301PL SERIES

301PL SERIES
LOW PROFILE, PHOTOELECTRONIC
PLUG-IN SMOKE DETECTOR
DESCRIPTION
The FCI 301PL series low profile photoelectronic smoke
detector is specifically designed to meet the performance requirements of fire detection/alarm systems. The 301PL detector uses a state-of-the-art optical sensing chamber and is
designed so that LED failure will not cause an alarm. The detector is designed to provide open area detection, and when
installed in a two-wire base, is compatible with FCI fire
alarm control panels. The detector’s operation and sensitivity
can be tested in place.
The 301PL detector is of plug-in construction and plugs
into the same base as the FCI 301IL series ionization smoke
detectors, making both models interchangeable. Bases are
available for two-wire, four-wire, and 120 VAC four-wire operation, and also with an audible sounder.
Two visible LEDs on each detector flash every ten seconds
indicating that power is being applied to the detector. The
LEDs light steadily when the detector is in alarm. A remote
LED annunciator is available as an optional accessory.
The 301PL is UL Listed for mounting inside ducts up to a
velocity of 3,000 FPM.
Functional testing is performed by placing a test magnet
against the cover. The LED on the detector should light
within 30 seconds.
Field metering of detector sensitivity may be performed
with the aid of a voltmeter and Test Kit, Part No. 119-9010N.
APPROVALS
UL (Std 268)
FM
CSFM
S 1913
0X5A5.AY
Approved
•
•
•
•
•
•
•
•
•
•
FEATURES
Low Profile Construction
Easy Plug-in of the Head to Base
Tamper-resistant Feature
Test Switch
360o View Angle of Alarm LEDs
Compatible with FCI Control Panels
Audible Sounder Base (Optional)
Field Metering of Detector Sensitivity
Removable Insect Screen and Cover
for Field Cleaning
Insect-resistant Screening (.020"/.508
mm Openings)
TECHNICAL SPECIFICATIONS
Sensitivity
Operating voltage
Standby current
Operating temperature
Operating humidity
Air velocity
Construction
Diameter
Height
Weight
3.0 %/ft. (nominal)
8.5 - 35 VDC (24 VDC nominal)
120 uA maximum
32o to 120o F (0o to 49o C)
10 % - 93 % relative humidity
3,000 feet per minute maximum
Off-white flame retardant plastic
6.2 inches (15.5 cm) (flanged base)
1.7 inches (4.2 cm)
3.6 oz. (104 g)
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed
by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.
© 1997 All Rights Reserved
301 2nd Ave Waltham, MA 02451-1133 USA TEL: (781) 487-0088 FAX: (781) 370-4132
9020-0375/Ver. 1.4
FIRE CONTROL INSTRUMENTS, Inc.
MOUNTING
• On a 4-inch square box with or without
plaster ring. Minimum depth 1.5 inches.
• On a 3.5-inch octagonal box. Minimum depth
1.5 inches.
INSTALLATION
Place the detector into the detector base. Turn the detector clockwise until the detector locks into place.
To use the tamper-proof feature, break the smaller tab
on the scribed line in the tamper proof tab located on the
detector mounting bracket. Install the detector. To remove the detector from the base when using the tamper-proof feature, insert the blade of a small
screwdriver into the hole on the side of the base and
push the plastic lever away from the detector head. This
will allow the detector to be rotated counterclockwise
for removal. NOTE: The decorative ring must be removed in order to remove the head when using the tamper-proof feature.
The tamper-proof feature may be defeated permanently by breaking the plastic lever off the base.
NOTE: The number of two-wire smoke detectors
which can be accommodated per zone varies with different control panels. Consult the control panel instruction manual to determine the capacity.
Refer to NFPA 72, Chapter 5-3, “Smoke Sensing Fire
Detectors” for spacing, location of detectors and other
guidelines.
TESTING
MAINTENANCE
Detectors may be tested in the following ways:
• Place a test magnet against the detector as
directed in the installation instructions. The detector should go into alarm within 30
seconds.
• Field metering of detector sensitivity may be
performed with the aid of a voltmeter and Test
Kit, P/N 119-9010N.
For the complete procedure, refer to the Installation
and Maintenance instructions furnished with each detector.
Cleaning programs should be adapted to the individual environment in conformance with NFPA Standard
72. We recommend at least an annual cleaning of the
unit. The detector screen and cover assembly can be removed, revealing the sensing chamber. A vacuum
cleaner can be used to remove dust from the screen,
cover and sensing chamber. For the complete procedure, refer to the Installation and Maintenance instructions furnished with each detector.
ORDERING AND TECHNICAL INFORMATION
Part No.
112-90001
110-90008
110-90009
110-90010
110-90014
138-01005
119-63020
119-9010N
2 of 2
Model
301PL
301BL
301BL4
301BL4AC
B401BH
RA-400Z
2040-24
Contacts
Description
Photoelectronic Detector
Base, Two-wire
Form A & C
Base, four-wire, 24 VDC operation
Form A, C & Supv. Base, four-wire, 120 VAC operation
Base, four-wire, with audible sounder
Remote Alarm Indicator
Form B
End of Line Relay, 24 VDC
Test Kit
9020-0375