H Class 200 Series Meter Product Data

H-Series Class 200 Meter
KWH & KWH/DEMAND METER
PRODUCT DATA
FEATURES
• Direct-read 2-line alpha-numeric LCD display without
multiplier displays cumulative kWh & “real-time” kW load.
• Demand option displays kW/Demand and kW Peak date
and time (15 minute interval standard, 30 and 60 minute
intervals available.)
• Patented 0-2 volt output split-core current sensors promote
enhanced safety and accurate remote mounting of current
sensors up to 2000 feet from meter without power
interruption.
• Onboard installation diagnostics & verification system.
• Parallel up to three (3) sets of current sensors for
cumulative reading.
• Meter can be used on the following configurations:
3-Phase, 4-Wire
3-Phase, 3-Wire
2-Phase, 3-Wire
• Fixed-value pulse output.
• Available in both industrial grade JIC steel enclosure and
NEMA 4X polycarbonate enclosure.
• Non-volatile Memory.
APPLICATION
The Honeywell Class 200 kWh/Demand meter is a 3-element
meter used to monitor electric power usage of individual loads
after the utility meter.
• UL/CUL Listed.
• Revenue Grade Accuracy. Certified by independent test lab
to ANSI C12.20 national accuracy standards. (+/- 0.2%
from 1% to 100% of rated load.)
Contents
Application ........................................................................
Features ...........................................................................
Ordering Information .........................................................
Specifications ...................................................................
63-2716-01
1
1
2
3
H-SERIES CLASS 200 METER
Class 200 and Green Meter Selection Guide
Series Class
H
20
Green or Demand
Option
Voltage
Current
-
208
100-
J
JIC STEEL
ENCLOSURE
-G-
GREEN
CLASS
METER
-
480
200-
R
NEMA 4X
ENCLOSURE
-D-
DEMAND
-
600
400-
KIT
NO
OPTIONS,
SPLIT
CORE
CURRENT
SENSORS
-
800-
-
1600-
-
3200-
Enclosure Type
Current
Sensors
KIT
SPLITCORE
CURRENT
SENSORS
Example: H20-208100-RKIT = Class 200 Three Phase 208/240V 100A, NEMA 4X Enclosure with 3 Current Sensors.
Example: H20-2081600R-D-KIT = Class 200 Three Phase 208/240V 1600A, NEMA 4X Enclosure, Demand Option, with 3
Current Sensors
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
63-2716—01
2
H-SERIES CLASS 200 METER
CLASS 200 METER TECHNICAL SPECIFICATIONS
Input Voltage Configuration
3-wire (Delta) Or 4-wire (Wye)
Mains Voltage Input
Up To 600 VAC RMS Available
Input Power
6 VA Maximum Rating
Current Sensor Rating
Up To 3200 Amps RMS AC Available
Power Factor
0.5 Leading Or Lagging
Line Frequency
50-60 Hz
Metering Accuracy
Certified To ANSI C12.16 (+/-% From 1- 100% Of Rated Load)
Voltage Operating Range
+/-10% Of Rated Load
Temperature Range
-20 C To +50 C (Standard indoor enclosure):
Temperature Range
-20 C To +70 C (NEMA 4X outdoor enclosure)
Relative Humidity Range
0-95% Non-condensing
Altitude
200 Meters Maximum
Voltage Overload
+25% Continuously: +100% For 20 Cycles
Current Sensor Overload
100% For 1 Minute Without Damaging Meter
Pollution Degree
Degree 2 In Accordance With IEC 664
Installation (Overvoltage) Category
Category 111
Measurement Category
Category 111
Enclosure Material
Indoor Housing Rating (J): JIC Steel Enclosure
Outdoor Housing Rating (R): NEMA 4X
Display Readout
KWh Accumulated,
Standard Ranges
4-Wire Wye, 120/208 VAC: 100, 200, 400, 800,1600,3200 Amp
2 Phase, 120/240 VAC: 100, 200, 400, 800,1600,3200 Amp
4-Wire Wye, 277/480 VAC: 100, 200, 400, 800,1600,3200 Amp
3-Wire Delta, 220/240 VAC: 100, 200,400,800,1600,3200 Amp
3-Wire Delta, 480 VAC: 100, 200, 400, 800,1600,3200 Amp
4-Wire Wye, 600 VAC: 100,200,400,800,1600,3200 Amp
Modem Interface
Cable:
UL-listed Telephone Cord,
6-cond. 300 VAC, Stranded Cond. 22-26 AWG.
Cable Connector:
RJ-45 male IDC
Input/Output Voltage:
+5 VDC/18 VAC
IDR Interface Port
Ckt Input Isolation
5.3K VAC for 1 Minute
Baud Rate:
9600
Cable:
UL-listed/rated Telephone Cord. 4-cond.
Input/output Voltage:
Ground-isolated +/-5.4VDC
Cable Connector:
RF-45 Male IDC Or Screw Terminal
Termination
Circuit Input Isolation:
5.3kVAC
Circuit output Isolation:
21.5kVAC
Isolated Pulse/Alarm Outputs (TB5, TB6):
Recommended
In-line Fuse
Battery Cell
Output Voltage Potential:
0 VDC to +5 VDC Logic Levels
Mating Plug Connector:
Weidmuller PN: 152876
Signal Isolation Voltage:
5.3K VAC for 1 Minute
Manufacturer:
Littlefuse
Mfg. Part No:
KLDR.100
Rating:
100mA, Time-delay, 600VAC Cartridge Fuse
Description:
Non-rechargeable Cell Used For Memory
Retention
Manufacturer:
Eagle-Picher
Mfg Part No:
LTC-3PN-S2
Working Voltage:
3.5VDC
Current Capacity
350mAhr
Electrolyte:
Lithium Thionyl Nitrate
3
63-2716—01
H-SERIES CLASS 200 METER
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark
© 2012 Honeywell International Inc.
63-2716—01 JPG Rev. 02-12
Printed in United States