POWER-ONE LS1601-7R

S Series
100 Watt AC-DC Converters
Input voltage range from 85…264 V AC
1 or 2 isolated outputs up to 48 V DC
4 kV AC I/O electric strength test voltage
LGA
• Rugged electrical and mechanical design
• Wide input frequency range from 47...440 Hz
• Operating ambient temperature range
–40...71°C with convection cooling
Selection chart
Output 1
Output 2
Input voltage
Uo nom
Io nom
Uo nom
Io nom
Ui
[V DC]
5.1
12
15
24
24
30
48
12
15
24
[A]
16
8
6.5
4.2
4
3.2
2
4
3.2
2
[V DC]
12
15
24
[A]
4
3.2
2
[V AC]
85...264
85...264
85...264
85...264
85...264
85...264
85...264
85...264
85...264
85...264
www.power-one.com
Edition 4/04.2001
Type
LS 1001-7R
LS 1301-7R
LS 1501-7R
LS 1601-7R
LS 2320-7R
LS 2540-7R
LS 2660-7R
LS 2320-7R
LS 2540-7R
LS 2660-7R
Options
-9, E, D, V, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
-9, E, D, P, T, B1
1
Cassette Style
S Series
Input
Input voltage AC
Input frequency
Input voltage DC
Inrush current limitation
wide input range
85...264 V AC
47...440 Hz
88...372 V DC
by thermistor
Output
Efficiency
Output voltage setting accuracy
Output voltage switching noise
Line regulation
Load regulation
Minimum load
Current limitation
Operation in parallel
Hold-up time
Ui nom, Io nom
Ui nom, Io nom
up to 85%
±0.6% Uo nom
IEC/EN 61204, total
typ. 90 mVpp
Ui min...Ui max, Io nom
typ. ±0.3% Uo nom
Ui nom, 10...100% Io nom, symmetrical output load typ. 0.5% Uo nom
not required
0A
rectangular U/I characteristic
typ. 110% Io nom
by current limitation
Ui nom, Io nom
80 ms
Control and protection
Input fuse
Input undervoltage lockout
Input overvoltage lockout
Input transient protection
Output
Output overvoltage
Overtemperature
Output voltage adjustment
Inhibit
Status indication
not user accessible
varistor
no-load, overload and short circuit proof
suppressor diode in each output
switch-off with auto restart
4 AT
typ. 90% Ui min
typ. 109% Ui max
typ. 130% Uo nom
TC typ. 100°C
0...110% Uo nom
TTL input, output(s) disabled if open circuit
LEDs: OK, inhibit, overload
Safety
Approvals
Class of equipment
Protection degree
Electric strength test voltage
EN 60950, UL 1950, CSA 22.2 No. 950
I/case
I/O
O/case
O/O
class I
IP 30
2 kV AC
4 kV AC
1 kV AC
0.1 kV AC
IEC/EN 61000-4-2, level 4 (8/15 kV)
IEC/EN 61000-4-3, level x (20 V/m)
IEC/EN 61000-4-4, level 4 (2/4 kV)
IEC/EN 61000-4-5, level 3 (2 kV)
IEC/EN 61000-4-6, level 3 (10 V)
CISPR 22/EN 55022
criterion A
criterion A
criterion A
criterion A
criterion A
class B
EMC
Electrostatic discharge
Electromagnetic field
Electr. fast transients/bursts
Surge
Conducted disturbances
Electromagnetic emissions
www.power-one.com
Edition 4/04.2001
2
S Series
100 Watt AC-DC Converters
Environmental
Operating ambient temperature
Operating case temperature TC
Storage temperature
Damp heat
Vibration, sinusoidal
Shock
Bump
Random vibration
MTBF
Ui nom, Io nom, convection cooled
Ui nom, Io nom
–25...71°C
–25...95°C
–40...100°C
56 days
0.35 mm/5 gn
100 gn
40 gn
4.9 gn rms
500'000 h
non operational
IEC/EN 60068-2-3, 93%, 40°C
IEC/EN 60068-2-6, 10...60/60...2000 Hz
IEC/EN 60068-2-27, 6 ms
IEC/EN 60068-2-29, 6 ms
IEC/EN 60068-2-64, 20...500 Hz
MIL-HDBK-217F, GB, 40°C
Options
Extended temperature range
–40...71°C, ambient, operating
Electronic inrush current limitation
Output voltage adjustment
40...110% Uo nom, excludes feature R and vice versa
Input and/or output undervoltage monitoring, excludes option V
Input and/or output undervoltage monitoring (VME), excludes option D
Current sharing
Cooling plate
-9
E
P
D0…D9
V0, V2, V3
T
B1
Pin allocation
Pin
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
Vo1+
Vo1+
Vo1–
Vo1–
S+
S–
R
i
D
V
T
N
N
P
P
LS 4000
Output 1
Output 1
Sense
Sense
Control of Uo1
Inhibit
Save data
ACFAIL
Current sharing
Protective earth
Neutral
Phase
Vo2+
Vo2+
Vo2–
Vo2–
Vo1+
Vo1–
R
i
D
LS 5000
Output 2
T
N
N
P
P
Output 2
Output 1
Control of Uo1
Inhibit
Save data
Current sharing
Protective earth
Neutral
Phase
S10002
30 26 22 18 14 10
32 28 24 20 16 12
www.power-one.com
Edition 4/04.2001
6
8
4
3
Cassette Style
S Series
Mechanical data
Tolerances ±0.3 mm (0.012") unless otherwise indicated.
European
Projection
171.93 (DIN 41494) (6.77")
7 TE
5 TE
Test jacks
Option P (Uo)
Option D (Uto)
Option D (Uti)
111 (3U) 4.37")
Measuring point of
case temperature TC
100 (3.93")
M4
152 (5.98")
LED i
LED OK
LED IoL
168.5 (6.63")
25.9
(1.02")
09004
11.8 (0.46")
60 (2.36")
Accessories
Front panels 19" (Schroff/Intermas)
Mating H15 connectors with screw, solder, fast-on or press-fit terminals
Connector retention facilities and code key system for connector coding
Chassis or wall mounting plates for frontal access
Universal mounting brackets for chassis or DIN-rail mounting
www.power-one.com
Edition 4/04.2001
4