LINEAGEPOWER ACE4000

ACE4000
3 Bay / 12 Kilowatt Power Shelf
Features:
• 3U High
• Up to 12,000W in a 19” Rack
• Single & Three Phase Input Models
• Fits 3 Hot-Plug / N+1 Redundant Rectifiers
• Current Sharing and Remote Sensing
• World-wide safety approvals
• Optional 1U Controller Available
FEATURES
BENEFITS
KEY MARKETS & APPLICATIONS
Single wire current sharing
Provide system stress balancing and increases reliability
Constant power characteristic
Better suited for battery charging applications
No Minimum Load
Eliminates need for pre-load resistors. Reduces cost of ownership.
Optional 1U High Controller
Addresses telecom application requirements for redundant operation
• Central Office • Telecom Access Nodes
• Satellite Hubs • Broadband Switchers • XDSL Access Networks
SPECIFICATIONS
Rack Model Number
Rectifier Module Part Number
• Cellular Base Stations
• Wireless
• RF Amplifiers
• PCS Installations
• Factory Automation
12,000 Watt Power Shelf for CAR4000 Front End Modules
ACE403
ACE403N
ACE433
ACE433N
CAR4010L1-1A
CAR4010K1-1A
CAR4010L1N-1A
CAR4010K1N-1A
CAR4030L1-1A
CAR4030K1-1A
CAR4030L1N-1A
CAR4030K1N-1A
Voltage Range
+43.2~52.8 VDC
+21.6~26.4 VDC
-43.2~52.8 VDC
-21.6~26.4 VDC
+43.2~52.8 VDC
+21.6~26.4 VDC
-43.2~52.8 VDC
-21.6~26.4 VDC
Output Current
250A @ +48Vout
500A @ +24Vout
250A @ -48Vout
500A @ -24Vout
250A @ +48Vout
500A @ +24Vout
250A @ -48Vout
500A @ -24Vout
Input Voltage
Maximum Input Current (per module)
Single Phase 180-264 VAC / 47-63 Hz
Three Phase 180-264 VAC / 47-63 Hz
25A @ Full Load and 180 VAC Operation (per module)
15A per phase @ Full Load and 180 VAC Operation (per module)
Maximum Output Power
12,000 Total Output Power (8,000 Watts Redundant Output Power)
AC Input Feeds
Individual Input Feeds for each rectifier for 4mm2 cable
Input Protection
Each CAR rectifier module is equipped with it's own internal fuse
Efficiency
90% typical at 230VAC
Regulation (Line & Load)
+/- 0.5% of V1
Ripple & Noise
1% of V1 (pk-pk) - using 10µF tantalum cap. and 0.1µF ceramic cap.
Load Sharing
Single wire. +/- 5% of nominal current
DC Bus
Rectifiers connected in parallel. Floating bus with common "+". Maximum current is 250A
Status Indicators
DC Good and Temperature OK (Green), AC Good (Amber)
Alarm Signals
Over Temperature, Over/Under Voltage, No Power, Module not present
Battery Interface
RJ45 signal connector per rectifier. RS232 for programming via laptop (with Controller).
Temperature Range
0 to 50°C at rated output power. Derates linearly to 60°C at 2.2% per °C
Shock & Vibration
Per MIL STD-810F, NEBS Compliant to GR 63 Core
EMI / EMC
Meets EN61000-3-2, -3 CISPR22 and FCC Part 15 Class A, Bellcore GR-1089-Core
Safety Approvals
UL: 478, 1012, 1950; CSA 22.2 No. 650; IEC: 380, 435, 950; VDE: 0804, 0806; & CE Mark (LVD)
Dimensions
Chassis Measures 18.00”/457.2mm (depth) x 17.165”/436.0mm (width) x 5.12”/132.1mm (height)
rev 100506
www.lineagepower.com/oem
Lineage Power
Lineage Power
Lineage Power (China)
3000 Skyline Dr.
Mesquite, TX 75149 Phone: (972) 284-2000
2841 Dow Avenue Tustin, CA 92780 USA Phone: (714) 544-6665
1353 Chenqiao Road, Shanghai Sengpu Industrial Park
Shanghai, 201401 China Phone: 021 6710 8910
ACE4000
3 Bay / 12 Kilowatt Power Shelf
18.00
(457.2)
Outline Drawing
18.00
(457.2)
Status / Control Connector
37 Pin D-Sub Connector
PIN
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
17.165
(436)
V1
FUNCTION
5vsbrtn
Temp.Ok1
PGood1
AcFail1
Present1
On/Off1
5vsbrtn
Temp.Ok2
PGood2
AcFail2
Present2
On/Off2
5vsbrtn
Temp.Ok3
PGood3
AcFail3
Present3
On/Off3
N/C
N/C
N/C
N/C
N/C
N/C
V1 Sense
RTN Sense
Margin 1
Margin 2
N/C
I-Share
RTN
N/C
5vsbrtn
5vsbrtn
5Vsb
5Vsb
N/C
18.00
(457.2)
18.00
(457.2)
17.165
(436)
RTN
V1
5.18
(131.6)
5.18
(131.6)
L1 L2 L3
FRONT END POWER SHELVES (POSITIVE POLARITY)
RTN
-
V1
+
17.165
(436)
RTN
5.18
(131.6)
V1
5.18
(131.6)
5.18
(131.6)
L1 L2 L3
V1 RETURN
FRONT END POWER SHELVES (NEGATIVE POLARITY)
L1 L2 L3
FRONT END POWER SHELVES (POSITIVE POLARITY)
ELECOM SHELVES
RTN
-
V1
5.18
(131.6)
+
L1 L2 L3
FRONT END POWER SHELVES (NEGATIVE POLARITY)
PART NUMBER DEFINITION GUIDE
Example Part Numbers:
Part #
Type
Phase
Polarity
ACE403
Front EndSingle
Positive
ACE433
Front End
Three
Positive
ACE403N
Front EndSingle
Negative
ACE433N
Front End
Three
Negative
ACE403H
Front EndSingle
Positive
ACE433H
Front End
Three
Positive
ACE403NH
Front EndSingle
Negative
ACE433NH
Front End
Three
Negative
ACE 4 x 3 x x x xx - 1A
Series
4=4kW x 3Bays
12kW Total
Power 0 = 1Ø
Rev.
Blank=Non-Compliant
Y0=5 of 6 Compliant
Z0=6 of 6 Compliant
RoHS Compliance
3 = 3Ø
Input Phase
3 = 3 Slots
Output V
Blank = Bus Bar
H = Positronic (front-end only)
Backplane Connector
Blank = Front End
T = Rectifier
Type
Blank = Positive
N = Negative
Polarity
Backplane
Connector
Bus Bar
Bus Bar
Bus Bar
Bus Bar
Positronic
Positronic
Positronic
Positronic
ACE 4 x 3 x x x xx - 1A
rev 100506
Lineage Power
3000 Skyline Dr.
Mesquite, TX 75149 Phone: (972) 284-2000
Series
4=4kW x 3Bays
12kW Total
Power 0 = 1Ø
Rev.
Blank=Non-Compliant
Lineage Power
Y0=5 of 6 Compliant
Z0=6 of 6 Compliant
2841 Dow Avenue RoHS Compliance
3 = 3Ø
Tustin, CA 92780 USA Blank = Bus Bar
Input Phase
Phone: (714) 544-6665
H = Positronic (front-end only)
3 = 3 Slots
Backplane Connector
Output V
Blank = Front End Blank = Positive
www.lineagepower.com/oem
Lineage Power (China)
1353 Chenqiao Road, Shanghai Sengpu Industrial Park
Shanghai, 201401 China Phone: 021 6710 8910