MEANWELL PLC-100-12

PLC-100
100W Single Output Switching Power Supply
series
Features :
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage / Over temperature
Built-in active PFC function
UL1310 Class 2 power unit
Cooling by free air convection
100% full load burn-in test
High reliability
Suitable for LED lighting and moving sign applications
Compliance to worldwide safety regulations for lighting
2 years warranty
110
F
M
M
MODEL
PLC-100-20
PLC-100-24
PLC-100-27
PLC-100-36
PLC-100-48
15V
20V
24V
27V
36V
48V
10.5 ~ 15V
14 ~ 20V
16.8 ~ 24V
18.9 ~ 27V
25.2 ~ 36V
33.6 ~ 48V
Note.6 5A
5A
4.8A
4A
3.55A
2.65A
2A
CURRENT RANGE
Note.6 0 ~ 5A
0 ~ 5A
0 ~ 4.8A
0 ~ 4A
0 ~ 3.55A
0 ~ 2.65A
0 ~ 2A
RATED POWER
Note.6 60W
75W
96W
96W
95.85W
95.4W
96W
RIPPLE & NOISE (max.) Note.2 150mVp-p
150mVp-p
150mVp-p
150mVp-p
150mVp-p
150mVp-p
200mVp-p
VOLTAGE ADJ. RANGE(ADJ V) 10.2 ~ 12V
12.8 ~ 15V
17 ~ 20V
20.4 ~ 24V
23 ~ 27V
30.6 ~ 36V
40.8 ~ 48V
CURRENT ADJ. RANGE(ADJ I) 3.75 ~ 5A
3.75 ~ 5A
3.6 ~ 4.8A
3 ~ 4A
2.6 ~ 3.55A
2 ~ 2.65A
1.5 ~ 2A
3.0%
3.0%
2.0%
2.0%
VOLTAGE TOLERANCE Note.3
3.0%
LINE REGULATION
1.0%
60ms/230VAC 30ms/115VAC at full load
HOLD UP TIME (Typ.)
Note.5 90 ~ 264VAC
47 ~ 63Hz
POWER FACTOR (Typ.)
PF>0.95/230VAC
EFFICIENCY (Typ.)
85%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
12V:0.8A/115VAC 0.4A/230VAC
COLD START 40A/230VAC
OVER CURRENT (Typ.) Note.4
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS Note.7
WITHSTAND VOLTAGE
PF>0.95/115VAC at full load
86%
89%
PF 0.9 at 70 ~ 100% load
88.5%
15V:0.9A/115VAC
88%
0.45A/230VAC
88%
20V ~ 48V:1.1A/115VAC
89%
0.55A/230VAC
<0.75mA / 240VAC
95 ~ 102%
Protection type : Constant current limiting, recovers automatically after fault condition is removed
13 ~ 16V
16.5 ~ 20V
22 ~ 27V
27 ~ 34V
30 ~ 36V
39 ~ 48V
52 ~ 64V
Protection type : Shut down and latch off o/p voltage, re-power on to recover
90
10
(RTH2)
Protection type : Shut down o/p voltage, re-power on to recover
-10 ~ +50
(Refer to output load derating curve)
20 ~ 95% RH non-condensing
-40 ~ +80
0.03%/
, 10 ~ 95% RH
(0 ~ 50
)
10 ~ 500Hz, 2G 12min./1cycle, period for 72min. each along X, Y, Z axes
UL1310 Class 2, EN61347-1, EN61347-2-13 independent,UL60950-1, TUV EN60950-1, UL879 ( listed in UL Sign Components Manual (SAM) )
CAN/CSA C22.2 No. 223-M91(except for 48V) approved
I/P-O/P:3.75KVAC
I/P-FG:1.88KVAC
O/P-FG:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
EMI CONDUCTION & RADIATION Compliance to EN55015, EN55022 (CISPR22) Class B
HARMONIC CURRENT
Compliance to EN61000-3-2,-3, Class C ( 70% load) ; EN61000-3-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN61547, EN55024, light industry level, (surge 4KV), criteria A
EMS IMMUNITY
MTBF
297.9Khrs min. MIL-HDBK-217F (25 )
DIMENSION
PACKING
NOTE
127 ~ 370VDC
FREQUENCY RANGE
LEAKAGE CURRENT
OTHERS
3.0%
1200ms, 80ms/230VAC 1200ms, 80ms/115VAC at full load
SETUP, RISE TIME
VOLTAGE RANGE
3.0%
2.0%
LOAD REGULATION
EMC
( except for 48V )
PLC-100-15
RATED CURRENT
SAFETY &
( for 48V only)
12V
CONSTANT CURRENT REGION Note.4 8.4 ~ 12V
INPUT
LPS
PLC-100-12
DC VOLTAGE
OUTPUT
SELV
EQUIVALENT
SPECIFICATION
200.5*70.5*35mm (L*W*H)
0.52Kg; 25pcs/14Kg/0.65CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Constant current operation region is within 50% ~100% rated output voltage. This is the suitable operation region for LED related applications, but please
reconfirm special electrical requirements for some specific system design.
5. Derating may be needed under low input voltage. Please check the derating curve for more details.
6. This is the maximum possible output current and power. Over load protection may be activated slightly below this level to comply with the requirement
of UL1310 class 2.
7. Safety and EMC design refer to EN60598-1, subject 8750(UL), CNS15233, GB7000.1, FCC part18.
File Name:PLC-100-SPEC 2009-01-12
PLC-100
100W Single Output Switching Power Supply
Mechanical Specification
Case No.981A
series
Unit:mm
200.5
70.5
20.63
6.26
20.93
2-R2.5
35
6.26
Fosc : 100KHz
Block Diagram
EMI FILTER
&
RECTIFIERS
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
PFC
CIRCUIT
+V
-V
O.L.P.
FG
O.L.P.
PFC
CONTROL
DETECTION
CIRCUIT
PWM & PFC
CONTROL
O.V.P.
Derating Curve
Static Characteristics
Ta=25
100
100
90
80
80
70
LOAD (%)
LOAD (%)
60
40
20
-10
0
10
20
30
40
50
AMBIENT TEMPERATURE ( )
60 (HORIZONTAL)
60
50
40
90
100
125
135
145
155 165
175
180
200
230
264
INPUT VOLTAGE (V) 60Hz
File Name:PLC-100-SPEC 2009-01-12