Network - Gamewell

E3Point specifications
Toxic and Combustible Gas Detector
Network Platform (BACnet MS-TP, Modbus)
General Specifications
UsesWall or duct-mounted, BAS or controller networkable gas detector for monitoring carbon monoxide (CO),
nitrogen dioxide (NO2), hydrogen sulfide (H2S), oxygen (O2), methane (CH4), hydrogen (H2) and propane (C3H8).
(Note: E3Point network version replaces Vulcain model VA201T)
Size
20.56 x 14.90 x 6.72cm (8.09 x 5.87 x 2.65”) (H x W x D)
Power Requirement
24 Vac nominal (17-27Vac), 50/60 Hz, 0.4A; 24 Vdc nominal (20-38Vdc)
Relay Output
1 DPDT relay, 5A @ 250Vac; 5A @ 30Vdc
Communications
RS485 Modbus; BACnet MS-TP master
Operating Environment
Commercial, Indoor, Extreme Temperature Environments
Operating Temperature
H2S, NO2, O2, CH4, H2, C3H8: -40 to 50ºC (-40 to 122ºF)
CO: -20 to 50ºC (-4 to 122ºF); future available CO version: -40 to 50ºC (-40 to 122ºF)
Display
8 character, 2 line backlit LCD
Visual Indicators
Green LED: Power
Amber LED 1: Alarm/Fault
Amber LED 2: Alarm/Fault
Audible Alarm
85 dBA at 3 m (10 ft)
Accuracy
+/- 3% of full scale @ 25 C
Gases Detected, Detection Ranges and Alarm Levels
Gas
Resolution
CO (Carbon monoxide)
1 ppm
H2S (Hydrogen sulfide)
Range
Alarm A
Alarm B
Alarm C
0-250 ppm
25 ppm
200 ppm
225 ppm
0.1 ppm
0-50 ppm
10 ppm
15 ppm
20 ppm
NO2 (Nitrogen dioxide)
0.1 ppm
0-16 ppm
0.7 ppm
2 ppm
9 ppm
O2 (Oxygen)
0.1% vol.
0-25% vol.
19.5% vol.
22% vol.
22.5% vol.
H2 (Hydrogen)
0.5% LEL
0-100% LEL
25% LEL
50% LEL
90% LEL
CH4 (Methane)
0.5% LEL
0-100% LEL
25% LEL
50% LEL
90% LEL
C3H8 (Propane)
0.5% LEL
0-100% LEL
25% LEL
50% LEL
90% LEL
Enclosure
Polycarbonate
Certification
© 2009 Honeywell Analytics
CSA C22.2 No. 61010-1,
UL 61010-1; FCC part 15; ICES-003 issue 4
Ordering Information
Single-Gas, Surface-Mount
* Base unit and sensor cartridge sold together ** Base unit only; sensor cartridge sold separately
Part Number
Description
E3SBSCO*
E3Point, CO, Surface-mount, BACnet MS-TP, 24Vac/dc, -20 to 50ºC (-4 to 122ºF)
E3SB**
E3Point, Surface-mount, BACnet MS-TP, 24Vac/dc, -40 to 50ºC (-40 to 122ºF)
E3SMSCO*
E3Point, CO, Surface-mount, Modbus, 24Vac/dc, -20 to 50ºC (-4 to 122ºF)
E3SM**
E3Point, Surface-mount, Modbus, 24Vac/dc, -40 to 50ºC (-40 to 122ºF)
Duct-Mount
Part Number
Description
E3DBSCO*
E3Point, CO, Duct-mount, BACnet MS-TP, 24Vac/dc, -20 to 50ºC (-4 to 122ºF) E3DB**
E3Point, Duct-mount, BACnet MS-TP, 24Vac/dc, -40 to 50ºC (-40 to 122ºF) E3DMSCO*
E3Point, CO, Duct-mount, Modbus, 24Vac/dc, -20 to 50ºC (-4 to 122ºF) E3DM**
E3Point, Duct-mount, Modbus, 24Vac/dc, -40 to 50ºC (-40 to 122ºF) Sensor Cartridges
Part Number
Description
E3SCO
CO Cartridge -20 to 50ºC (-4 to 122ºF), Carbon Monoxide
E3NO2
NO2 Cartridge -40 to 50ºC (-40 to 122ºF), Nitrogen Dioxide
E3H2S
H2S Cartridge -40 to 50ºC (-40 to 122ºF), Hydrogen Sulfide
E3H2 H2 Cartridge -40 to 50ºC (-40 to 122ºF), Hydrogen
E302
O2 Cartridge -40 to 50ºC (-40 to 122ºF), Oxygen
E3M CH4 Cartridge -40 to 50ºC (-40 to 122ºF), Methane
E3P C3H8 Cartridge -40 to 50ºC (-40 to 122ºF), Propane
Examples of How to Order
To order a network version, surface-mount, BACnet MS-TP, CO detector, -20 to 50ºC (-4 to 122ºF): Order E3SBSCO
To order a network version, surface-mount, Modbus, H2S detector, -40 to 50ºC (-40 to 122ºF): Order E3SM + E3H2S
To order a network version, duct-mount, BACnet MS-TP, NO2 detector, -40 to 50ºC (-40 to 122ºF): Order E3DB + E3NO2