN/E5EN/E5GN
Power ON
Start in manual mode.
Start in automatic mode.
Press the O Key or the
PF Key for at least 1 s. *4
Operation
Level
Adjustment
Level
Press the
O Key less than 1 s.
a-m
PF Key
Manual
mode
*3
Press the O Key
for at least 3 s while
a-m is displayed.
(a-m will flash after
1st second.)
PF Key
Press the
O+ M
Keys for at
least 1 s.
c
25
100
*5
*4
Press the PF Key
for at least 1 s.
Manual
Control Level
*5
Monitor/Setting
Item Level
Press the
O+ M
Keys for at
least 3 s.
(Display
will flash
after 1st
second.)
Press the
O Key for
at least 1 s.
Control stops.
c
Press the O Key for at
least 3 s. (Display will flash
after 1st second.)
25
100
Protect Level
*1
Note: The time taken to
move to the protect
level can be adjusted
by changing the
“Move to protect level
time” setting.
Communications Setting
Level
Initial Setting
Level
Press the
O Key for less than 1 s.
Input password while
amoV is displayed. (Set
value −169)
Press the O Key
for at least 1 s.
Advanced Function
Setting Level
Control in progress
Input password.
Control stopped
Calibration Level
*2
Not displayed for some models
Level change
*1. You can return to the operation level by executing a software reset.
*2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel.
It can be done only by first turning OFF the power.
*3. From the manual control level, key operations can be used to move to the operation level only.
*4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/E5EN).
*5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/E5EN).
Error Displays (Troubleshooting)
When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below.
No.1 display
Meaning
Action
s.err (S. Err)
Input error
*2
A/D
converter
error *2
Check the setting of the input type. Also check the input wiring and check for broken
wires or short-circuits in the temperature sensor.
Turn the power OFF then back ON again. If the display remains the same, the controller
must be repaired. If the display is restored to normal, then a probable cause can be
external noise affecting the control system. Check for external noise.
Turn the power OFF then back ON again. If the display remains the same, the controller
must be repaired. If the display is restored to normal, then a probable cause can be
external noise affecting the control system. Check for external noise.
e333 (E333)
e111 (E111)
Memory
error
Status at error
Control output *1
Alarm output
Operates as above
OFF
the upper limit.
OFF
OFF
OFF
OFF
Note: If the input value exceeds the display limit (-1999 to 9999), though it is within the control range,
will be displayed under -1999 and
above 9999. Under these conditions, control output and alarm output will operate normally.
For details on the control range, refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156).
*1. If the control output is assigned to the transfer output and the transfer output type is set to the present value, the upper limit value will be output
for the present value when there is an input error.
*2. Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status.
1
Operation for E5@N/E5@N-H/E5@N-HT
Advanced Type
E5CN-H/E5AN-H/E5EN-H
Power ON
Start in manual mode.
Start in automatic mode.
Press the O Key or the
PF Key for at least 1 s. *4
Operation
Level
a-m
Manual
mode
*3
Press the O Key
for at least 3 s while
a-m is displayed.
(a-m will flash after
1st second.)
Adjustment
Level
Press the
O Key less than 1 s.
Press the
O Key less than 1 s.
PID Setting
Level
Press the
O Key less
than 1 s.
Bank Setting
Level
Press the PF Key
for at least 1 s. *4
Manual
Control Level
PF Key
Press the
O Key less
than 1 s.
Press
the O +
M Keys
for at
least 3 s.
(Display
will flash
after 1st
second.)
c
25.0
100.0
Protect Level
Press the O Key for at
least 3 s. (Display will flash
after 1st second.)
25.0
c
PF Key *5
Monitor/Setting
Item Level
*5
Press the O Key
for at least 1 s.
Press the O+
M Keys for at
least 1 s.
Note: The time taken to
move to the protect
level can be adjusted
by changing the
“Move to protect level
time” setting.
100.0
*1
Control stops.
Communications Setting
Level
Initial Setting
Level
Press the
O Key for less than 1 s.
Press the O Key
for at least 1 s.
Input password while
amov is displayed.
(Set value −169)
Advanced Function
Setting Level
Input password.
Control in progress
Control stopped
*2
Calibration Level
Not displayed for some models
Level change
*1. You can return to the operation level by executing a software reset.
*2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel.
It can be done only by first turning OFF the power.
*3. From the manual control level, key operations can be used to move to the operation level only.
*4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H).
*5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H).
Error Displays (Troubleshooting)
When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below.
No.1 display
Meaning
s.err (S. Err)
Input error
*2
e333 (E333)
e111 (E111)
Action
Status at error
Control output *1
Alarm output
Check the setting of the input type. Also check the input wiring and check for broken
wires or short-circuits in the temperature sensor.
OFF
Operates as above
the upper limit.
A/D
converter
error *2
Turn the power OFF then back ON again. If the display remains the same, the controller
must be repaired. If the display is restored to normal, then a probable cause can be
external noise affecting the control system. Check for external noise.
OFF
OFF
Memory
error
Turn the power OFF then back ON again. If the display remains the same, the controller
must be repaired. If the display is restored to normal, then a probable cause can be
external noise affecting the control system. Check for external noise.
OFF
OFF
Note: If the input value exceeds the display limit (-19999 to 32400), though it is within the control range,
will be displayed under -19999
and
above 32400. Under these conditions, control output and alarm output will operate normally.
For details on the control range, refer to the E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157).
*1. If the control output is assigned to the transfer output and the transfer output type is set to the present value, the upper limit value will be output
for the present value when there is an input error.
*2. Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status.
2
Operation for E5@N/E5@N-H/E5@N-HT
Programmable Type
E5CN-HT/E5AN-HT/E5EN-HT
Power ON
Start in manual mode.
Start in automatic mode.
Operation
Level
a-m
Press the O Key
for at least 3 s while
a-m is displayed.
(a-m will flash after
1st second.)
Manual
mode
Program
Setting Level
Press the
O Key less than 1 s.
Press the
O Key less than 1 s.
PID Setting
Level
Press the
O Key less
than 1 s.
Adjustment
Level
Press the
O Key less
than 1 s.
Press
the O +
M Keys
for at
least 3 s.
(Display
will flash
after 1st
second.)
Press the O+
M Keys for at
least 1 s.
c
Press the PF Key
for at least 1 s.
Manual
Control Level
c
25.0
100.0
Protect Level
Monitor/Setting
Item Level
Press the O Key
for at least 1 s.
25.0
Press the O Key for at
least 3 s. (Display will flash
after 1st second.)
Note: The time taken to
move to the protect
level can be adjusted
by changing the
“Move to protect level
time” setting.
100.0
Control stops.
Communications Setting
Level
Initial Setting
Level
Press the
O Key for less than 1 s.
Press the O Key
for at least 1 s.
Advanced Function
Setting Level
Input password.
Control in progress
Control stopped
Calibration Level
Not displayed for some models
Level change
*1. You can return to the operation level by executing a software reset.
*2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel. It can be done only by first turning
OFF the power.
*3. From the manual control level, key operations can be used to move to the operation level only.
*4. When the PF Setting parameter is set to A-M. For the E5CN-HT, press the M+U Keys at the same time to implement the PF Key.
*5. When the PF Setting parameter is set to PFDP. For the E5CN-HT, press the M+U Keys at the same time to implement the PF Key.
Error Displays (Troubleshooting)
When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below.
No.1 display
Meaning
s.err (S. Err)
Input error
*2
e333 (E333)
e111 (E111)
Action
Status at error
Control output *1
Alarm output
Check the setting of the input type. Also check the input wiring and check for broken
wires or short-circuits in the temperature sensor.
OFF
Operates as above
the upper limit.
A/D
converter
error *2
Turn the power OFF then back ON again. If the display remains the same, the controller
must be repaired. If the display is restored to normal, then a probable cause can be
external noise affecting the control system. Check for external noise.
OFF
OFF
Memory
error
Turn the power OFF then back ON again. If the display remains the same, the controller
must be repaired. If the display is restored to normal, then a probable cause can be
external noise affecting the control system. Check for external noise.
OFF
OFF
Note: If the input value exceeds the display limit (-19999 to 32400), though it is within the control range,
will be displayed under -19999
and
above 32400. Under these conditions, control output and alarm output will operate normally.
For details on the control range, refer to the E5CN-HT/E5AN-HT/E5EN-HT Digital Controllers User's Manual Programmable Type (Cat. No. H169).
*1. If the control output is assigned to the transfer output and the transfer output type is set to the present value, the upper limit value will be output
for the present value when there is an input error.
*2. Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status.
3
Operation for E5@N/E5@N-H/E5@N-HT
Parameters
Basic Type
E5CN/E5CN-U/E5AN/E5EN/E5GN
Some parameters are not displayed depending on the
model of the Controller and parameter settings.
For details, refer to the E5CN/E5AN/E5EN/E5GN
Digital Temperature Controllers User's Manual Basic
Type (Cat. No. H156).
Starting in manual mode.
PF Key *2
Power ON
Manual Control Level
Press the PF Key for
at least 1 s. *1
Adjustment
Level
Press the O
PID
Key or the PF
25 Control Key for at least
only
1 s.
*1
PV/MV
PF Key *2
Press the O Key for at least 3 s.
Other than the Auto/Manual Switch display
Starting in
automatic
mode.
Initial Setting Level
Press the
O Key for
at least 1 s.
C
Press the O Key less than 1 s.
in-t Input Type
5
Press the O Key less than 1 s.
M
in-h
Operation Level
Press the O Key less than 1 s.
C
0.0 Input Shift Value parameters.
2-point shift
M
Limit
insl Lower
Temperature
C
0.0 Input Shift Value
off
C
0.0
M
Burnout
hb1 Heater
Detection 1
M
i
M
d
M
Overcurrent
oc1 Heater
Detection 1
50.0
M
hb2
0.0
M
oc2
50.0
M
lcr1
0.0
0.0
M
hs1
Heating/cooling
M
c-db Dead Band
C
0.0
M
of-r
1.0
0.0
M
hs2
C
M
soak Soak Time
Leakage Current 2
Monitor
HS Alarm 2
1
M
wt-b
C
off
M
sp-0
M
mv-s
SP 0
M
sp-2
MV at Stop
M
Current 2
lcr2 Leakage
Monitor
MV at PV Error
SP used by
multi-SP
SP 2
M
sp-3 SP 3
C
M
sprt SP Ramp Set Value
off
M
ol-h
0
105.0
M
M
ol-l
MV Upper Limit
MV Lower Limit
M
orl MV Change Rate Limit
0.0
M
sqrp
0.0
M
C
Extraction of Square Root
Low-cut Point
Alarm Value
Upper Limit 2
M
Value
al2l Alarm
Lower Limit 2
C
M
al-3 Alarm Value 3
0
M
Value
al3h Alarm
Upper Limit 3
0
M
prst Program Start
C
rset
M
Value
al3l Alarm
Lower Limit 3
M
d-u
c
0
C
M
M
s-hc
M Initial Setting/
Protect:
icpt Communications
This protect level restricts movement
1 to the initial setting, communications
M levels.
Change Protect:
wtpt Setting
Protects changes to setups by
off operating the front panel keys.
M
Key Protect
pfpt PF
Restricts PF key operation
off (E5AN/E5EN only)
M
Mask Enable:
pmsk Parameter
Displayed only when a
on parameter mask is set.
M
to Move to Protect Level:
prlp Password
Password setting
0
M
Standard or
Heating/Cooling
stnd
M
st ST (Self-tuning)
on
M
ptrn
For input type of
temperature, standard
control, or PID
Program Pattern
off When assigning PID or
M
control output to ON/OFF
output
cp Control Period (Heating)
M
o MV Monitor (Heating)
20
M
c-cp
Set the ON/OFF
output cycle.
Control Period (Cooling)
20
M
orev Direct/Reverse Operation
or-r
Press the O and M Keys for at least 1 s.
Operation/Adjustment Protect:
oapt Restricts displaying and
modifying menus in operation,
0 adjustment, and manual control
levels.
Limit the set point
SP Lower Limit
onof
M
Move to Protect Level:
Displayed only when a password
0 is set. Restricts moving to protect
level.
M
sl-l
M
cntl PID ON/OFF
0.0
Protect Level
SP Upper Limit
-200
M
c-o MV Monitor (Cooling)
Note: The time taken to move to the protect
level can be adjusted by changing the
"Move to protect level time" setting.
Temperature Unit
°C, °F
For input type of
temperature
1300
0.0
M
Press the O and M Keys for
at least 3 s.
M
sl-h
C
0
M
sktr Soak Time Remain
Decimal Point
0 For input type of analog
0
C
setting, and advanced function setting
-5.0
M
al2h
0
0.0
pmov
0.0
0
C
M
mv-e
SP 1
0
C
M
Current 1
lcr1 Leakage
Monitor
Wait Band
0.0
0
M
sp-1
Heater Current 2 Value
Monitor
1.0
50.0
C
0.0
M Hysteresis settings
chys Hysteresis (Cooling)
50.0
M
lcr2
Manual Reset Value
Clear the offset during
M
hys Hysteresis (Heating)
C
C
0.0
M
ct2
M
al-2 Alarm Value 2
0
0.0
50.0 stabilization of P or PD
C
C
M
Current 1 Value
ct1 Heater
Monitor
PID settings
M
Value
al1l Alarm
Lower Limit 1
0
M
dp
0
M
Point During
sp-m Set
SP Ramp
Derivative Time
control.
HS Alarm 1
C
Integral Time
1.00
Heater Overcurrent
Detection 2
Leakage Current 1
Monitor
0
C
Multi-SP
Set Point Setting
M
Value
al1h Alarm
Upper Limit 1
0
0
M
c-sc Cooling Coefficient
Heater Current 2
Value Monitor
Heater Burnout
Detection 2
m-sp
40
0.0
C
Added when
auto/manual select
M addition is ON.
Press the
O Key
for at
least 3 s.
M
al-1 Alarm Value 1
0
M
Switch
a-m Auto/Manual
PID control only.
233
0.0
M
ct2
M
p Proportional Band
8.0
C
0
1-point shift
M
Set either
Limit
insh Upper
of these
Temperature
AT Execute/Cancel
M
Current 1
ct1 Heater
Value Monitor
M
Value/
25 Process
Set Point
C
0.0
off
M
cmwt Communications
Writing
ins Temperature Input Shift
run
Set either of these parameters.
M
at
C
M
in-l Scaling Lower Limit
r-s RUN/STOP
Process Value
Added when Additional
PV display is ON.
Set either of these parameters.
l.adj
25
Set either of these parameters.
C
Adjustment Level
Display
Displayed only
once when
entering
adjustment level.
Scaling Upper Limit
100
M
alt1
Press the O Key
less than 1 s.
Communications
Setting Level
C
Note: Displayed only for models with communications.
Changes are effective after cycling power or
after a software reset.
Alarm 1 Type
2
M
alh1
0.2
Alarm 1
Hysteresis
M
Setting:
psel Protocol
Switches between
cwf CompoWay/F (SYSWAY)
and Modbus.
M
u-no Communications Unit No.
1
M
Communications
bps Baud Rate
9.6
CompoWay/F
(SYSWAY) only
M
len Communications
Data Length
7
M
sbit Communications
Stop Bits
2
M
prty Communications Parity
even
M
sdwt
*1. When the PF Setting
parameter is set to A-M for a
Controller with a PF Key
(E5AN/E5EN).
*2. When the PF Setting
parameter is set to PFDP for a
Controller with a PF Key
(E5AN/E5EN).
Send Data Wait Time
20
M
4
Operation for E5@N/E5@N-H/E5@N-HT
Monitor/Setting Item Level
25
C
0
Monitor/Setting
Item Display 1
PF
(E5AN/E5EN only)
Monitor/Setting
Item Display 2
Monitor/Setting
Item Display 3
PF
Monitor/Setting
Item Display 4
PF
Monitor/Setting
Item Display 5
PF
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).
Press the O Key for at least 1 s.
alt2
Advanced Function Setting Level
Alarm 2 Type
0.2
2
M
alh3
C
0.2
M
mspu Multi-SP Uses
M
a2lt Alarm 2 Latch
M
spru
M
a3lt Alarm 3 Latch
SP Ramp Time Unit
Alarm 3
Hysteresis
M
Sequence
rest Standby
Reset
M
to Protect Level
prlt Move
Time
M
sb1n
M
sero Input Error Output
off
M
tr-h
Linear output
n-o
Transfer Output
Upper Limit
M
sb2n
100.0
M
Output
tr-l Transfer
Lower Limit
n-o
M
sb3n
0.0
M
o1-t Linear Current Output
4-20
n-o
M
hbu
Linear output
M
of Multi-SP Uses
ev-m Number
Two SPs: 1
none
M
ev-2
stop
on Method
M
Command
rlrv MB
Logic Switching
Auxiliary Output 3
Open in Alarm
off
M
colr PV Change Color
HB ON/OFF
red
off
M
Burnout
hbh Heater
Hysteresis
0.1
Event Input
Assignment 2
M
of Square
sqr Extraction
Root Enable
M
Junction
cjc Cold
Compensation
on
Event Input
Assignment 1
C
0.65
setting/communications
M protect is set to 0.
0.8
Move by setting password (−169).
C
M
at-h AT Hysteresis
0.8
M
a2on Alarm 2 ON Delay
M
a3on Alarm 3 ON Delay
M
a1of Alarm 1 OFF Delay
0
M
a2of Alarm 2 OFF Delay
0
M
Cycle MV
lcma Limit
Amplitude
20.0
M
inf Input Digital Filter
0.0
M
pvad Additional PV Display
off
M
o-dp
M
a1on Alarm 1 ON Delay
0
M
at-g AT Calculated Gain
0 Displayed when initial
5.0
0
M
alfa α
M
to Advanced
amov Move
Function Setting Level:
C
M
pv-b PV Stable Band
0
M
st-b ST Stable Range
15.0
off
M
hsh HS Alarm Hysteresis
0.1
M
a3of Alarm 3 OFF Delay
0
M
istp Input Shift Type
ins1
M
at Stop and Error
mvse MV
Addition
off
MV Display
off
M
Display
ret Automatic
Return Time
0
C
M
Select
amad Auto/Manual
Addition
off
M
rt RT
off
off
M
M
M
lbal LBA Level
M (E5AN/E5EN only)
pfd2 Monitor/Setting Item 2
M
pfd3 Monitor/Setting Item 3
0
M
pfd4 Monitor/Setting Item 4
0
8.0
C
M
pfd1 Monitor/Setting Item 1
0
M
lba LBA Detection Time
off
Auxiliary Output 2
Open in Alarm
M
hbl Heater Burnout Latch
1 Four SPs: 2
M
ev-1
Auxiliary Output 1
Open in Alarm
PF Setting
(E5AN/E5EN only)
1
off
3
a
tr-t Transfer Output Type
pf
a-m
M
hsl HS Alarm Latch
off
m
HS Alarm Use
on
off
off
M
alt3 Alarm 3 Type
hsu
off
off
M
2
alh2 Alarm
Hysteresis
C
a1lt Alarm 1 Latch
init Parameter Initialization
2
M
lbab LBA Band
3.0
M
pfd5
Monitor/Setting Item 5
0
M
Output 1
out1 Control
Assignment
M
spdp
M
out2
Control Output 2
Assignment
M
odsl MV Display Selection
Auxiliary Output 1
Assignment
M
Decimal Point
pvdp PV
Display
o
none
M
sub1
alm1
M
sub2
Auxiliary Output 2
Assignment
alm3
"PV/SP" Display
Screen Selection
o
on
M
PV Status Display
pvst Function
off
alm2
M
sub3
4
Auxiliary Output 3
Assignment
(E5AN/E5EN only)
M
csel Character Select
on
M
t-u Soak Time Unit
m
M
alsp Alarm SP Selection
sp-m
M
MV
manl Manual
Limit Enable
off
M
Rate of Change
pvrp PV
Calculation Period
4
M
csca
off
Automatic Cooling
Coefficient Adjustment
M
Status Display
svst SV
Function
off
M
Refresh
d.ref Display
Period
0.25
M
Output 1
ra1m Control
ON/OFF Count
0 Monitor
M
ra2m
Control Output 2
ON/OFF Count
0 Monitor
M
ra1
Control Output 1
ON/OFF Count
0 Alarm Set Value
M
Output 2
ra2 Control
ON/OFF Count
0 Alarm Set Value
M
Counter
rac ON/OFF
Reset
0
M
Overcurrent
ocu Heater
Use
M
to Calibration
cmov Move
Level
M
Overcurrent
ocl Heater
Latch
M
exfn Expansion Functions
on
0
off
0
M
och
M
0.1
Heater Overcurrent
Hysteresis
M
5
Operation for E5@N/E5@N-H/E5@N-HT
Advanced Type
E5CN-H/E5AN-H/E5EN-H
Some parameters are not displayed
depending on the model of the Controller and
parameter settings.
For details, refer to the E5CN-H/E5AN-H/
E5EN-H Digital Controllers User's Manual
Advanced Type (Cat. No. H157).
Power ON
Manual Control
Level
Protect Level
Operation
Level
Adjustment
Level
Initial Setting
Level
Communications Setting
Level
PID Setting
Level
Bank Setting
Level
Monitor/Setting
Item Level
Advanced
Function Setting
Level
Press the O Key less than 1 s.
Bank Setting Level
PID Setting Level
Press the O Key less than 1 s.
Display PID Selection
Press the O Key less than 1 s.
Display Bank Selection
d.bnk Bank0
d.pid PID1
1
d.pid
0
2 PID2
d.bnk Bank1
1
d.pid
d.bnk
d.
bnk
3 PID3
22 Bank2
d.pid
8
d.bnk Bank7
PID8
7
M
M
1.i
c
M
8.d
PID 1 Derivative Time
8.olh
M
8.oll
M
PID 1 Automatic Selection
1320.0 Range Upper Limit
PID 1 Cooling Coefficient
1.00
M
c
c
PID 8 Automatic Selection
1320.0 Range Upper Limit
M
PID 8 Cooling Coefficient
1.00
PID 1 LBA Detection Time
c
M
8.lba
0
M
c
7.pid
M
0.a3h
c
c
c
0.0
M
0.a1h
M
c
0.a3l
M
0.0
0.a1l
0.0
M
0.sok
M
1
M
0.a-2
M
1
M
0.a-1
0.0
PID 8 LBA Detection Time
0.a2l
0.a-3
c
0.wtb
Bank 7 SP
0.0
0.0
c
7.lsp
M
0.0
0.0
M
8.aut
8.csc
M
0
PID 8 MV Lower Limit
c
M
M
0.0
-5.0
1.aut
1.lba
c
105.0
PID 1 MV Lower Limit
-5.0
M
1.csc
PID 8 MV Upper Limit
c
M
0.spr
off
M
105.0
c
c
0.a 2h
0.0
0.pid
40.0
PID 8 MV Upper Limit
c
M
1
PID 8 Derivative Time
M
0.lsp
0.0
233.0
40.0
M
1.oll
c
M
8.i PID 8 Integral Time
PID 1 Integral Time
M
M
1.olh
M
PID 8 Proportional Band
8.0
233.0
1.d
M
8.p
c
7.a-2
c
7.a 2h
c
7.a2l
M
7.spr
Bank 7
0.0 Alarm Value 1
M
7.a1h
Bank 7
Alarm Value
0.0 Upper Limit 1
Bank 7
Alarm Value
0.0 Lower Limit 1
7.a1l
Bank 7
Alarm Value
0.0 Upper Limit 2
M
Bank 7 SP
off Ramp Set Value
M
7.a-1
Bank 7
0.0 Alarm Value 2
M
Bank 7 PID
Set No.
M
c
c
c
Bank 7
Alarm Value
0.0 Lower Limit 2
M
7.a-3 Bank 7
0.0 Alarm Value 3
c
c
M
M
7.a3h
Bank 7
Alarm Value
0.0 Upper Limit 3
M
7.a3l
Bank 7
Alarm Value
0.0 Lower Limit 3
M
7.sok
off
M
Set either of these parameters
PID 1 Proportional Band
8.0
Set either of these parameters
1.p
Set either of these parameters
c
Bank 7 Soak Time
1
c
M
7.wtb
Bank 7 Wait Band
off
M
6
Operation for E5@N/E5@N-H/E5@N-HT
Power ON
Starting in manual mode.
Manual Control Level
PID
Press the O
25.0 Control Key or the PF
100.0 only
Key for at least
1 s. *1
PV/MV
Press the PF Key
for at least 1 s.
Starting in
automatic
mode.
c
*1
Press the O
and M Keys for
at least 3 s.
Press the O Key less than 1 s.
at
off
c
c
8.0
M
i
AT Execute/Cancel
M
M
cmwt
d
M
irda
40.0
Infrared Communications Use
SP Mode
lsp
0.0
M
ct1
M
of-r
Heater Current 1
M
hys
Heater Burnout
1.0
0.0 Detection 1
M
oc1
M
chys
M
M
soak
Heater Overcurrent
50.0 Detection 1
ct2
Heater Current 2
M
hb2
0.0
M
oc2
50.0
Heater Burnout
Detection 2
mv-s
M
mv-e
M
hs1
M
sprt
Leakage Current 1
0.0 Monitor
0.0
M
hs2
50.0
0.0
HS Alarm 1
0.00
M
c
c
M
ol-h
Leakage Current 2
Monitor
105.0
ol-l
HS Alarm 2
-5.0
M
orl
Temperature Input Shift
M
c
Bank No.
0.0 Lower Limit 1
c
Remote SP Monitor
c
Set Point During
M
ct1
c
Heater Current 1 Value
M
c
ct2
Heater Current 2 Value
0.0 Monitor
lcr2
Alarm Value
M
al2l
Press the O
and M Keys for
at least 1 s.
Alarm Value
0.0 Lower Limit 2
0.0 Monitor
lcr1
al2h
0.0 Upper Limit 2
0.0 SP Ramp
M
al-3
0.0
Alarm Value 3
M
al3h Alarm Value
Leakage Current 1
0.0 Upper Limit 3
M
al3l Alarm Value
Leakage Current 2
0.0 Lower Limit 3
0.0 Monitor
M
M
MV at PV Error
Alarm Value 2
0.0
M
0.0 Monitor
MV at Stop
al-2
M
M
Wait Band
M
al1l Alarm Value
M
M
Soak Time
Alarm Value
0.0 Upper Limit 1
0.0
sp-m
Hysteresis settings
al1h
o
prst Program Start
rset
0.0
M
M
c-o
sktr Soak Time Remain
MV Monitor (Heating)
MV Monitor (Cooling)
0.0
0
M
M
v-m
SP Ramp Set Value
Valve Opening
Monitor
0.0
M
MV Upper Limit
Lower Limit
Temperature
Input Shift Value
0.0
MV Lower Limit
PF Key *2
MV Change Rate Limit
Monitor/Setting Item Level
(E5AN-H/E5EN-H only)
M
1-point shift
Upper Limit
Temperature
0.00 Input Shift Value
2-point shift
M
0.00
rsp
control.
Hysteresis (Heating)
c
M
c
Manual Reset Value
Clear the offset during
Auto/Manual Switch
PID control only.
Added when
auto/manual select
addition is ON.
0
Heating/cooling
Alarm Value 1
0.0
M
insh
insl
bank
al-1
M
off
M
ins
M
Dead Band
0.0
lcr1
M
lcr2
a-m
Press
the O
Key for
at least
3 s.
M
M
50.0
PID settings
Derivative Time
off
Heater Overcurrent
Detection 2
M
c
M
1
M
wt-b
run
Process Value/
0.0 Set Point
Integral Time
1.0 Hysteresis (Cooling)
0.0 Value Monitor
r-s RUN/STOP
25.0
50.0 stabilization of P or PD
0.0 Value Monitor
M
hb1
c
M
c-sc Cooling Coefficient
M
c-db
M
Process Value
Added when Additional
PV display is ON.
M
1.00
off
spmd
25.0
Proportional Band
233.0
Communications
off Writing
c
p
Set either of these parameters.
M
Adjustment Level
Display
Displayed only
once when
entering
adjustment level.
Set either of these parameters.
l.adj
Operation Level
Set either of these parameters.
Adjustment Level
Set either
of these
parameters.
db
2.0
Position Proportional
Dead Band
oc-h
25.0 Monitor/Setting
Item Display 1
Monitor/Setting
Item Display 2
PF
PF
Monitor/Setting
Item Display 3
0.0
M
PF
Open/Close Hysteresis
0.8
M
sqrp
Extraction of Square
Root
0.0 Low-cut Point
M
Monitor/Setting
Item Display 4
PF
Monitor/Setting
Item Display 5
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to
5 parameters (advanced function setting level).
PF Key *2
*1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H).
*2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H).
7
Operation for E5@N/E5@N-H/E5@N-HT
Press the O Key for at least 1 s.
Press the O Key for at least 3 s.
Other than the Auto/Manual Switch display
Initial Setting Level
Press the O Key less than 1 s.
Press the O Key less than 1 s.
Protect Level
The time taken to move to the protect level
can be adjusted by changing the "Move to
protect level time" setting.
to Protect Level:
pmov Move
Displayed only when a password
0 is set. Restricts moving to protect
level.
M
Operation/Adjustment
Protect:
oapt Restricts displaying and
modifying menus in
0 operation, adjustment, and
M manual control levels.
icpt
0
M
Initial Setting/
Communications Protect:
This protect level restricts
movement to the initial setting,
communications setting, and
advanced function setting levels.
Change Protect:
wtpt Setting
Protects changes to setups
off by operating the front panel
keys.
M
pfpt
PF Key Protect
Restricts PF key operation
off (E5AN-H/E5EN-H only)
M
Mask Enable:
pmsk Parameter
Displayed only when a
on parameter mask is set.
M
Password to Move to
Protect Level:
0 Password setting
prlp
M
in-t
Communications
Setting Level
5
Input Type
Displayed only for models with communications. Changes
are effective after cycling power or after a software reset.
in-h
M
in-l
M
Scaling Upper Limit
dp
M
bps
7
d-u
c
Communications
Data Length
c
M
sbit
2
M
sl-h
c
Decimal Point
Temperature Unit
°C, °F
For input type of
temperature
M
s-hc
20
M
100.0
0.0
M
o1-t
Standard or
Heating/Cooling
ST (Self-tuning)
For input type of
temperature,
standard control, or
PID
Program Pattern
off
cp
c-cp
When assigning PID or
control output to ON/OFF
output
Control Period (Heating)
Set the ON/OFF
output cycle.
Control Period (Cooling)
20
M
orev Direct/Reverse Operation
or-r
M
alt1
2
0.2
M
Bank Numbers Used
M
ev-1
none
Event Input
Assignment 1
M
M
ev-3
none
Event Input
Assignment 3
M
ev-4
none
Event Input
Assignment 4
M
clfl
Closed/Floating
flot
M
calb
Motor Calibration
off
Alarm 1 Type
M
alh1
Linear output
M
stop
Valid Program Bank
20
M
Linear Current Output
Input
ev-2 Event
Assignment 2
M
7
Transfer Output
Lower Limit
4-20
1
M
Transfer Output
Upper Limit
M
tr-l
ev-b
pbnk
Linear output
M
M
st
M
ptrn
c
M
stnd
on
Alarm 3
Hysteresis
tr-t Transfer Output Type
tr-h
Limit the set point
M
sl-l SP Lower Limit
pid
Send Data Wait Time
M
alh3
off
SP Upper Limit
M
cntl PID ON/OFF
M
c
0.2
-200.0
even
Alarm 3 Type
2
1300.0
Communications
Stop Bits
M
prty Communications Parity
sdwt
alt3
M
M
Alarm 2
Hysteresis
M
Scaling Lower Limit
0 For input type of analog
Communications
Baud Rate
9.6
CompoWay/F
(SYSWAY) only
M
alh2
0.2
M
1
len
c
0
Communications Unit No.
Alarm 2 Type
2
100
Protocol Setting:
psel Switches between
cwf CompoWay/F (SYSWAY)
and Modbus.
u-no
alt2
M
M
mot
Travel Time
30
Alarm 1
Hysteresis
M
sqr
off
Extraction of Square
Root Enable
M
Move to Advanced Function
Level:
amov Setting
Displayed when initial
0 setting/ communications
M
protect is set to 0.
Move by setting password (−169).
8
Operation for E5@N/E5@N-H/E5@N-HT
Power ON
Manual Control
Level
Protect Level
Operation
Level
Adjustment
Level
Initial Setting
Level
Communications Setting
Level
PID Setting
Level
Bank Setting
Level
Monitor/Setting
Item Level
Advanced
Function Setting
Level
Press the O Key for at least 1 s.
Advanced Function Setting Level
o-dp
init
Parameter Initialization
off
SP Ramp Time Unit
m
a
Standby Sequence
Reset
3
HB ON/OFF
Heater Burnout
Hysteresis
off
ST Stable Range
M
0.65
M
AT Calculated Gain
M
c
PV Stable Band
M
Limit Cycle MV
Amplitude
M
0.0
00
Additional PV Display
M
M
odsl MV Display Selection
M
o
M
PID Set Automatic
Selection Hysteresis
pvdp
on
pvst
off
svst
off
Direct Setting of
off Position Proportional MV
M
pvrp
Control Output 2
Assignment
M
Auxiliary Output 1
Assignment
Auxiliary Output 2
Assignment
M
ra2m
Automatic Cooling
off Coefficient Adjustment
M
on
M
ocl
M
Soak Time Unit
Use
Heater Overcurrent
Hysteresis
pf
M
ra1
Control Output 1
ON/OFF Count
0 Alarm Set Value
ra2
Control Output 2
ON/OFF Count
0 Alarm Set Value
M
Counter
rac ON/OFF
Reset
0
M
a-m
Control Output 2
ON/OFF Count
0 Monitor
M
M
0.1
Control Output 1
ON/OFF Count
M
Heater Overcurrent
Heater Overcurrent
off Latch
och
Display Refresh
Period
0 Monitor
M
M
M
ra1m
csca
alm2
Character Select
0.25
SV Status Display
Function
M
PV Rate of Change
17 Calculation Period
ocu
M
PV Status Display
Function
M
Manual MV
Limit Enable
M
M
PV Decimal Point
Display
M
PV Dead Band
d.ref
m
Alarm 3 OFF Delay
PID Set Automatic
Selection Data
"PV/SP" Display
4 Screen Selection
M
t-u
M
M
spdp
pmvd
Control Output 1
Assignment
Monitor/Setting Item 5
Remote SP Input
Error Output
3.0
on
0
0
LBA Band
pfd5
M
csel
a2of Alarm 2 OFF Delay
a3of
lbab
Monitor/Setting Item 4
0
0.0
off
sub2
M
LBA Level
p-db
pfd4
M
SP Tracking
M
c
M
alm1
Alarm 3 ON Delay
a1of Alarm 1 OFF Delay
M
0.50
manl
sub1
0
Input Digital Filter
pidh
LBA Detection Time
Monitor/Setting Item 3
0
0
M
8.0
none
Alarm 2 ON Delay
M
a3on
pv
HS Alarm Hysteresis
M
out2
0
20.0
lbal
o
Alarm 1 ON Delay
M
a2on
pidi
out1
0
AT Hysteresis
0.8
M
PV Change Color
M
a1on
M
M
M
c
5.0
1.0
off
pv-b
off
pfd3
M
Remote SP
Lower Limit
off
0
M
c
M
rseo
lba
MB Command
Logic Switching
red
α
on
M
Monitor/Setting Item 2
M
Remote SP
Upper Limit
off
HS Alarm Use
M
Cold Junction
M
colr
sptr
0.1
M
rlrv
M
M
hsh
on Compensation
Method
15.0
pvad
Input Error Output
M
cjc
-200.0
RT
hsl HS Alarm Latch
off
M
inf
Time
rspl
pfd2
0
M
c
off
hsu
M
sero
off
lcma
Alarm 3 Latch
M
M
at-h
rt
prlt Move to Protect Level
M
c
on
1300.0
Auto/Manual Select
Addition
M
Alarm 2 Latch
off
Burnout
hbl Heater
Latch
at-g
amad
rsph
Monitor/Setting Item 1
M
Remote SP Enable
M
c
pfd1
1
off
MV at Stop and Error
Addition
M
M
on
alfa
off
a3lt
M
st-b
M
off
sb2n Auxiliary Output 2
n-o Open in Alarm
c
mvse
M
M
0.1
rspu
a2lt
sb1n Auxiliary Output 1
n-o Open in Alarm
hbh
M
off
M
hbu
ins1
a1lt Alarm 1 Latch
M
rest
M
M
off
Alarm SP Selection
sp-m
Input Shift Type
istp
Display
ret Automatic
Return Time
M
spru
alsp
MV Display
off
M
PF Setting
cmov
0
Move to Calibration
Level
M
exfn
Expansion Functions
0
M
9
Operation for E5@N/E5@N-H/E5@N-HT
Programmable Type
E5CN-HT/E5AN-HT/E5EN-HT
Some parameters are not displayed
depending on the model of the Controller and
parameter settings.
For details, refer to the E5CN-HT/E5AN-HT/
E5EN-HT Digital Controllers User's Manual
Programmable Type (Cat. No. H169).
Power ON
Manual
Control Level
Operation
Level
Program Setting
Level
Initial Setting
Level
Communications Setting
Level
Protect Level
Adjustment
Level
Monitor/Setting
Item Level
PID Setting
Level
Advanced
Function Setting
Level
Adjustment Level
Press the O Key less than 1 s.
Press the O Key less than 1 s.
PID Setting Level
Press the O Key less
than 1 s.
l.adj
at
d.pid PID1
1
d.pid
M
cmwt
2 PID2
off
d.pid
d.pid
8
M
1.p
M
1.i
c
M
8.d PID 8 Derivative Time
40. 0
8.ol h
PID 1 MV Lower Limit
-5. 0
M
1.aut
M
1.csc
Range Upper Limit
PID 1 Cooling
1. 00 Coefficient
M
1.lba
PID 1 LBA Detection
0 Time
M
c
PID 8 Automatic
Selection
1320. 0 Range Upper Limit
8.aut
M
8.c sc PID 8 Cooling
Coefficient
1. 00
M
8.lba PID 8 LBA Detection
0 Time
M
Fixed SP
M
ct1
0. 0
M
hb1
0. 0
Integral Time
PID settings
M Heating/cooling
c-db Dead Band
0.0
Manual Reset Value
Clear the offset during
500
. stabilization of P or PD
control.
of-r
M
oc2
M
hys
1. 0
Heater
Overcurrent
50. 0 Detection 2
c
M
lcr1 Leakage Current 1
Monitor
M
chys
1.0
c
M
wt-b
Hysteresis
(Heating)
Hysteresis settings
Hysteresis
(Cooling)
50 0
.
Wait Band
M
Current 2
lcr2 Leakage
Monitor
0. 0
M
0. 0
M
db Position
Proportional
2. 0 Dead Band
M
oc-h
Open/Close
Hysteresis
M
Extraction of
sqrp Square Root
M
stb
MV at Reset
Standby Time
0.00
M
SP
psps Program
Shift Value
0. 0
M
-200.0
M
ps1
-2 00.0
RSP 0 before
Correction
RSP 1 before
Correction
M
ps10
-2 00.0
RSP 10 before
Correction
M
0
bc1
M
mv-r
M
Change
orl MV
Rate Limit
bc0
of f
HS Alarm 1
-5. 0
ps0
M
c
M
ol-l MV Lower Limit
0. 0 Low-cut Point
Derivative Time
1.00
c
MV Upper Limit
105 0
.
0. 8
M
c-sc Cooling Coefficient
Heater Burnout
Detection 1
Heater Burnout
0. 0 Detection 2
M
Input Shift Value
M
p Proportional Band
400
.
M
hb2
0. 0
Limit
inslLower
Temperature
M
d
0. 0
M
hs1
1-point shift
Set
either
Upper Limit
of these
Temperature
0. 00 Input Shift Value parameters
M 2-point shift
23 3 0
.
Heater Current 1
Value Monitor
50.0 Detection 1
0.0
M
insh
M
i
M
ol-h
Temperature Input
Shift
8. 0
PID 8 MV Lower Limit
M
PID 1 Automatic
c
M
Current 2
ct2 Heater
Value Monitor
-5. 0
13 20. 0 Selection
c
SP Mode
PID 8 MV Upper Limit
10 5. 0
M
8.ol l
M
fs p
M
ins
0. 00
M
oc1 Heater
Overcurrent
M
PID 1 MV Upper Limit
105. 0
c
c
0. 0
233. 0
PID 1 Derivative Time
40. 0
M
1.oll
PID 8 Proportional Band
M
8.i PID 8 Integral Time
PID 1 Integral Time
M
M
1.olh
8.p
8. 0
23 3. 0
1.d
M
spmd
psp
M
PID 1 Proportional Band
8. 0
c
0. 00
Communications
Writing
off Use
PID8
HS Alarm 2
50 0
.
AT Execute/
Cancel
MV at PV Error
0.0
M
irda Infrared
Communications
3 PID3
c
mv-e
hs2
M
off
Display PID Selection
Adjustment Level
Display
Displayed only
once when
entering
adjustment level.
0
RSP Broken-line
Correction Value 0
RSP Broken-line
Correction Value 1
M
bc10
0
RSP Broken-line
Correction Value 10
M
10
Operation for E5@N/E5@N-H/E5@N-HT
Power ON
Starting in manual mode.
Manual Control Level
Press the PF Key
for at least 1 s.*1
c
Press the O Key
or the PF Key for
at least 1 s. *1
PID
25 .0 Control
100.0 only
PV/MV
Starting in
automatic
mode.
Press the O
and M Keys for
at least 3 s.
Press the O Key less than 1 s.
Operation Level
Program Setting Level
Operation Level
d.prg
d.prg
0
d.prg
1
Press the
O Key for
at least 3 s.
Display Program Selection
d.prg
2
7
c
s-n o
Number of Segments
8 Used, 1 to 32
c
25.0
ct 2
PV
0.0
Display Segment Selection, END or 0 to
Number of Segments −1
d.seg
d.seg
end
d.seg
0
d.se g
1
M
lcr 1
M
lcr 2
Switch
prg
M
Program Number
r-r
0
pid
styp
1
c
al-1
Alarm Value 1
c
0.0
M
c
Ral1h
0.0
M
Ra l1 l
c
0.0
M
Alarm Upper
Limit 1
Alarm Lower
Limit 1
al-2
Alarm Value 2
c
Alarm Upper
Limit 2
c
0.0
M
Ral2l
0.0
M
c
al-3
Alarm Lower
Limit 2
Alarm Value 3
0.0
M
c
Ral3h
0.0
Alarm Upper
Limit 3
M
al3l
c
0.0
Alarm Lower
Limit 3
M
Rrp t
0
sp
0
Segment n SP
Hold
Rpr
0.0
M
time
Segment n Ramp
Rate
Segment n Time
M
c- o MV Monitor (Cooling)
Hold
off
M
adv
0.0
M
V-m
Advance
Valve Opening
0.0 Monitor
off
M
stb m
Press the O
and M Keys for
at least 1 s.
0.0
M
0.0
M
c
M
o MV Monitor (Heating)
M
Remaining Standby
0.00 Time Monitor
M
Program
prg t Elapsed
Time Monitor
0.00
M
0.00
0.0
M
Ral2h
Segment n Format
Run/Reset
rst
M
No.
seg Segment
Monitor
ramp
M
M
Leakage Current 2
0.0 Value Monitor
M
PID Set No.
Leakage Current 1
0.0 Value Monitor
(See note.)
M
a-m Auto/Manual
7
Heater Current 2
0.0 Value Monitor
M
25.0 PV/SP
Program
Repetitions
lin k
end
M
Program Link
Destination
ts1 s
Time Signal 1
on1
Time Signal 1
ON Time
0 Set Segment
M
0.00
M
of1
M
rptm
Program Execution
0 Repetition Monitor
c
M
rsp Remote SP Monitor
0.0
Heater Current 1
ct1
0.0 Value Monitor
M
Time Signal 1
0.00 OFF Time
M
ts2s
0
Time Signal 2
Set Segment
M
on2
0.00
Time Signal 2
ON Time
M
of2
0.00
Time Signal 2
OFF Time
PF Key *2
Monitor/Setting Item Level
25 .0
0.0
Monitor/Setting
Item Display 1
(E5AN/EN-HT only)
Monitor/Setting PF
Item Display 2
PF
Monitor/Setting
Item Display 3
PF
Monitor/Setting
Item Display 4
PF
Monitor/Setting
Item Display 5
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to
5 parameters (advanced function setting level).
PF Key *2
*1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/EN-HT).
*2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/EN-HT).
11
Operation for E5@N/E5@N-H/E5@N-HT
Press the O Key for at least 1 s.
Press the O Key for at least 3 s.
Other than the Auto/Manual Switch display
Initial Setting Level
Press the O Key less than 1 s.
Press the O Key less than 1 s.
Protect Level
The time taken to move to the protect level
can be adjusted by changing the "Move to
protect level time" setting.
to Protect Level:
pmov Move
Displayed only when a password
is set. Restricts moving to protect
0
M
level.
Communications
Setting Level
Operation/Adjustment
0
M
9.6
0
dp
len
d-u
Setting Change Protect
sbit
2
M
prty Communications Parity
pfptPF Key Protect
off
M
c
Send Data Wait Time
sl-l
SP Lower Limit
M
Password to Move to
s-hc
0
M
Standard or
Heating/Cooling
stnd
Control Period (Heating)
M
Control Period (Cooling)
20
M
Alarm 1 Type
2
Alarm 2 Type
Hysteresis
Alarm 3 Type
Alarm 3
Hysteresis
0.2
M
M
Tt-u
Program Time Unit
Time/Rate of
t-pr Step
Rise Programming
pru
Time Unit of
Ramp Rate
m
rtsm Reset Operation
p-on
Operation after Power ON
cont
eset
Operation at End of Operation
M
M
off
Extraction of Square
Root Enable
rst
2
tr-t
sqr
Travel Time
M
M
alh3
30
M
M
Alarm 2
0.2
c
M
stop
2
M
alt3
Motor Calibration
M
M
alh2
calb
M
Alarm 1
Hysteresis
0.2
c
flot
M
time
M
alt2
clfl Closed/Floating
h-m
M
M
alh1
Input
ev-4 Event
Assignment 4
M
or-r
c
Event Input
Assignment 3
off
orev Direct/Reverse Operation
alt1
ev-3
mot
20
c-cp
Event Input
Assignment 2
off
M
cp
ev-2
none
M
pid
Level:
prlp Protect
Password setting
Event Input
Assignment 1
none
M
none
M
cntl PID ON/OFF
on
M
M
ev-1
M
SP Upper Limit
-200.0
M
M
Linear Current Output
none
1300.0
M
20
Parameter Mask Enable
Temperature Unit
M
sl-h
c
even
sdwt
M
Decimal Point
c
Communications
Stop Bits
o1-t
4-20
M
Communications
Data Length
Transfer Output
Lower Limit
M
Scaling Lower Limit
0
M
off
M
pmsk
Communications
Baud Rate
CompoWay/F
only
tr-l
0.0
0
M
M
7
M
wtpt
1
M
bps
Initial Setting/
Communications Protect
in-l
Transfer Output
Upper Limit
M
Scaling Upper Limit
100
M
Communications
Unit No.
tr-h
100.0
M
in-h
M
oapt Protect
Input Type
5
Protocol Setting:
psel Switches between
cwf CompoWay/F and
Modbus.
u-no
icpt
in-t
Displayed only for models with communications. Changes
are effective after cycling power or after a software reset.
pvst PV Start
sp
M
Transfer Output Type
amov
Move to Advanced Function
Setting Level
0
M
12
Operation for E5@N/E5@N-H/E5@N-HT
Power ON
Manual
Control Level
Operation
Level
Program Setting
Level
Initial Setting
Level
Communications Setting
Level
Protect Level
Adjustment
Level
Monitor/Setting
Item Level
PID Setting
Level
Advanced
Function Setting
Level
Press the O Key for at least 1 s.
Advanced Function Setting Level
init
Parameter Initialization
cjc
on
off
a
M
sb1n
n-o
Standby Sequence
Reset
colr
PV Change Color
sub2
c
pv-b
PV Stable Band
Auxiliary Output 2
Auxiliary Output 3
Open in Alarm
a2on Alarm 2 ON Delay
hbu
HB ON/OFF
a3on
hbl
Heater Burnout
Latch
a1of
Heater Burnout
Hysteresis
a2of
sb3n
n-o
0.1
M
alfa
at-g
at-h
20.0
M
inf
M
on
M
rt
Input Digital Filter
MV Display
M
ret
off
Automatic Display
Return Time
c
Move to Protect Level
Time
off
M
out1
o
out2
none
M
ocu
ocl
off
och
pf
0.25
ra2m
SV Status Display
Function
Display Refresh
Period
0
Control Output 1
ON/OFF Count
Monitor
M
0
Control Output 2
ON/OFF Count
Monitor
M
Manual MV
Limit Enable
ra1
Direct Setting of
Position Proportional MV
ra2
0
Control Output 1
ON/OFF Count
Alarm Set Value
M
0
Control Output 2
ON/OFF Count
Alarm Set Value
M
PV Rate of Change
rac
0
ON/OFF Counter
Reset
M
Automatic Cooling
Coefficient Adjustment
pend
Program End ON Time
0.0
M
Heater Overcurrent
Heater Overcurrent
Latch
s-u
Standby Time Unit
h-m
M
psad
off
Program SP Shift
Value Addition
M
Heater Overcurrent
0.1 Hysteresis
r-r
M
d.ref
PV Dead Band
rcad
off
RSP Broken-line
Correction
Display Addition
M
M
Control Output 2
Assignment
PV Status Display
Function
M
M
Control Output 1
Assignment
off
ra1m
M
LBA Band
M
Input Error Output
csca
svst
PID Set Automatic
Selection Hysteresis
on Use
M
M
sero
lbab
pvst
M
PID Set Automatic
Selection Data
M
lbal LBA Level
3.0
M
3
c
pvrp
off
M
Alarm 3 Latch
Remote SP Input
Error Output
M
LBA Detection Time
8.0
M
SP Tracking
17 Calculation Period
M
Alarm 2 Latch
off
prlt
HS Alarm Hysteresis
0
off
a3lt
M
lba
M
a2lt
pmvd
M
M
M
off
manl
off
0.1
a1lt Alarm 1 Latch
p-db
PV Decimal Point
Display
M
M
off
hsh
on
M
pidh
MV Display Selection
M
M
hsl HS Alarm Latch
off
pvdp
off
M
on
M
M
Remote SP
Lower Limit
off
pidi
"PV/SP" Display
Screen Selection
o
off
rseo
Monitor/Setting Item 5
M
odsl
0.0
HS Alarm Use
spdp
Remote SP
Upper Limit
M
RT
pfd5
3
0.50
M
hsu
sptr
Monitor/Setting Item 4
M
Remote SP Enable
M
Auto/Manual Select
Addition
off
Additional PV Display
rspl
pv
M
amad
rsph
pfd4
0
M
off
Limit Cycle MV
Amplitude
Alarm SP Selection
off
at Reset and Error
mvre MV
Addition
AT Hysteresis
off
o-dp
Input Shift Type
ins1
0.0
M
pvad
Alarm 3 OFF Delay
0
M
istp
rspu
Monitor/Setting Item 3
0
0
M
sp-m
-200.0
M
M
0.8
M
lcma
Alarm 2 OFF Delay
0
AT Calculated Gain
Character Select
1300 .0
M
M
1.0
M
alsp
pfd3
M
M
Alarm 1 OFF Delay
0
a3of
Auxiliary Output 3
Assignment
off
M
α
csel
Monitor/Setting Item 2
0
M
M
Alarm 3 ON Delay
0
0.65
M
sub3
Monitor/Setting Item 1
1
M
M
M
off
M
pfd2
on
0
on
M
hbh
Alarm 1 ON Delay
0
M
M
Auxiliary Output 2
Assignment
M
a1on
n-o
M
pfd1
alm3 (E5AN/E5EN-HT only)
5.0
M
Open in Alarm
sb2n
Auxiliary Output 1
Assignment
M
M
Auxiliary Output 1
Open in Alarm
alm1
alm2
M
red
M
c
sub1
M
M
rest
Cold Junction
Compensation
Method
PF Setting
cmov
0
Move to Calibration
Level
M
13