MA-COM CGB-38

Catalog 1308242
Issued 3-03
P&B
CG series
CMOS IC Time Delay Relay
• Repeatability to .05%
• Choice of timing modes
– Delay on operate
– Delay on release
– Interval on
• Knob adjustable
• 10A output relay with DPDT contacts
• Various models time from 0.5 sec. to 100 min.
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Contact Data @ 25°C
Timing Modes
Delay on operate – Delay period begins when input voltage is applied. At
the end of the delay period, the relay will operate and will not release until
input voltage is removed. Reset occurs when input voltage is reapplied.
ON
OFF
N.O. RELAY
CONTACTS
ON
OFF
➛
INPUT
VOLTAGE
Arrangements: 2 Form C (DPDT).
Material: Silver-cadmium oxide alloy.
Rating: 10A @ 30VDC or 277VAC, resistive; 1/2 HP @ 250VAC;
1/3 HP @ 120VAC.
Expected Mechanical Life: 10 million operations.
Expected Electrical Life: 100,000 operations, min., at rated load.
➛
TIME
Initial Dielectric Strength
Delay on release – Input voltage must be applied continuously to operate
the internal relay. When the control switch is closed, the relay energizes.
When the control switch is opened, timing begins. When timing is
complete, the relay will de-energize. Time may be reset to zero during
timing by closing the control switch.
Between Open Contacts: 500V rms, 60 Hz.
Between All Other Conductors: 500V rms, 60 Hz.
CONTROL
SWITCH
Input Data @ 25°C
ON
OFF
N.O. RELAY ON
CONTACTS OFF
TIME
➛
➛
Interval on – The relay energizes and timing begins when input voltage is
applied. At the end of the time delay period the relay will de-energize.
Reset is accomplished by removing, then reapplying, the input voltage.
INPUT
VOLTAGE
ON
OFF
Voltage: 120VAC and 24VDC.
Power Requirement: AC Types: Typically less than 3 VA.
DC Types: Typically less than 3 W.
Transient Protection: Yes.
Reverse Voltage Protection: Yes.
Input Voltages & Limits @25°C
Voltage
Type
Nominal
Voltage
Minimum
Voltage
Maximum
Voltage
AC
DC
120
24
105
20
130
32
Note: DC voltage must be filtered (5% p-p ripple max. at nom. voltage).
AC models will operate on 50 or 60 Hz.
➛
N.O. RELAY ON
CONTACTS OFF
TIME
➛
Environmental Data
Temperature Range: Storage: -40°C to +85°C.
Operating: -10°C to +55°C.
Timing Specifications
Timing Ranges: From 0.5 to 5.0 sec. through 10 to 100 min.
Timing Adjustment: Knob adjustable.
Tolerance (for AC units add ±1/2 cycle 60 Hz.):
Knob Adj. Types:–0, +10% of max. specified at high end of timing range;
+0, –10% of min. specified at low end.
Delta Time (for AC units add ±1 cycle 60 Hz.): ± 2%, typ.; ± 5%, max.
Repeatability (including first cycle of operation):
AC: ± 0.1%, typ.; ± 0.5%, max.; but not less than ± 16 ms.
DC: ± 0.05% typ.; ± 0.1% max.; but not less than ± 3 ms.
Release Time: 30 ms, typ.; 45 ms, max.
Recycle Time: AC: 40 ms, typ.; 60 ms, max.
DC: 30 ms, typ.; 45 ms, max.
Dimensions are shown for
1220 reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Mechanical Data
Termination: 8- or 11-pin octal style plug.
Enclosure: Yellow plastic case. Knob adjustable types have dial scale for
reference only.
Sockets: Models with 8-pin base fit either 27E122 or 27E891 (snap-on)
screw terminal sockets. 11-pin types fit either 27E123 or
27E892 (snap-on) screw terminal sockets.
Weight: 8 oz. (227g) approximately.
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
Catalog 1308242
Issued 3-03
P&B
Ordering Information – Authorized distributors are more likely to stock boldface items listed below.
Delay on Operate Models
Voltage
120VAC
24VDC
Time
Delay on Release Models
Adjustment
0.5 to 5 Min.
1 to 10 Min.
5 to 50 Min.
10 to 100 Min.
5 to 50 Min.
Wiring Dia.
Knob
1
Knob
1
Part Number
Voltage
CGB-38-70005M
CGB-38-70010M
CGB-38-70050M
CGB-38-70100M
120VAC
CGD-38-30050M
Time
Adjustment
Wiring Dia.
Part Number
Knob
2
CGB-38-78010M
CGB-38-78050M
1 to 10 Min.
5 to 50 Min.
Interval on Models
Voltage
Adjustment
Wiring Dia.
Part Number
120VAC
0.5 to 5 Sec.
1 to 10 Min.
Time
Knob
1
CGB-38-79005S
CGB-38-79010M
24VDC
1 to 10 Min.
Knob
1
CGD-38-39010M
➛
Outline Dimensions
2.406 MAX.
(61.1)
➛
2.937 MAX.
(74.6)
➛
➛
➛
➛
.56
(14.2)
➛
.60
(15.2)
1.781 MAX.
(45.2)
➛
➛
➛
➛
Fig.1
8 Pin
➛
➛
+ INPUT _
(DC POLARITY INDICATED)
➛
➛
➛
Wiring Diagrams – Bottom Views (pins numbered clockwise from keyway)
EXT.
CONT.
SW*
_
+
INPUT
(DC POLARITY INDICATED)
Fig.2
11 Pin
* If control switch is closed when power is applied, relay will immediately energize. A 50 millisecond minimum switch closure is required. IMPORTANT: a dry circuit switch is recommemded. A
“dry circuit” switch is one rated to reliably switch currents of less than 50mA. Use of a switch rated for other than dry circuit may result in failure of the time delay relay to function properly.
** Note: input polarity for DC operation. For most reliable operation on AC, connect high side to “+” and low side to “–”.
Dimensions are shown for
reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
1221
Refer to inside back cover.