COOPER 10-315A

Bussmann
®
Square Body – DIN 43 620
690V (IEC/U.L.)
10-315A
®
Electrical Characteristics
Size
000
Rated
Current
RMS-Amps
10
16
20
25
32
40
50
63
80
100
125
160
200
250
315
Ordering Information
Pre-arc
Clearing
at 660V
Watts
Loss
DIN 000
Type T
Indicator
for Micro
3.8
7.2
11.5
19
40
69
115
215
380
695
1200
2300
4200
7750
12000
25.5
48
78
130
270
460
770
1450
2550
4650
8500
16000
28000
51500
80500
3.0
5.5
7
9
10
12
15
16
19
24
28
32
37
42
52
170M1558
170M1559
170M1560
170M1561
170M1562
170M1563
170M1564
170M1565
170M1566
170M1567
170M1568
170M1569
170M1570
170M1571
170M1572
I2t (A2S)
n Interrupting rating 200kA (Estimated 300kA) RMS Symmetrical.
n Watts loss provided at rated current.
n Microswitch indicator ordered separately.
Curves
Carton
Qty.
Carton
Weight
(kg)
10
1.30
BIF #
17056310
1 kg = 2.2 lbs.
1 lb = 0.45 kg
Rated Current
The rated current of this fuse range has been given with
copper conductors that have a current density of 1.3
A/mm2 (IEC 60269-4). For conductor cross section
according to IEC 60269-1, the fuses with a rated current
higher than 125A must be derated. Please contact
Bussmann for application assistance.
7-11-01
SB01191
Form No.
Page 1 of 2
BIF Doc #720016
Bussmann
®
Square Body – DIN 43 620
10-315A
690V (IEC/U.L.)
®
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K , given as
a function of applied working voltage,
E g , (RMS).
1.5
Arc Voltage
This curve gives the peak arc voltage,
U L , which may appear across the fuse
during its operation as a function of the
applied working voltage, E g , (RMS) at a
power factor of 15%.
1.4
1.2
103
9
8
7
6
K
1.0
0.5
0.4
1.0
Kp
0.8
UL
0.6
0.5
0.4
0.3
5
0.3
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current . The correction factor, K p ,
is given as a function of the RMS load
current, Ib , in % of the rated current .
0.2
4
0.2
Eg
Eg
3
200
100 200 300 400 500 600 690
300
400
500
600 690
Ib
0.1
30 40 50
60
70
80 90 100%
Dimensions
DIN 43 620: Type DIN 000
Dimension in mm.
1mm = 0.0394∑
1∑ = 25.4mm
54 Max
Indicator
15
48
79
21
6
35
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled.
This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right,
without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without
notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
7-11-01
SB01191
Form No.
Page 2 of 2
BIF Doc #720016