GOG9xx15 1 - Green Power Solutions

Green Power Solutions srl
Phone: +39-011-988 2251
Fax: +39-011-988 1358
Web: www.gpsemi.it
e-mail: [email protected]
Via Venezia 34D - 10088 Volpiano (TO), Italy
GOG9xx15
THREE PHASE AC-DC BRIDGE
Fuse protection
Blown fuse indicators with microswitch
Over temperature switches
Fan loss detection circuit
Snubber for SCR's protections
Extractible stacks for easy field service
LINE VOLTAGE UP TO 690V
DC OUTPUT CURRENT 1500A
GOG94015
400 V
Line to line voltage
Characteristic
Conditions
GOG95015 GOG96015
500 V
690 V
Value
Value
IDC
DC output current
1500 A
1500 A
1500 A
Value
VINS (rms)
Insulation voltage
3000 V
3000 V
3000 V
THYRISTOR TRIGGERING CHARACTERISTICS
VGT
Gate trigger voltage
Tj = 25 °C, V D = 5 V
3 V
3 V
3 V
IGT
Gate trigger current
Tj = 25 °C, V D = 5 V
300 mA
300 mA
300 mA
dV/dt
Critical rate of rise off-state voltage
Tj= 125 °C
1000 V/us
1000 V/us
1000 V/us
VRRM
Blocking Voltage
Tj = 125 °C
1200 V
1600 V
2200 V
FUSE TYPE SIBA 2068132.1000 / 2078132.1000
VNF
Rated voltage
690 V
690 V
690 V
INF
Rated current
1000 A
1000 A
1000 A
PVF
Power loss
At rated current
131 W
131 W
131 W
I²t
Total I2t
At 660V
2
860 kA s
2
860 kA s
2
860 kA s
Width
500 mm
500 mm
500 mm
Depth
275 mm
275 mm
275 mm
Height
855 mm
855 mm
855 mm
MECHANICAL AND THERMAL CHARACTERISTICS
Mass
70 kg
70 kg
Ta max
Max amb. op. Temp.
40 °C
40 °C
40 °C
Tstg
Storage temperature
-40/60 °C
-40/60 °C
-40/60 °C
Document GOG9xx15T002
70 kg
THREE PHASE AC-DC BRIDGE
GOG9xx15
T5
T4
T6
T2
T1
T3
A
A
B
B
The part numbering system is reported at the beginning of the Open Assembly section.
Customisations are available on request. Please contact factory.
In the interest of product improvement Green Power Solutions reserves the right to change any specification given in this data sheet
without notice.
Document GOG9xx15T002
THREE PHASE AC-DC BRIDGE
GOG9xx15
FAN BOARD
PE
V3
1
2
U3
FAN CAPACITOR
1
32
2
31
FAN CAPACITOR
BROWN
BLACK
BLUE
GREEN/YELLOW
FAN 2
BLUE
GREEN/YELLOW
BROWN
BLACK
AC
AC
NO
COM
NC
FAN 1
Cooling:
Fan type:
Number of fans:
Voltage:
Current:
Frequency:
Noise:
single phase axial
2
230 V
0.4 A
50/60 Hz
62 dBA
U3-V3: MAIN SUPPLY
PE: GROUND CONNECTION (GND)
31-32: FAN BOARD CONTACT (CLOSED WHEN FAN RUNNING)
In the interest of product improvement Green Power Solutions reserves the right to change any specification given in this data sheet
without notice.
Document GOG9xx15T002