FCI-CONNECTOR 1451

1451
System Sensor
Ionization Smoke Detector
Description
The System Sensor 1451 ionization type smoke detectors
are specifically designed to meet the performance requirements of fire detection/alarm systems. The 1451 ionization detector uses a state-of-the-art, dual unipolar sensing
chamber. The detector is designed to provide open area
detection and when installed in a two-wire base is compatible with FCI fire alarm control panels. The detectors
operation and sensitivity can be tested in place.
The 1451 detector is of plug-in construction and plugs into
the same base as the 2451 Series photoelectronic smoke
detectors, making both models interchangeable. Bases
are available for two-wire, four-wire, and 120 VAC fourwire operation.
Two visible LEDs on each detector flash approximately
every ten seconds indicating that power is being applied
to the detector. The LEDs light steadily when the detector
is in alarm. A remote LED annunciator is available as an
optional accessory.
The 1451 detector is Listed for use inside ducts up to a
velocity of 1,200 FPM.
Sensitivity testing is performed by placing a test magnet
against the cover. The LED on the detector should light
within 5 seconds.
Field metering of detector sensitivity may be performed
with the aid of a voltmeter and Test Kit, MOD 400R.
Specifications
Nominal Sensitivity
Operating voltage
Operating
temperature
Operating humidity
Air velocity
Altitude
Construction
Diameter
Height
Weight
1451
Features
• Unique dual unipolar sensor provides exceptional
stability.
• Easy plug-in of the head to base.
• Built-in tamper-resistant feature.
• Built-in test switch.
• Built-in visual alarm indicators.
• 360° view angle of alarm LEDs.
• Compatible with FCI control panels.
• Field adjustable sensitivity.
• Field metering of detector sensitivity.
• Removable insect screen and cover for field
cleaning.
• Sealed against dirt, insects, and back pressure.
• Insect-resistant screening (.020"/.508 mm
openings).
1.5 %/ft
8.5 - 35 VDC (24 VDC nominal)
32° to 120° F (0° to 49° C)
10 % - 93 % relative humidity
1,200 FPM
10,000 ft.
Off-white flame retardant plastic
6.2 inches (15.7 cm)
3.2 inches (8.1 cm)
0.5 lb (277 g)
An ISO 9001-2000 Company
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2006 Gamewell-FCI. All rights reserved.
www.gamewell-fci.com
9020-0584 Rev. B page 1 of 2
Mounting
• On a 4 inch square box with or without plaster ring or
supplied adapter. Minimum depth 1.5 inches.
• On a 3.5 or 4 inch octagonal box. Minimum depth 1.5
inches.
• On a single gang box. Min. depth 1.5 inches.
Installation
Place the detector into the detector base. Turn the detector clockwise until the detector locks into place.
Views Showing Position of Test Magnet
To use the tamper-proof feature, break the smaller tab on
the scribed line in the tamper proof tab located on the
detector mounting bracket. Install the detector. To remove
the detector from the base when using the tamper-proof
feature, insert the blade of a small screwdriver into the
hole on the side of the base and push the plastic lever
away from the detector head. This will allow the detector
to be rotated counterclockwise for removal.
Note: The decorative ring must be removed in order to
remove the head when using the tamper-proof feature.
The tamper-proof feature may be defeated permanently
by breaking the plastic lever off the base.
Note: The number of two-wire smoke detectors which can
be accommodated per zone varies with different control
panels. Consult the control panel instruction manual to
determine the capacity.
Refer to NFPA 72, Chapter 5-3, “Smoke Sensing Fire
Detectors” for spacing, location of detectors and other
guidelines.
Testing
Detectors may be tested in the following ways:
• Place a test magnet against the cover opposite the test
module socket. (See illustration). The detector should
go into alarm within 5 seconds.
• Field metering of detector sensitivity may be performed
with the aid of a voltmeter and Test Kit MOD 400R. For
the complete procedure, refer to the Installation and
Maintenance Instructions furnished with each detector.
Maintenance
Cleaning programs should be adapted to the individual
environment. We recommend at least, an annual cleaning
of the unit. The detector screen and cover assembly can
be removed, revealing the sensing chamber. A vacuum
cleaner can be used to remove dust from the screen,
cover and sensing chamber. For the complete procedure,
refer to the Installation and Maintenance Instructions furnished with each detector.
WARNING: To prevent detector contamination during construction, smoke detectors must be protected
from dust and contamination until the area is clean
and dust free. see NFPA 72 -5-3.7.1.3.
Ordering Information
Part Number
Description
1451
Alarm Current
B401B
Ionization Detector
‡
Base, two-wire
.
00012 A
‡
Base, four-wire, 24 VDC operation
Supervisory
Current
Alarm Current
B402B
Supervisory
Current
Alarm Current
Contacts
301B4AC
Contacts
RA-400
Alarm Current
PAM-1
Alarm Current
Contacts
.00012 A
.036 A
Form A, C*
Base, four-wire, 120 VAC operation
Form A, C* & Supv.
Remote alarm indicator
.007 A
End-of-line relay, 24 VDC
.015 A
Form B
Test kit
*Resistive load
(contact ratings):
Form A - 2.0 A @ 30 VAC/DC
Form C - 2.0 A @ 30 VAC/DC, 1.0 A
@ 120 VAC
‡Note: Alarm current of detector is limited by control panel
initiating device circuit.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell-fci.com
9020-0584 Rev. B page 2 of 2