COOPER 170M2664

Bussmann
®
Square Body – DIN 43 653
10-400A
690V (IEC/U.L.)
Electrical Characteristics
Size
000
00
†
n
n
n
Rated
Current
RMS-Amps
10
16
20
25
32
40
50
63
80
100
125
160
200
250
315
25
32
40
50
63
80
100
125
160
200
250
315
350
400
I2t (A2 Sec)
Clearing
Pre-arc at 660V
3.8
7.2
11.5
19
40
69
115
215
380
695
1200
2300
4200
7750
12000
19
28.5
50
95
170
310
620
1000
1900
3400
6250
10000
13500
18000
25.5
48
78
130
270
460
770
1450
2550
4650
8500
16000
28000
51500
80500
130
195
360
640
1200
2100
4150
6950
13000
23000
42000
68500
91500
125000
Watts
Loss
3.0
5.5
7
9
10
12
15
16
19
24
28
32
37
42
52
6
7
9
10
12
15
20
25
30
35
45
55
60
70
7-11-01
SB01191
®
Ordering Information
-U/80
Without
Indicator
-/80
Visual
Indicator
-TN/80
Type T
Indicator
for Micro
170M1308
170M1309
170M1310
170M1311
170M1312
170M1313
170M1314
170M1315
170M1316
170M1317
170M1318
170M1319
170M1320
170M1321
170M1322
170M1358
170M1359
170M1360
170M1361
170M1362
170M1363
170M1364
170M1365
170M1366
170M1367
170M1368
170M1369
170M1370
170M1371
170M1372
170M2608
170M2609
170M2610
170M2611
170M2612
170M2613
170M2614
170M2615
170M2616
170M2617
170M2618
170M2619
170M2620
170M2621
170M1408
170M1409
170M1410
170M1411
170M1412
170M1413
170M1414
170M1415
170M1416
170M1417
170M1418
170M1419
170M1420
170M1421
170M1422
170M2658
170M2659
170M2660
170M2661
170M2662
170M2663
170M2664
170M2665
170M2666
170M2667
170M2668
170M2669
170M2670
170M2671
U.L. Recognition/CSA Component Acceptance on Size 000.
Interrupting rating 200kA (Estimated 300kA) RMS Symmetrical.
Watts loss provided at rated current.
Microswitch indicator ordered separately.
†
R
Curves
Carton
Qty.
Carton
Weight
(kg)
10
1.34
5
1.05
BIF #
17056310
17056312
1 kg = 2.2 lbs.
1 lb = 0.45 kg
Form No.
Page 1 of 2
BIF Doc #720013
Bussmann
®
Square Body – DIN 43 653
10-400A
690V (IEC/U.L.)
†
R
®
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K , given as
a function of applied working voltage,
E g , (RMS).
1.5
Arc Voltage
This curve gives the peak arc voltage,
U L , which may appear across the fuse
during its operation as a function of the
applied working voltage, E g , (RMS) at a
power factor of 15%.
1.4
1.2
103
9
8
7
6
K
1.0
0.5
0.4
1.0
Kp
0.8
UL
0.6
0.5
0.4
0.3
5
0.3
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current . The correction factor, K p ,
is given as a function of the RMS load
current, Ib , in % of the rated current .
0.2
4
0.2
Eg
Eg
3
200
100 200 300 400 500 600 690
300
400
500
Ib
0.1
600 690
30 40 50
60
70
80 90 100%
Dimensions
DIN 43 653: Type -U/80, -/80, -TN/80
Size
000
00
D
40
51
E
21
30
F
20
28
G
51
67
H
8
10
K
2
2
Dimension in mm.
1mm = 0.0394∑
1∑ = 25.4mm
54
Indicator*
D
K
G
100
78
E
H
F
*Indication for Size 00 Fuses is a red pin
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled.
This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right,
without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without
notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
7-11-01
SB01191
Form No.
Page 2 of 2
BIF Doc #720013