ETC EDM35V1D41

Panel Meters and Controllers
Panel Meter Modular
Series EDM 35
• Modular digital panel meter, 3 1/2-digit
• Indicating or controlling current, voltage,
resistance, temperature, tacho or frequency.
• Easy programming
• Programmable hysteresis and time delay
(up to 2 setpoints)
• Data hold
• Peak/valley function
• Password protection of programming parameters
• Stock-saving - several ranges on each input module
• IP 65 (front)
• Optional hardware lock of programming
• Optional high-efficiency red or green display
Product Description
Ordering Key
The EDM 35 is a 3 1/2-digit,
modular digital panel meter
where input and output modules can be combined to suit
many applications. Scaling
and setpoints are fully programmable and the program-
ming itself is very user-friendly. Furthermore, the EDM 35
includes peak/valley function
and password protection. The
housing is easy to mount and
ensures a protection degree
of IP 65.
Main unit
Range
Power supply
Relay output
Signal output
Options
Range AC Voltmeters:
V1A: 0 to 199.9 mV
V2A: 0 to 1.999 V
V3A: 0 to 19.99 V
V4A: 0 to 199.9 V
V5A: 0 to 600 V *
Range Ohmmeters:
R1D: 0 to 199.9 Ω
R2D: 0 to 1.999 kΩ
R3D: 0 to 19.99 kΩ
R4D: 0 to 199.9 kΩ
Range DC Ammeters:
A1D: -199.9 to +199.9 µA
A2D: -1.999 to +1.999 mA
A3D: -19.99 to +19.99 mA
A4D: -199.9 to +199.9 mA
A5D: -1999 to +1999 mA
A6D: -5.00 to +5.00 A
A7D: -10.00 to +10.00 A
Signal Output:
X: None
1: 4 to 20 mA
2: 0 to 20 mA
4: 0 to 10 V
5: Transducer power
supply 12 VDC
6: Transducer power
supply 24 VDC
Contact factory for other output signals
Options:
XX:
None
CX: High eff. red display
DX: Green display
XP:
Program lock
01-99: Special options
(assigned by factory)
EDM35V1D41XXX
Type Selection
Range DC Voltmeters:
V1D: -199.9 to +199.9 mV
V2D: -1.999 to +1.999 V
V3D: -19.99 to +19.99 V
V4D: -199.9 to +199.9 V
V5D: -600 to +600 V *
* Nominal voltage according to IEC 60664-1.
The measuring range includes 15% tolerance equal to 690 V.
Range AC Ammeters:
A1A: 0 to 199.9 µA
A2A: 0 to 1.999 mA
A3A: 0 to 19.99 mA
A4A: 0 to 199.9 mA
A5A: 0 to 1999 mA
A6A: 0 to 5.00 A
A7A: 0 to 10.00 A
Range Thermometers:
Pt 100:
P1C:
-100.0 to 199.9°C
P2C:
-100 to 850°C
P1F:
-148.0 to 199.9°F
P2F:
-148 to 392°F
P3F:
-148 to 1562°F
Thermocouple Type J:
-JC:
-100 to 760°C
-JF:
-148 to 1400°F
Thermocouple Type K:
-KC:
-100 to 1250°C
-KF:
-148 to 1999°F
Relay Output:
0: None
1: 1 Relay
2: 2 Relays
Power Supply:
3: 12 to 48 VDC
4: 230 VAC
5: 115 VAC
6: 48 VAC
7: 24 VAC
Specifications are subject to change without notice (27.10.99)
Range Frequency Meters:
F1X*: 5.0 to199.9 Hz
F2X*: 10.0 to 1999 Hz
*
Replace X with:
A for Namur input
B for NPN, PNP
& Contact input
C 600 VAC input
1
Series EDM 35
Type Selection (cont.)
Separate Ordering Numbers
Range Tachometers:
T1X*: 8.0 to 199.9 rpm @30 ppr**
T2X*: 5.0 to 199.9 rpm @60 ppr**
T3X*: 2.0 to 199.9 rpm @100 ppr**
T4X*: 20 to 1999 rpm @30 ppr**
T5X*: 10 to 1999 rpm @60 ppr**
T6X*: 10 to 1999 rpm @100 ppr**
Main unit
(mechanical parts included)
Red display (standard red)
Red display (high-bright red)
Green display
*
Replace X with:
A for Namur input
B for NPN, PNP & Contact input
** pulses per revolution
Input Specifications - General
Power supply
EMC
Immunity
Input modules supplied by
main unit
Electromagnetic
compatibility
Acc. to IEC 60801-4
Acc. to IEC 60801-5
Input modules
VDC
VAC
ADC
AAC
AAC/ADC 10 A
Ohm
Pt 100
Pt 100 850°C
Thermocouple Type J
Thermocouple Type K
Tachometer
Frequency meter
Output modules
1 Relay
2 Relays
Analog output
12/24 VDC excitation output
Power supply modules
12 to 48 VDC
24 VAC
48 VAC
115 VAC
230 VAC
Ordering number
5100511
5100512
5100510
5100530
5100531
5100532
5100533
5100534
5100535
5100536
5100539
5100537
5100538
5100540
5100541
5100561
5100562
5100560
5100526
5100524
5100523
5100522
5100521
5100520
Supply Specifications
General Specifications
Power supply AC
Rated operational voltage
Display
Frequency
Voltage interruption
Rated insulation voltage
Rated impulse withstand
voltage
Power supply DC
Rated operational voltage
Voltage interruption
Rated insulation voltage
Rated impulse withstand
voltage
Rated operational power
EMC
Immunity
Overvoltage cat. III (IEC 60664)
230 VAC ± 10%
115 VAC ± 10%
48 VAC ± 10%
24 VAC ± 10%
50/60 Hz ± 5Hz
≤ 20 ms
250 VAC basic rms
6 kV (1.2/50 µs) IEC 60664-1
12 to 48 VDC ±15%
≤ 10 ms (voltage = 10 VDC)
150 VDC basic
4.0 kV (1.2/50 µs) IEC 60664-1
< 7 VA
Electromagnetic
compatibility
Acc. to IEC 60801-4
Acc. to IEC 60801-5
Min./Max. indication
Overrange indication
Accuracy
Temperature drift
Scaling
Electrical input range
Display range
Decimal point position
Module connection
Environment
Degree of protection
Operating temperature
Storage temperature
Weight
Housing
Dimensions
Housing material
Front material
Colour
Approvals
2
With Program
Lock
5100630
5100631
5100632
5100633
5100634
5100635
5100636
5100639
5100637
5100638
5100640
5100641
7-segment LED,
height 14.2 mm
2 LEDs for indication of
relay ON
-1999/1999
EE (underrange: -EE)
See module specifications
See module specifications
Progr. within whole range
Progr. within whole range
Programmable
Screw terminals
IP 65 (front)
IP 20 (behind panel)
0° to +50°C. R.H. < 90%
non-condensing
-10° to +60°C. R.H. < 90%
non-condensing
Approx. 350 g
depends on modules used
48 x 96 x 89 mm
ABS/Polycarbonate blend
Polycarbonate
Black housing
Red front with red display
Grey front with green display
UL, CSA, SEV
Specifications are subject to change without notice (27.10.99)
Series EDM 35
Input Specifications - Modules
Voltmeters - AC/DC (5100531/5100530,
5100631/5100630)
Thermometers (5100536/5100537/5100538,
5100539/5100636/5100637/5100638/5100639)
Measuring Jumper
ranges
position
Range
Range code Resolution Input
imped.
AC DC
199.9 mV
1-4
7
1
0.1 mV
100 kΩ
1.999 V
2-5
8
2
1 mV
100 kΩ
19.99 V
2-5
9
3
10 mV
1 MΩ
199.9 V
3-6
10
4
0.1 V
1 MΩ
600 V *
5-6
12
6
1V
1 MΩ
* Nominal voltage according to IEC 664-1. The measuring
range includes 15% tolerance equal to 690 V.
Accuracy
AC voltmeter
DC voltmeter
Temperature drift
AC voltmeter
DC voltmeter
0.3% of reading ±3 dgt
0.2 % of reading ±2 dgt
±150 ppm/°C ±0.2 dgt/°C
±100 ppm/°C ±0.05 dgt/°C
Ammeters - AC/DC(5100533/5100532/
5100534, 5100633/5100632/5100634)
Measuring
ranges
Jumper
position
Range
code
AC
DC
Resolution
199.9 µA
1.999 mA
19.99 mA
199.9 mA
1999 mA
5.00 A
1-2
2-3
4-5
5-6
2-5
2-5
7
8
9
10
11
12
1
2
3
4
5
6
0.1 µA
1 µA
10 µA
0.1 mA
1 mA
10 mA
12
-
6
10 mA
10 mA
10 AAC
2-3
10 ADC
1-2
Accuracy
AC ammeter
AC ammeter (10 A)
DC ammeter
DC ammeter (10 A)
Temperature drift
AC ammeter
AC ammeter (2 A, 5 A)
AC ammeter (10 A)
DC ammeter
DC ammeter (2 A, 5 A)
DC ammeter (10 A)
Voltage drop
0.3% of reading ±3 dgt
0.5% of reading ±5 dgt
0.2 % of reading ±2 dgt
0.5% of reading ±5 dgt
±150 ppm/°C ±0.5 dgt/°C
±200 ppm/°C ±0.1 dgt/°C
±200 ppm/°C ±0.5 dgt/°C
±100 ppm/°C ±0.05 dgt/°C
±200 ppm/°C ±0.5 dgt/°C
±200 ppm/°C ±0.5 dgt/°C
< 200 mV (all ranges)
Specifications are subject to change without notice (27.10.99)
Reso- Accuracy
lution
Temperature
drift
0.1°C ± 0.2% of reading
± 2 dgt
0.2°F ± 0.2% of reading
± 4 dgt± 0.10 dgt/°F
± 0.2% of reading
± 4 dgt± 0.10 dgt/°F
±150 ppm/°C
± 0.05 dgt/°C
±180 ppm/°F
-148 to 392°F
±180 ppm/°F
Pt100, 850°C:
-100 to 850°C
1°C
-148 to 1562°F
2°F
±150 ppm/°C
± 0.05 dgt/°C
±180 ppm/°F
± 0.1 dgt/°F
Pt 100:
-100.0 to 199.9°C
-148.0 to 199.9°F
1°F
± 0.2% of reading
± 3 dgt
± 0.4% of reading
± 6 dgt
Thermocouple type J:
-100 to 760°C
1°C
± 0.1% of reading
± 4 dgt
-148 to 1400°F
1°F
± 0.1% of reading
± 8 dgt± 0.1 dgt/°F
Thermocouple type K:
-100 to 1250°C
1°C
± 3% of reading
± 3 dgt
-100 to -50°C
1°C
± 1% of reading
+ 5/-1 dgt
-50 to 780°C
1°C
± 0.1% of reading
± 3 dgt
780 to 1250°C
1°C
± 0.25% of reading
+ 1/-3 dgt
-148 to 1999°F
2°F
± 3% of reading
± 6 dgt± 0.1 dgt/°F
2°F
± 1% of reading
+ 10/-2 dgt
-58 to 1436°F
2°F
± 0.1% of reading
± 6 dgt± 0.1 dgt/°F
1999°F
2°F
± 0.25% of reading
+2/-6 dgt
±100 ppm/°C
± 0.05 dgt/°C
±180 ppm/°F
±100 ppm/°C
± 0.05 dgt/°C
±100 ppm/°C
± 0.05 dgt/°C
±100 ppm/°C
± 0.05 dgt/°C
±100 ppm/°C
± 0.05 dgt/°C
±180 ppm/°F
-148 to -58°F
±180 ppm/°F
± 0.1 dgt/°F
±180 ppm/°F
1436 to
±180 ppm/°F
± 0.1 dgt/°F
Ohmmeters (5100535, 5100635)
Measuring
ranges
Jumper
position
Rangecode
Resolution
199.9 Ω
1.999 kΩ
19.99 kΩ
199.9 kΩ
1-4
2-5
3-6
1-2
7
8
9
10
0.1 Ω
1Ω
0.01 kΩ
0.1 kΩ
Accuracy
Temperature drift
0.2% of reading ±2 dgt
±150 ppm/°C ±0.1 dgt/°C
3
Series EDM 35
Input Specifications - Modules (cont.)
Tachometers (5100540, 5100640)
Measuring
ranges
199.9 rpm @30 ppr*
199.9 rpm @60 ppr*
199.9 rpm @100 ppr*
1999 rpm @30 ppr*
1999 rpm @60 ppr*
1999 rpm @100 ppr*
Jumper
position
J4, 1-2
J5, 1-2
J6. 1-2
J4, 2-3
J5, 2-3
J6, 2-3
Range
code
7
8
9
10
11
12
Frequency Meters (5100541, 5100641)
Resolution
0.1 RPM
0.1 RPM
0.1 RPM
1 RPM
1 RPM
1 RPM
* pulses per revolution
Input selection
Namur
NPN, PNP, Contact
Accuracy
Temperature drift
Input impedance
Namur
NPN, PNP and Contact
Time constant (tc)
J1
J2
1% of reading ±5 dgt
± 200 ppm/°C
Measuring
ranges
199.9 Hz
1999 Hz
Jumper
position
J7
J8
Input selection
Namur
NPN, PNP, Contact
600 VAC
Accuracy
Temperature drift
Input impedance
Namur
NPN, PNP and Contact
600 VAC
Time constant (tc)
Range
code
7
8
Resolution
0.1 Hz
1 Hz
J1, J4 and J6
J2 and J5
J3
1% of reading ±5 dgt
± 200 ppm/°C
1 kΩ
5 kΩ
600 kΩ
1 sec.
1 kΩ
5 kΩ
1 sec.
Output Specifications
Excitation output (5100526)
Relay output 1 or 2 relays (5100561/5100562)
Power supply
Output voltage
12 VDC: jumper position
24 VDC: jumper position
Output current
12 VDC
24 VDC
EMC
Power supply
Output
Rated insulation voltage
Contact ratings (AgCdO)
Resistive
AC 1
DC 1
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
Immunity
Supplied by main unit
3 - 6, tolerance ±20%
1 - 4, tolerance ±20%
≤ 35 mA DC
≤ 20 mA DC
Electromagnetic
compatibility
Acc. to IEC 60801-4
Acc. to IEC 60801-5
Analogue output (5100560)
Measuring
ranges
Load
resistance
0 to 20 mA
4 to 20 mA
0 to 10 V
≤ 500 Ω
≤ 500 Ω
≥ 1,000 Ω
Accuracy
0 to 20 mA
4 to 20 mA
0 to 10 V
Temperature drift
Short-circuit protection
4
Supplied by main unit
1 or 2 SPDT relays
250 V basic rms
5 A, 250 VAC
5 A, 24 VDC
2 A, 250 VAC
3 A, 24 VDC
≥ 40 x 106 operations
≥ 105 operations
(at max. load)
max. 10 Hz (50% duty cycle)
Operating frequency
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
±1% of reading ±0.1 mA
±1% of reading ±0.1 mA
±1% of reading ±0.05 V
±200 ppm/°C
yes
Specifications are subject to change without notice (27.10.99)
Series EDM 35
Wiring Diagrams
*)
*)
*)
*)
*)
*)
Power
supply
5100520-23
*)
5100530
*)
5100536
Modules with type nos.
xxxx63x are equipped
with
Program
Lock
function.
*) Module position (slot) in
the base unit is indicated
by a drawing on the plastic cover.
5100524
5100526
*)
5100531
*)
5100532
*)
5100537
*)
5100538
Caution!
Since the input circuitry is not
galvanically isolated, the potential of the measured variable will be present on all connections to the unit (i.e.
"Hold" input). This is of special importance when measuring line voltage and current.
Specifications are subject to change without notice (27.10.99)
5100560
*)
5100533
*)
5100540
5100561
*)
5100534
5100562
*)
5100535
*)
5100541
Note.
By short-circuiting terminals
marked "HOLD" (supply module), it is possible to hold the
displayed value indefinitely
(hold function). The comparison of the input variable with
the alarm setpoint remains
active. To reactivate the display, remove the short-circuit.
5
Series EDM 35
Front Panel Description
2. Display
3 1/2-digit (maximum read-out 1999).
2
Alphanumeric indication by means of 7-segment display
for:
- Displaying of the measured value.
- Indication of programming parameters.
3
3. LED
- “1” and “2” LED indicators for alarm conditions.
1
4
1. Keyboard
« S »
«
»
«
»
4. Engineering unit
Screen for interchangeable unit label.The symbols in the
greyish areas are those available on the set of engineering
unit labels supplied with the EDM. (Engineering unit label to
be inserted by customer.)
Set/enter
Up
Down
Set-up and programming procedures are easily controlled
by the three pushbuttons.
Set/Enter key:
- Entry of variables.
- Selecting programming functions.
W = 08
MΩ = 16
mV = 01
kW = 09
Hz = 17
mbar = 25
% = 24 mm HG = 32
l/min = 33
cm = 40
m = 41
V = 02
MW = 10
kHz = 18
bar = 26
l/h = 34
kg = 42
ppm = 43
kV = 03
var = 11
RPM = 19
psi = 27
kg/min = 35
µA = 04
kvar = 12
m/s = 20
ata = 28
ton/h = 36
kA = 44
mA = 05
Mvar = 13
m/min = 21
ate = 29
m2/min = 37
cos φ = 45
A = 06
Ω = 14
°C = 22
kg/cm2 = 30
m2/h = 38
m3 = 46
mW = 07
kΩ = 15
°F = 23 mm H2O = 31
mm = 39
µs = 47
Up and Down key for:
- Display control.
- Increasing or decreasing programming value.
- Selecting programming functions and instrument
configuration together with the « S » key.
Operation Diagrams
Setpoint Operation
6
Scaling Operation
Specifications are subject to change without notice (27.10.99)
Series EDM 35
Modules and Slot Position
Mode of Operation
Depending upon the input
modules used, it is possible to
measure AC/DC (current or
voltage), resistance (the range
is selected with a jumper on
the input module) or temperature (Pt 100 or Thermocouple J/K). Without an output
module, the EDM is an indicator - by inserting an output module the EDM is a controller.
The input range and the display range are fully programmable, and so are the setpoint(s) if a relay output module is inserted. A hold function is available for freezing a
measured value. Passwords 0
to 99 are for overall programming while passwords 100 to
199 allow direct set-point programming outside the password protection. See user
manual for further details.
Settings
Programmable setting:
Jumper setting:
Rear view of main unit
Slot
#1
Slot
#2
Input Module:
VAC
VDC
AAC
ADC
10A AC/DC
Ω
Pt 100
Thermo couple
Tachometer
Frequency
Slot
#3
Output Module:
Excitation output
Analogue output
Slot
#4
Power Supply module:
24 VAC
48 VAC
115 VAC
230 VAC
12-48 VDC
Slot
#5
Output Module:
1 Relay output
2 Relay outputs
See user manual.
See user manual.
Overall Dimensions and Panel Cutout
Front view
Side view
Top view
Panel cutout
Panel
All dimensions in mm.
Specifications are subject to change without notice (27.10.99)