Green Power Solutions srl Phone: +39-011-988 2251 Fax: +39-011-988 1358 Web: www.gpsemi.it e-mail: [email protected] Via Venezia 34D - 10088 Volpiano (TO), Italy GOG9xx27 THREE PHASE AC-DC BRIDGE Fuse protection Blown fuse indicators with microswitch Over temperature switches Fan loss detection circuit Snubber for SCR's protections Extractible stacks for easy field service LINE VOLTAGE UP TO 690V DC OUTPUT CURRENT 2700 A GOG94027 400 V Line to line voltage Characteristic Conditions GOG95027 GOG96027 500 V 690 V Value Value IDC DC output current 2700 A 2700 A 2700 A Value VINS (rms) Insulation voltage 3000 V 3000 V 3000 V THYRISTOR CHARACTERISTICS VGT Gate trigger voltage Tj = 25 °C, V D = 5 V 3 V 3 V 3 V IGT Gate trigger current Tj = 25 °C, V D = 5 V 400 mA 400 mA 400 mA dV/dt Critical rate of rise off-state voltage Tj= 125 °C 1000 V/us 1000 V/us 1000 V/us VRRM Blocking Voltage Tj = 125 °C 1200 V 1600 V 2200 V FUSE TYPE: 2 x SIBA 2068132.800 VNF Rated voltage 690 V 690 V 690 V INF Rated current 800 A 800 A 800 A PVF Power loss At rated current 118 W 118 W 118 W I²t Total I2t At 660 V 2 480 kA s 2 480 kA s 2 480 kA s Width 500 mm 500 mm 712 mm Depth 275 mm 275 mm 395 mm Height 855 mm 855 mm 855 mm Mass 140 kg MECHANICAL AND THERMAL CHARACTERISTICS 140 kg 140 kg Ta max Max amb. op. Temp. 40 °C 40 °C 40 °C Tstg Storage temperature -40/60 °C -40/60 °C -40/60 °C Document GOG9xx27T001 THREE PHASE AC-DC BRIDGE GOG9xx27 T5 T4 T6 T2 T1 T3 A A B B The part numbering system is reported at the beginning of the Open Assembly section. Customisations are available on request. Please contact factory. In the interest of product improvement Green Power Solutions reserves the right to change any specification given in this data sheet without notice. Document GOG9xx27T001 THREE PHASE AC-DC BRIDGE GOG9xx27 FAN BOARD BROWN BLACK BLUE GREEN/YELLOW FAN 2 BLUE GREEN/YELLOW BROWN BLACK AC AC NO COM NC FAN 1 PE V3 1 2 U3 FAN CAPACITOR 1 32 2 31 FAN CAPACITOR Cooling: Fan type: Number of fans: Voltage: Current: Frequency: Noise: single phase axial 2 230 V 1.3 A 50/60 Hz 62 dBA U3-V3: MAIN SUPPLY PE: GROUND CONNECTION (GND) 31-32: FAN BOARD CONTACT (CLOSED WHEN FAN RUNNING) In the interest of product improvement Green Power Solutions reserves the right to change any specification given in this data sheet without notice. Document GOG9xx27T001