COOPER S505-6.3-R

HALOGEN
5 x 20mm Time-Delay, Ceramic Tube Fuses
HF
FREE
S505 Series
5 x 20mm fuse with
optional axial leads
Pb
Dimensions - mm
• Ratings above 6.3A have a maximum
0.81mm diameter lead
• With TR2 packaging code, leadwire
length is 19.05mm
Description
• Time-delay, high breaking capacity
• Available with optional axial leads
• Ceramic tube, silver-plated endcap construction (500mA-800mA),
nickel-plated brass endcap construction (1-12A)
• Optional sleeve is flexible flouropolymer (UL flammability rating VW-1).
Consult factory for details.
• 5 x 20mm physical size
• Designed to IEC 60127-2 (500mA-10A) & extension 12A
Electrical Characteristics
1.5In
2.1In
2.75In
4In
10In
Amps
Min
min.
Max
min.
Min
ms
Max
s
Min
ms
Max
s
<1A
60
30
250
80s
50
1A-3.15A
60
30
750
80s
95
4A-6.3A
60
30
750
80s
8A-12A
30
30
750
80s
Min
ms
Max
ms
5s
5
150
5s
10
150
150
5s
10
150
150
5s
10
150
Specifications
Product
Code
S505-500-R
S505-800-R
S505-1-R
S505-1.25-R
S505-1.6-R
S505-2-R
S505-2.5-R
S505-3.15-R
S505-4-R
S505-5-R
S505-6.3-R
S505-8-R
S505-10-R
S505-12-R
Voltage
Interrupting
Typical DC Cold
Typical
Rating
Rating at Rated
Resistance
Pre-arching
AC
Voltage (50Hz) AC1
(Ω)2
I2t (A2s)AC3
250
1500
0.5070
0.188X
250
1500
0.2370
0.632X
250
1500
0.1401
1.28
250
1500
0.1075
2.22
250
1500
0.0700
6.78
250
1500
0.0545
9.60
250
1500
0.0395
16.60
250
1500
0.0305
36.60
250
1500
0.0185
38.45X
250
1500
0.0131
71.30X
250
1500
0.0102
111X
250
1500
0.0077
228X
250
1500
0.0061
397
250
1000
0.0053
713.7X
1. Interrupting ratings: 500mA to 10A were measured at 70% to 80% PF on AC,12A was measured
at 100% PF on AC.
2. Typical DC Cold Resistance (measured at <10% of rated current).
3. Typical Pre-Arching I2t (measured at listed interrupting rating and rated voltage if not specified);
With "X" specified, the typical I2t value is measured at 10 times of rated current under DC.
1111 BU-SB11758
Page 1 of 2
Agency Information
•
•
•
•
•
•
•
UL Recognized Card: Guide JDYX2, File E19180, JDYX8, File E19180
CSA Component Acceptance: File 53787
SEMKO: File 816547, 1119019
VDE: File 40014091, 40024352, 40023140
BSI: File KM55676
IMQ: File CA03.00100 and CA03.00529
PES+JET: File 1641-31003-1009, 1641-31003-1010,
1641-31003-1011, 1641-31003-1012, 1641-31003-2001,
1641-31003-2002
• CCC: File 2002010207011295, CQC11012061930
• KC-Mark: File SU05011-4012A, SU05011-5004A
Ordering
• Specify packaging code (insert packaging code prefix before part number)
e.g., BK- (or BK1-/TR2-) S505-1-R
• Specify option codes if desired (for axial leads, insert “V” between catalog
series and amp rating) e.g., BK-S505-V-1-R
Typical
Voltage
Drop (mV)4
295
189
152.5
150
125
118.5
115
102.5
86.5
77.5
75
73
72
77
IMQ5
X
X
X
X
X
X
X
X
X
X
X
X
X
VDE SEMKO
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Agency Information
CCC/ PSE/
cURus CQC5 JET CSA5
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X6
X
X
X
X6
X
X
X
KC5
X
X
X
X
X
X
X
X
X
X
X
BSI
X
X
X
X
X
X
X
X
X
X
X
X
X
4. Typical Voltage Drop( Voltage Drop was measured at 20°C ambient temperature at rated current).
5. No room for "CSA" & "KC" on the fuse endcap for Non-V Rev. No room for "IMQ", "CQC' or "KC"
on fuse endcap for -V Rev.
6. CQC only.
Data Sheet 2037
Time-Current Curves
Packaging Code
Packaging Code Prefix
BKBK1TR2-
Description
100 fuses packed into a cardboard carton
1000 fuses packed into a poly bag
1500 fuses on tape and reel (19.05mm leadwire length)
Option Code
Option Code
-V
Description
Axial leads – copper tinned wire with nickel-plated brass endcaps
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Life Support Policy: Cooper Bussmann does not authorize the use of any of its products for use in life support devices or systems without the express written approval of an officer of the Company. Life support systems are devices which support or sustain life, and whose failure to perform, when properly used in accordance with instructions for use provided in the labeling, can be reasonably expected to result
in significant injury to the user.
© 2011 Cooper Bussmann
www.cooperbussmann.com
1111 BU-SB11758
Page 2 of 2
Data Sheet 2037