62-0353—01 - C7262A Sensor and Controller

C7262A Sensor and Controller
CARBON DIOXIDE/TEMPERATURE SENSOR
PRODUCT DATA
• Automatic Background Calibration (ABC) algorithm based
on long-term evaluation reduces required typical zero-drift
check maintenance.
SPECIFICATIONS
Models: C7262 Sensor. A stand-alone carbon dioxide (CO2)
and temperature sensor with two jumper-adjustable CO2
outputs (one analog and one SPST relay).
C7262A1008: Wall module with display.
C7262A1016: Wall module without display.
Dimensions: See Fig. 1.
C7262A1008
C7262A1016
APPLICATION
The C7262 Sensor is a stand-alone carbon dioxide (CO2) and
temperature sensor for use in determining ventilation
necessity with HVAC controllers. The C7262 measures the
CO2 concentration and temperature in the ventilated space.
The C7262 is used in ventilation and air conditioning systems
to control the amount of fresh outdoor air supplied to maintain
acceptable levels of CO2 in the space and to sense the
temperature of the space.
FEATURES
• Used for CO2 based ventilation control.
• Integral 20K ohm NTC temperature output.
• Models available with LCD that provides CO2 ppm level.
• Non-Dispersion-Infrared (NDIR) technology used to
measure carbon dioxide gas.
• Device provides voltage or current output based on CO2
levels.
• Models available with SPST relay output.
Sensor Performance Ratings:
Response Time: Less than 3 min.
Carbon Dioxide Sensor:
Operation: Non-dispersive infrared (NDIR).
Sampling: Diffusion.
CO2 Range: 0 to 2000 ppm
Accuracy: ± (30 ppm + 3% of reading) from 59°F to 85°F
(15°C to 30°C).*
Temperature Sensor:
Thermistor: 20K ohms NTC.
Operating temperature range: 22°F to 122°F
(-6°C to +50°C).
* This product complies with Title 24 Part 6, CEC Standard
for Residential and Non-Residential Buildings—2005,
when installed according to instructions.
Electrical Ratings:
Power Supply: 24 Vac/dc ±20%, 50/60 Hz (Class 2).
Maximum Power Consumption: 1W.
Peak Current (20 ms duration): At rated voltages it is 120mA
or less.
Relay:
Configuration: Shipped N.O.
Contact Rating: 1A at 50 Vac/24 Vdc.
Minimum Permissible Load: 1 mA at 5 Vdc.
Linear Analog Output:
Voltage: 0/2-10 Vdc (resistive load greater than
5000 ohms).
Current: 0/4-20 mA (resistive load less than 500 ohms).
Outputs (Jumper Adjustable, see Table 2):
CO2 outputs
62-0353-03
C7262A SENSOR AND CONTROLLER
INSTALLATION
Analog: 0-10 Vdc (Default: 0-10 Vdc, 0 to 2000 ppm),
2-10 Vdc, 4-20mA.
Relay: Normally Open SPST (Default: Close at 800 ppm).
When Installing this Product...
Ambient Ratings:
Temperature:
Operating: +32°F to +122°F (0°C to +50°C).
Storage: -4°F to +158°F (-20°C to +70°C).
Relative Humidity (non-condensing): 0 to 95 percent.
1.
2.
CO2 Pressure Dependence: 1.6% change in reading per
1 kPa deviation from 100 kPa.
3.
Wiring Connections: Terminals (16 gauge maximum)
4.
Mounting:
Vertical surface with standard single-gang junction box.
Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
Installer must be a trained, experienced service
technician.
After installation is complete, check out product
operation as provided in these instructions.
IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.
Automatic Background Calibration (ABC) default: On.
Calibration: This product is factory calibrated. No field calibration is necessary for the life of this product.
CAUTION
Health Hazard.
Approvals: CE
Improper use can create dangerous situations.
Use in application for sensing carbon dioxide and
temperature only.
For life-safety applications, this device can function
only as a secondary or lesser device.
3 (76)
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
4-13/16
(122)
CAUTION
Equipment Damage Hazard.
Electrostatic discharge can short equipment
circuitry.
Ensure that you are properly grounded before
handling the unit.
C7262A Cover Removal/Replacement
7/8 (22)
A snap-fit locking mechanism is used to attach the cover of
the wall module to its subbase. To disassemble the cover from
the subbase:
M32567
Fig. 1. C7262A dimensions in inches (mm).
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
62-0353—03
2
C7262A SENSOR AND CONTROLLER
1.
2.
Insert a thin, flat blade screwdriver into each of the two
slots at the bottom of the module to release the two locking tabs.
Tilt the cover out and away from the subbase to release
the top two locking tabs.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
Location and Mounting
CAUTION
Equipment Damage Hazard.
C7262 Sensors mount directly on the wall, sheet metal duct, or
a panel. When planning the installation, allow enough
clearance for maintenance and service. Mount the sensor in a
well-ventilated area.
NOTES:
Electrostatic Discharge Can Short Equipment Circuitry.
Ensure that you are properly grounded before
handling the unit.
Do not install the sensor where it can be affected by:
— drafts or dead spots behind doors and in corners.
—air from ducts.
IMPORTANT
1. All low voltage connections to this device must be
24 Vac Class 2.
2. All wiring must comply with applicable local codes,
ordinances and regulations.
Sensor must be mounted in a location which sees at
lease one 4-hour unoccupied period per week so that
the CO2 level drops to outdoor levels. Automatic
Background Calibration will not work properly in locations without four hours of unoccupied time per week,
or where there are sources of CO2 other than people
(breweries, mushroom farms, etc).
Table 1. C7262 Terminal Connections (see Fig. 3).
Designation
Function
V+
24V Hot
IMPORTANT
This sensor is not for use in highly corrosive environments.
Com AC/DC 24V Common for OUT1 and OUT2
TEMP
20k ohm NTC temperature output
Wall Mounting
OUT1: CO2
Analog Output, CO2
OUT2: CO2
Analog Output, CO2
TEMP
The C7262 Wall Mount models can be mounted using two or
four screws:
1. Remove C7262 cover.
2. Mount the subbase to the wall using washers and two or
four screws (not supplied) appropriate for the wall
material.
RELAY NO
COM AC/DC (CONVENIENCE)
NOTE: When mounting on a junction box, see Fig. 2.
3.
Normally Open potential free relay contacts
RELAY NO
V+ COM
24V AC/DC
Replace the cover.
TEMP
TEMP
COM
AC/DC
OUT1: OUT2: RELAY RELAY
CO2 CO2
COM NO
STANDARD UTILITY CONDUIT BOX
NO. 6 SCREW
COMMON FOR
OUT1 AND OUT2
M33069A
24V
Fig. 3. Wiring the C7262.
FRONT
COVER
Input Signal
SUBBASE
NO. 6 SCREW
The C7262 Sensors have an adjustable range. These ranges
are determined by the SW1 and SW2 jumper settings (see
Table 2).
M32569A
Fig. 2. Junction box mounting (C7262A).
Table 2. CO2 Range Jumper Settings
WIRING
SW1a
The factory ships the device with the output default settings
shown in Tables 2 and 3. Set the jumpers and wire the device
(see Table 1 and Fig. 3).
3
SW2a
OUT1 & OUT2 (ppm)
Relayb (ppm)
On
On
500 to 1500
1200
On
Off
500 to 2000
1200
Off
On
0 to 1000
1000
Offc
Offc
0 to 2000
800
62-0353—03
C7262A SENSOR AND CONTROLLER
Output Signal
COM AC/DC
V
COM AC/DC
SW1 ON and SW2 ON state means jumper is set in upper
position and OFF state means jumper is set in lower position.
b
When the level reaches this value, the contacts close; when
the level drops 100 ppm below this value, the contacts open.
c
Setting when shipped from the factory.
RELAY COM
a
The output signal can be adjusted for 0/2-10 Vdc or 0/4-20 mA
(see Table 3).
Table 3. Output Signal Jumper Settings
OUT 1 & OUT 2
AN OUT1 & OUT2
0-100%
20-100%
Voltage
0-10Vdc
2-10Vdc
Current
0-20 mA
4-20 mA
NOTES:
—
—
—
Jumpers are shown on the sticker on the inside of
the cover.
Use needle nose pliers to carefully reposition
jumpers.
The CO2 settings and the output signal settings
are independent of each other. 0-100% and
20-100% are simply markings for the OUT jumper
settings on the sensor (to differentiate between
the two voltage and the two current ranges) and
do not refer to or alter the ppm range chosen.
M33068A
Fig. 4. C7262 default jumper settings.
Example
For a CO2 setting of 0-2000 ppm and a voltage output of 0-10 Vdc, the output would be as shown in Table 4 (arbitrary points
along the analog curve).
Table 4. 0-10 Vdc Output Example.
CO2 Level (ppm)
Voltage Output (Vdc)
0
200
400
600
800
1000
1200
1400
1600
1800
2000
0
1
2
3
4
5
6
7
8
9
10
For a CO2 setting of 0-2000 ppm and a voltage output of 2-10 Vdc, the output would be as shown in Table 5 (arbitrary points
along the analog curve).
Table 5. 2-10 Vdc Output Example.
CO2 Level (ppm)
Voltage Output (Vdc)
0
250
500
750
1000
1250
1500
1750
2000
2
3
4
5
6
7
8
9
10
CHECKOUT
Perform a quick test of the unit with the unit powered:
1. Stand close to the unit and breathe air into the sensor.
2. Check the CO2 level registered by the controller to
ensure a strong rise.
3.
When connected to a damper in a ventilation system,
the controller typically signals an increase in air flow.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark
© 2012 Honeywell International Inc.
62-0353—03 J.J. 09-12
Printed in United States