General purpose 10 amp Power Relay available in 2PCO Plug-in, PCB, chassis mount ■ Arc barriers prevent flashover between contacts ■ Manual operator for circuit testing option ■ LED operation indicator option ■ High reliability/long life expectancy ■ UL, CSA and TUV approvals PY M New od els General Purpose Power Relays Options and ordering codes PY 2 1 XXF General purpose power relay 230VAC For coil voltages see table 2 pole changeover 2 Plug-in 1 Printed Circuit Board 2 PRICE INFORMATION AND ORDERING Clear case XX P Manual operator R Lamp D Diode F Flange cover Specification Rated load Rated current Maximum switching voltage Maximum switching capacity Operate time Release time Maximum operate frequency Dielectric strength Ambient operating temperature Mechanical ser vice life Electrical ser vice life Contact material Power consumption Resistive 10A @ 240V AC/28V DC Inductive 7.5A @ 240V AC, 5A @ 28V DC 10A 240V AC/125V DC 2400VA, 280W 100VA, 140W 25m sec max 25m sec max 1800 ops/hr at rated load, 18,000 ops/hr mechanical 1500V AC 50/60Hz for 1 min -25 to +55˚C -25 to +40˚C 10 million ops minimum 100 000 ops at rated load AgCdO 1.2VA AC 0.9 watts DC Coil Data Rated Voltage 12 24 110 230 AC Coils Coil res. Ohms 40 160 3400 13600 DC Coils Rated current 100 mA 50 mA 11 mA 7.7 mA Coil res. Ohms 160 650 11000 _ Rated current 75 mA 37 mA 10 mA – PY 21.5 21.5 Outline dimensions (mm) 35.2 35.2 10 6 4.6 0.6 27.5 5 2 7 7 4 10 4 6 27.5 0.5 4.6 3 0.6 14.2 14.2 0.6 41.7 5 21.6 40.2 DIN Socket 9672 33.5 27 3.5 10 23.6 5 35.2 3.5 3 78 44 5 5 7 19.4 6 38 0.5 27.5 35 4 4.6 2 4 0.6 3.5 14.2 Clip included 41.7 PCB layout Terminal arrangement 14.2 2 3 4 5 6 8 ø2.5-8 10 5.5 7 3.4 PRICE INFORMATION AND ORDERING 4.6 7 13 4 1