63-2700—10 - JADE™ Economizer Module

JADE™ Economizer Module
(MODEL W7220)
PRODUCT DATA
System Components
The JADE™ Economizer System includes an Economizer
Module, 20k mixed air sensor, damper actuator, an optional
CO2 sensor, and either a 20k outdoor air temperature sensor
or Sylk Bus sensors for measuring Outdoor Air and return air
enthalpy, temperature, and humidity.
Economizer Module
This is the core of the JADE™ Economizer System and
includes the user interface for the system. The W7220
Economizer Module provides the basic inputs and outputs to
provide simple economizer control. When used with the
optional Sylk Bus sensors, the Economizer Module provides
more advanced economizer functionality.
PRODUCT DESCRIPTION
The JADE™ Economizer System is an expandable
economizer control system, which includes a W7220
Economizer Module (controller) with an LCD and keypad. The
W7220 can be configured with optional sensors.
The W7220 Economizer Module can be used as a standalone economizer module wired directly to a commercial set
back space thermostat and sensors to provide Outdoor Air
dry-bulb economizer control.
The W7220 Economizer Module can be connected to optional
Sylk Bus sensors for single or differential enthalpy control. The
W7220 Economizer Module provides power and
communications on the Sylk Bus for the Sylk Bus sensors.
The W7220 Economizer Module automatically detects
sensors by polling to determine which sensors are present. If
a sensor loses communications after it has been detected, the
W7220 Economizer indicates a device fail error on its LCD.
Sylk Bus Sensors (optional)
The Sylk Bus Sensor is a combination temperature and
humidity sensor which is powered by and communicates on
the Sylk Bus. Up to three sensors may be configured with the
JADE™ Economizer Module. See page 2 for details.
CO2 Sensor (optional)
A CO2 sensor can be added for Demand Control Ventilation
(DCV). Either an analog (2-10 Vdc) or a wall-mount Sylk bus
TR40 CO2 sensor can be used with the Jade economizer.
PC MOD Tool (optional)
The PC MOD tool is connected to a personal computer and
communicates with the Jade economizer controller via the
Sylk bus. The W7220 PCMOD tool software is free and can be
downloaded from the url in the Accessories section.
Some features on the Jade controller can only be enabled or
disabled using the W7220 PC MOD tool. See the PC MOD
tool options section in Table 5.
Contents
Product Description ..........................................................
Specifications ...................................................................
Before Installation ............................................................
Installation and Setup ......................................................
Mounting ..........................................................................
Wiring ...............................................................................
Wiring Application Examples ...........................................
Interface Overview ...........................................................
Setup and Configuration ..................................................
Checkout ..........................................................................
Troubleshooting ................................................................
E4436
1
2
3
3
3
4
9
18
18
30
31
63-2700-10
JADE™ ECONOMIZER MODULE
SPECIFICATIONS
Dry Bulb Temperature (optional) and Mixed Air
(required), C7250A:
2-wire (18 to 22 AWG);
Temperature range -40 to 150 °F (-40 to 65 °C).
Temperature accuracy -0°F/+2°F
W7220A Economizer Module
The module is designed for use with any Honeywell 2 to 10
Vdc or Honeywell Sylkbus communicating actuator. The
module includes terminals for a CO2 sensor, Mixed Air sensor,
and an Outdoor Dry Bulb sensor. Enthalpy and other options
are available with Sylk Bus sensors.
Temperature and Humidity, C7400S1000 (optional):
Sylk Bus; 2-wire (18 to 22 AWG)
Temperature: range -40 to 150 °F (-40 to 65 °C)
Temperature accuracy -0°F/+2°F
Humidity: range 0 to 100% RH with 5% accuracy.
User Interface: Provides status for normal operation, setup
parameters, checkout tests, and alarms and error
conditions with a 2-line 16 character LCD display and a
four button keypad.
NOTE: Up to three (3) SYLK Bus sensors may be
connected to the JADE™ Economizer module.
For outdoor air (OA), return air (RA) and
discharge (supply) air (DA).
Electrical
DCV (CO2) Sensor (C7232 or C7632):
2-10 Vdc control signal; minimum impedance >50k ohm.
Rated Voltage: 20 to 30 Vac RMS; 50/60 Hz
Transformer: 100 VA maximum system input
4 Binary inputs:
1-wire 24 Vac + common GND (see page 6 for wiring
details). 24 Vac power supply: 20 to 30 Vac 50/60Hz;
100 VA Class 2 transformer.
Nominal Power Consumption (at 24 Vac, 60 Hz): 11.5 VA
without sensors or actuators
Relay Digital Output Rating at 30 Vac (maximum power
from Class 2 input only): 1.5A run;
3.5A inrush @ 0.45PF (200,000 cycles) or
7.5A inrush @ 0.45PF (100,000 cycles)
Outputs
Actuator signal: 2-10 Vdc; minimum actuator impedance is
2k ohm; Sylkbus two-wire output for Honeywell Sylkbus
communicating actuators.
External Sensors Power Output: 21 Vdc +/- 5% @ 48mA
IMPORTANT
All inputs and outputs must be Class 2 wiring.
Inputs
Exhaust fan, Y1, Y2 and AUX1 O:
All Relay Outputs (at 30 Vac):
Running: 1.5A maximum
Inrush: 7.5A maximum
SENSORS:
Environmental
NOTE: A Mixed Air (MA) analog sensor is required on all
W7220 units; either an Outdoor Air (OA) sensor
for dry bulb change over or an OA Sylkbus
sensor for outdoor enthalpy change over is
required in addition to the MA sensor. An
additional Return Air (RA) Sylkbus sensor can be
added to the system for differential enthalpy or
dry bulb changeover. For differential dry bulb
changeover a 20k ohm sensor is required in the
OA and a Sylkbus sensor in the RA. Dip switch
on RA Sylkbus sensor must be set in the RA
position.
Operating Temperature: -40 to 150 °F (-40 to 65 °C).
Exception of display operation down to -4 °F with full
recovery at -4 °F from exposure to -40 °F
Storage Temperature: -40 to 150 °F (-40 to 65 °C)
Shipping Temperature: -40 to 150 °F (-40 to 65 °C)
Relative Humidity: 5% to 95% RH non-condensing
Dimensions (See Fig. 1 on page 3):
Height: 4.98 inches (126.4 mm)
Width: 6.3 inches (160 mm)
Depth: 1.34 inches (34 mm)
Weight: 0.58 lb. (0.265 kg)
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:
1.
2.
Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
Honeywell Customer Care
1985 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
63-2700—10
2
JADE™ ECONOMIZER MODULE
INSTALLATION AND SETUP
Approvals: UL listed (XAPX) for USA and Canada;
California Energy Commission (CEC) FDD ID number
HJW10.
The following installation procedures should be performed in
the order listed:
1. Mounting — see page 3.
2. Wiring — see page 4.
3. Interface and Programming overview – see page 18.
4. Setup and Configuration — see page 18
5. Checkout — see page 30.
6-19/64 (160)
4-63/64
(126)
Troubleshooting and Alarms—see page 31.
MOUNTING
This section describes the mounting procedures for the
JADE™ Economizer module and the sensors.
MOUNTING HOLE (X2)
3-5/32 (80)
Economizer Module Location and
Mounting
M32273A
Fig. 1. Dimensions in inches (mm) showing mounting
holes.
Accessories
—
—
—
—
—
—
—
IMPORTANT
Avoid mounting in areas where acid fumes or other
deteriorating vapors can attack the metal parts of the
module’s circuit board, or in areas where escaping
gas or other explosive vapors are present.
50048926-001 2-pin edge connector for sensors (20
pieces per bag)
50048926-002 6-pin edge connector for field wiring (20
pieces per bag)
C7250A 20k sensor for MA or OA (dry bulb changeover)
C7400S Sylkbus sensor for enthalpy control in OA and/
or RA and RA for differential dry bulb changeover
W7220 PCMOD interface tool for JADE controller and
Personal Computer. For the software, go to
www.customer.honeywell.com/economizertools
50053060-001 Duct mounting kit for sensors
C7632 or C7232 CO2 analog sensors OR one TR40
Sylk bus CO2 sensor
IMPORTANT
The module must be mounted in a position that allows
clearance for wiring, servicing, and removal.
Mount the Economizer module on any convenient interior
location using the two mounting holes provided on the
enclosure using #6 or #8 screws (screws are not provided and
must be obtained separately). Use the dimensions in Fig. 1 on
page 3 as a guide.
BEFORE INSTALLATION
The Economizer module may be mounted in any orientation.
However, mounting in the orientation shown in Fig. 1 on page 3
permits proper viewing of the LCD display and use of the
keypad.
Review the “Specifications” on page 2 before installing the The
JADE™ Economizer System.
Sensor Location and Mounting
When Installing This Product
1.
2.
3.
4.
The JADE™ Economizer W7220 uses digital and
communicating sensors for control. The C7250 temperature
sensors (MAa and OAb) are 20k NTC. A MA sensor is required
for all applications and is mounted in the mixed air section of a
rooftop unit either directly to the sheet metal using self tapping
sheet metal screws or in the air stream using the duct
mounting kit. Duct mount kit is part number 50053060-001.
Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condition.
Check ratings given in instructions and on the product to
ensure the product is suitable for your application.
Installer must be a trained, experienced service
technician.
After installation is complete, check out product
operation as provided in these instructions.
Optional OA, RAc and DAd Sylkbus sensors communicate with
the W7220 on the two-wire communication bus and can either
be wired using a two pin header or using a side connector.
Each Sylkbus sensor includes a two pin side connector with
the packaging. The SKU number of the Sylkbus sensor is
C7400S. All OA, RA and DA sensors are the same SKU
NOTE: Jade will be in the "set up" mode for the first 60
minutes after powered. If a sensor for OA air or
Sylkbus device (sensor, actuator) is disconnected
during the set up mode, the Jade will not alarm
that failure. The MA sensor is a system "critical"
sensor, if the MA sensor is removed during the
set up mode, the Jade will alarm. After 60 minutes
the Jade controller will change to operation mode
and all components removed or failed will alarm
in the operation mode.
a
MA = Mixed Air
OA = Outdoor Air
c RA = Return Air
d DA = Discharge Air
b
3
63-2700—10
JADE™ ECONOMIZER MODULE
number. The sensor is set for the appropriate type of sensing
using the three position DIP switch located on the sensor. OA
position is OFF, OFF, OFF; RA is ON, OFF, OFF and DA is
OFF, ON, OFF. During installation the sensors are set for the
usage desired. See “Sylk Bus Sensor Wiring” on page 7 for
DIP switch details.
NOTE: The protective film on the dip switch is only necessary during the factory assembly process. Simply push through the film to set the dip switches;
this will not harm the device.
Once installed, a sensor can be changed to a different
application by simply changing the DIP switch setting.
WIRE HOLDER
Sensor Mounting
LENGTH ADJUSTS
6-12 INCHES
The sensors can be mounted directly on to the sheet metal of
unit or can be mounted in the air stream using the duct
mounting kit (order separately).
The kit contains a rod to hold the sensor in the duct, a flange to
secure the sensor rod to the duct wall and fill the hole and a
gasket to prevent air from leaking through the duct wall. There
are five (5) kits in each bag assembly. See Fig. 2.
The rod has slots for threading the wire to prevent loose or
hanging wire in the duct and can be adjusted for 6 to 12 inch
length. The flange has extended relief for ease of mounting.
See Fig. 3.
EXTENDED RELIEF
(FOR CORRECT MOUNTING)
M32282A
Fig. 3. Duct Mounting Adjustments.
WIRING
All wiring must comply with applicable electrical codes and
ordinances, or as specified on installation wiring diagrams.
Module wiring in the field is terminated to the four screw
terminal blocks located on the left and right sides.
ROD - 1 PIECE
Module wiring at the OEM factory is terminated via the header
pin terminals located on the left and right sides. The header
terminal pins and the terminal blocks have common
terminations for the appropriate input or output. See OEM
wiring diagram in Fig. 20.
GASKET - 1 PIECE
FLANGE - 1 PIECE
M32281A
Fig. 2. Duct Mounting Kit (Part No. 50053060-001).
The remainder of this section describes the wiring for the
JADE™ Economizer module, W7220A.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring, or
making wiring connections, to prevent electrical shock
or equipment damage.
CAUTION
Equipment Damage Hazard.
Electrostatic discharge can short equipment
circuitry.
Ensure that you are properly grounded before handling
the unit.
63-2700—10
4
JADE™ ECONOMIZER MODULE
TWO STAGE COOL
PROGRAMMABLE
THERMOSTAT
DISCHARGE
AIR SENSOR
C7400S
W7720A
C7250A
1
MIXED AIR
SENSOR
MS3103J
MS3105J
MS7505
ACTUATOR
C7400S
ENTHALPY
SENSOR
OUTDOOR
AIR
DIRECT
EXPANSION
COIL
RETURN AIR
C7400S
ENTHALPY
SENSOR
1
1 FOR DIFFERENTIAL ENTHALPY, THE TWO C7400S ENTHALPY
SENSORS ARE CONNECTED TO THE W7720A ECONOMIZER
CONTROL ONE IS MOUNTED IN RETURN AIR, AND THE
OTHER IS MOUNTED IN OUTDOOR AIR. DIFFERENTIAL
ENTHALPY CONTROL PROVIDES GREATER ENERGY
SAVINGS THAN SINGLE ENTHALPY.
M35163
Fig. 4. Location of Outdoor Air, Return Air, Mixed Air, and Discharge Air Sensors in an economizer system.
5
63-2700—10
JADE™ ECONOMIZER MODULE
Economizer Module Wiring Method
Economizer Module Wiring Details
Wire the sensors and outputs, then wire the power connection.
The wiring connection terminals for each module/sensor are:
• “JADE™ Economizer Module Wiring” on this page.
• “Sylk Bus Sensor Wiring” on page 7.
Each terminal can accommodate the following gauges of wire:
• Single wire – from 18 AWG to 22 AWG solid or stranded
• Multiple wires – up to two 22 AWG stranded
• For the 24 Vac connections: single wire – from 14 to 18
AWG solid or stranded
• For S-BUS wiring, the sensors may be mounted up to 200
ft. (61 m) from the JADE controller. When the length of wire
is over 100 feet use twisted pair shielded wire.
• All sensor wiring to the Sylk bus and analog sensors is
polarity insensitive.
JADE™ Economizer Module Wiring
Use Fig. 6 and Tables 1 and 2 to locate the wiring terminals for
the Economizer module.
NOTE: The four terminal blocks are removable. You can
slide out each terminal block, wire it, and then
slide it back into place.
Prepare wiring for the terminal blocks, as follows:
1. Remove the plastic tabs from the side of the controller
where the connectors will slide onto the PWA.
2. Strip 1/2 in. (13 mm) insulation from the conductor.
3. Cut a single wire to 3/16 in. (5 mm). Insert the wire in the
required terminal location and tighten the screw.
4. If two or more wires are being inserted into one terminal
location, twist the wires together a minimum of three
turns before inserting them to ensure proper electrical
contact. See Fig. 5 on page 6.
5. Cut the twisted end of the wires to 3/16 in. (5 mm) before
inserting them into the terminal and tightening the screw.
6. Pull on each wire in all terminals to check for good
mechanical connection.
AUX2-I
JADE CONTROLLER
OCC
E-GND
EXH1
AUX1-O
AUX2-I
AUX1-O
Y2-I
Y2-O
Y1-I
Y1-O
C
R
LEFT TERMINAL
BLOCK LABEL
RIGHT TERMINAL
BLOCK LABEL
M32283C
1. STRIP 1/2 IN. (13 MM)
FROM WIRES TO
BE ATTACHED AT
ONE TERMINAL.
Fig. 6. W7220 Economizer module terminal connection
labels.
1/2 (13)
Table 1. Economizer Module - Left hand terminal blocks.
2. TWIST WIRES
TOGETHER WITH
PLIERS (A MINIMUM
OF THREE TURNS).
Label
Description
Top Left Terminal Block
MAT
MAT
20k NTC
and
COM
Mixed Air Temperature Sensor
(polarity insensitive connection)
OAT
OAT
20k NTC
and
COM
Outdoor Air Temperature Sensor
(polarity insensitive connection)
S-BUS
S-BUS
SYLK Bus Sylk Bus sensor
(polarity insensitive connection)
IAQ 2-10
2-10 Vdc
Air Quality Sensor Input
(e.g. CO2 sensor)
IAQ COM
COM
Air Quality Sensor Common
IAQ 24V
24 Vac
Air Quality Sensor 24 Vac Source
ACT 2-10
2-10 Vdc
Damper Actuator Output (2-10 Vdc)
Bottom Left Terminal Block
3. CUT TWISTED END OF WIRES
TO 3/16 IN. (5 MM) BEFORE INSERTING
INTO TERMINAL AND TIGHTENING SCREW.
THEN PULL ON EACH WIRE IN ALL
TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.
M24382A
Fig. 5. Attaching two or more wires at terminal blocks.
63-2700—10
Type
6
ACT COM COM
Damper Actuator Output Common
ACT 24V
24 Vac
Damper Actuator 24 Vac Source
n/a
The bottom pin is not used.
JADE™ ECONOMIZER MODULE
Table 2. Economizer Module - Right hand terminal blocks.
Label
Type
Table 3. SYLK Bus Sensor Wiring Terminations.
Description
Terminal
Top Right Terminal Block
n/a
The first pin is not used
AUX2 I
24 Vac IN
Shut Down (SD) or Heat (W)
Conventional only
or
Heat Pump Changeover (O/B) in
Heat Pump mode.
OCC
24 Vac IN
Occupied / Unoccupied Input
E-GND
EGND
Earth Ground - System Required
EXH1
24 Vac OUT Exhaust Fan 1 Output
AUX1 O
24 Vac OUT Programmable:
Exhaust fan 2 output
or
ERV
or
System Alarm output.
Nbr
24 Vac IN
Y2-O
24 Vac OUT Y2 out - Cooling Stage 2 Output to
stage 2 mechanical cooling
Y1-I
24 Vac IN
Y1-O
24 Vac OUT Y1 out - Cooling Stage 1 Output to
stage 1 mechanical cooling
C
COM
24 Vac Common
R
24 Vac
24 Vac Power (Hot)
Description
Sylk Bus Communications
(Sensor Bus) polarity insensitive
2
S-BUS SYLK
Bus
Sylk Bus Communications
(Sensor Bus) polarity insensitive
DIP Switch Positions for Switches 1, 2, & 3
Use
1
2
3
DAa
OFF
ON
OFF
RAb
ON
OFF
OFF
OFF
OFF
OFF
c
OA
a DA
= Discharge Air
= Return Air
c OA = Outdoor Air
b RA
Y2 in - Cooling Stage 2 Input from
space thermostat
NOTE: When using the Sylkbus sensors there will be a
slight delay while the Jade controller and the
sensor communicate. Analog sensors do not
communicate on the Sylkbus and output a 20k
ohm signal to the Jade controller so the response
time is instantaneous.
Y1 in - Cooling Stage 1 Input from
space thermostat
NOTE: When using the C7400S (Sylk bus enthalpy)
sensor there is an operation that will allow test of
the operation of the W7220 economizer when the
outdoor air conditions (temperature and humidity)
are too high for economizing.
Sylk Bus Sensor Wiring
The labels on the sensors and controller are color coded for
ease of installation. Orange labeled sensors can only be wired
to orange terminals on the controller. Brown labeled sensors
can only be wired to S-bus (brown) terminals. Use Fig. 7 and
Table 3 to locate the wiring terminals for each Sylk Bus sensor.
1.
2.
Use Fig. 7 and Table 4 to set the DIP switches for the desired
use of the sensor.
3.
4.
5.
6.
DIP
SWITCH
LABEL
7.
DIP
SWITCHES
(3)
SYLK BUS
TERMINALS
(1 AND 2)
Type
S-BUS SYLK
Bus
Table 4. SYLK Bus Sensor DIP Switch Settings.
Bottom Right Terminal Block
Y2-I
Label
1
8.
Remove the C7250A dry bulb sensor from the OAT
terminals IF you are using temperature only economizing
change over.
If you are using enthalpy change over and have a
C7400S sensor with a date code prior to 1301, remove
the sensor and replace it with one with a date code after
1301.
Connect a C7400S Sylk bus sensor to the S-Bus
terminals (brown colored) on the W7220A Jade using
18 AWG to 22 AWG solid or stranded wires.
Check the STATUS screen for actual outdoor air (OA)
temperature and OA humidity readings.
Change the 3-position DIP switch on the C7400S sensor
from 1 OFF, 2 OFF, 3 OFF to 1 ON, 2 ON, 3 ON position
and immediately back to 1 OFF, 2 OFF 3 OFF position.
The output of the C7400S sensor to the W7220A will be
40 ºF and 40 %RH which will allow the economizer to go
into free cooling mode (economizing available).
Make sure you have 24 Vac on terminal Y1 In to simulate
a call for cooling.
After 15 minutes the C7400S sensor will change back to
the actual OA temperature and humidity.
NOTE: If you removed a dry bulb sensor, remove the
C7400S from the S-bus terminals and replace the
OAT sensor onto the OAT terminals.
SYLK BUS
2 PIN SIDE
CONNECTOR
M32271B
Fig. 7. Sylk Bus sensor DIP switches.
7
63-2700—10
JADE™ ECONOMIZER MODULE
Actuator Wiring Options:
1.
2.
3.
C7232
The JADE economizer controller can only have one (1)
communicating actuator connected to it.
Up to four (4) non-communicating and two (2) 2-position
actuators (1 each on EXH1 and AUX1 O)
One (1) communicating and up to four (4) non-communicating and two (2) 2-position actuators (1 each on EXH1
and AUX1 O). When using a 2-position actuator on the
AUX1 O, the AUX1 O must be programmed for Exh2 and
the % open is the % open of the outdoor damper when
the 2-pos actuator opens. Connect 24 V to Exh1 and/or
AUX1 O and ground to the Jade "C" terminal.
RED
24V
ANALOG
OUT
BLACK
+
–
YELLOW
BROWN
ORANGE
GREEN
L1
(HOT)
L2
1
1
POWER SUPPLY. PROVIDE
DISCONNECT MEANS AND
OVERLOAD PROTECTION
AS REQUIRED.
M17543B
Fig. 8. Wiring for C7232
CO2 Sensor Wiring
L1
(HOT)
L2
1
C7632
When using the C7232 Honeywell CO2 sensors the black and
brown common wires are internally connected and only one is
connected to "IAQ COM" on the Jade. Use the power from the
Jade to power the CO2 sensor OR make sure the ground for
the power supplies are common. See wiring diagram below for
the C7232 and C7632 wiring diagrams.
0-10 VDC
1
NOTE: When using the C7632 (or any 0-10 Vdc CO2 sensor) with the Jade you will need to set the
CO2ZERO to 400 ppm and the CO2SPAN to
1600 ppm in the ADVANCED SETUP menu.
M34095
Fig. 9. Wiring for C7632
NOTE: When using the TR40 CO2 sensor set the address
on the TR40-CO2 to 6. Only one TR40 CO2 sensor
can be used with the Jade economizer controller.
Address 6 is for a CO2 sensor, address 11 is for a
communicating actuator.
63-2700—10
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
8
JADE™ ECONOMIZER MODULE
WIRING APPLICATION EXAMPLES
This section shows the wiring configurations for the JADE™ Economizer system.
Stand-alone Economizer
The most basic configuration is the stand-alone Economizer (see Fig. 10 and Fig. 15).
A stand-alone Economizer is directly wired to sensors, actuators, thermostat, and mechanical cooling controls in the roof top unit.
It does not require Sylk Bus communications.
MA TEMP
SENSOR
20K NTC
ROOF TOP UNIT
W7220 ECONOMIZER CONTROLLER MODULE
Y1
O/B
OCC
MA
MA
OAT
OAT
1 OA TEMP
SENSOR
20K NTC
CO2
SENSOR
2-10 VDC
(OPTIONAL)
G
W1
Y2
W2
3
1K1
AUX2-I
OCC
E-GND
AUX1-0
Y2I
IAQ (2-10V)
IAQ COM
IAQ 24V
Y2O
Y1I
ACT (2-10V)
ACT COM
ACT 24V
Y1O
C R
TR
TR1
R(+)
24 VAC
M7215
IN
+
IN
-
1K1
C(-)
2
1
NOTE THAT THE C7250 20K NTC SENSOR CAN BE MOUNTED IN THE OAT ONLY IN THIS CONFIGURATION.
2
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O
OR B AND W2 MAY BE LABELED W.
3
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
THERMOSTAT
M28980D
Fig. 10. Stand-alone dry bulb Economizer configuration with black motor M7215.
EXH1 OR AUX1 O
1
C
2
V
ACTUATOR
NOTE: ON/OFF ACTUATORS CAN BE USED ON THE EXH1 OR AUX1
O TERMINAL WITH GROUND TO THE C TERMINAL. WHEN
PROGRAMMING THE EXH1 OR AUX1 O, THE % IS THE PERCENT
OPEN POSITION OF THE OUTDOOR AIR DAMPER WHEN THE
EXH1 OR AUX1 O TERMINAL IS ENERGIZED AND THE 2-POS
DAMPER GOES OPEN. IF USING THE AUX1 O TERMINAL
PROGRAM AUX1 O FOR EXH2.
M33409
Fig. 11. 2-position actuator.
9
63-2700—10
JADE™ ECONOMIZER MODULE
ON JADE CONTROLLER:
1. Y2-O CONNECT TO STAGE 2 MECHANICAL COOLING
2. Y1-O CONNECT TO STAGE 1 MECHANICAL COOLING
3. MAT IS MIXED AIR SENSOR C7250A1001
4. OAT IS TEMPERATURE CHAGEOVER C7250A1001
SENSOR OR S-BUS OA ENTHALPY SENSOR C7400S1000
5. AUX1 OUT PROGRAM TO SYS IN SYSTEM SETUP MENU
JADE W7220A1000
MS3103J1030
COMMUNICATING DCA
AUX2-I
OCC
E-GND
1
2
3
4
5
AUX1 OUT
Y2I
Y2O
Y1I
Y1O
C
R
C
R
PRESTIGE
THX9421R5013
TO THERMOSTAT
EIM
CONV
POWER
HEAT
STATUS
LEDS
COOL
FAN
U1
U2
U3
A
RELAY
R822N1011
1
3
KIT WITH PRESTIGE AND EIM
YTHX9421R5051
1
EIM
THM5421R1013
R
C
SENSORS
1
TRANSFORMER
24
VAC
120
VAC
THE TRANSFORMER NEEDS
TO BE 100VA.
M35158
Fig. 12. Prestige and EIM with communicating actuator.
63-2700—10
10
JADE™ ECONOMIZER MODULE
ROOF TOP UNIT
MA TEMP
SENSOR
20K NTC
W7220 ECONOMIZER CONTROLLER MODULE
O/B
MAT
MAT
G
W1
Y2
W2
8
1K1
AUX2-I
OCC
E-GND
S-BUS
S-BUS
CO2
SENSOR
2-10 VDC
(OPTIONAL)
Y1
OCC
G
Y1
Y2
AUX1-0
W1
Y2I
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
Y2O
Y1I
Y1O
1K1 C
C R
R(+)
24 VAC
1
2
C(-)
7
MS3103J
3 S-BUS
OR MS3105J
4 S-BUS
THERMOSTAT
5
C7400S
RETURN AIR
TEMP/HUMIDITY
(ENTHALPY)
SYLKBUS SENSOR
Y1
W1
C
1
Y2
C
C
C
3
2
G
BASIC I/O BOARD
C
TERMINAL
4
6
8
5
NOTES: SEE INSTALLATION INSTRUCTIONS
62-0331 FOR SPECIFIC W7220 JADE
WIRING INFORMATION.
1
W1
Y2
C7400S
OUTSIDE AIR
TEMP/HUMIDITY
(ENTHALPY)
SYLKBUS SENSOR
14
RELAY 1, DPDT RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 4 FOR HIGH SPEED FAN WITH W1 CALL.
6
1
+10 Vref
SIGNAL
DEFAULT
REFERENCE OUTPUT
2
AI1+
ANALOG INPUT,
VOLTAGE OR CURRENT*
3
AI1-
ANALOG INPUT COMMON
(CURRENT)
4
AI2+
ANALOG INPUT,
VOLTAGE OR CURRENT
5
AI2
ANALOG INPUT COMMON
(CURRENT)
24V AUX. VOLTAGE
4
RELAY 3, SPST RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 1 FOR LOW SPEED FAN WITH Y1 CALL.
RELAY 4, SPST RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 1 FOR LOW SPEED FAN WITH G CALL.
6
24Vout
GND
I/O GROUND
8
DI1
DIGITAL INPUT 1
9
DI2
10
DI3
11
CM
COMMON A FOR DIN1-DIN6**
12
24Vout
24V AUX. VOLTAGE
13
GND
14
DI4
DIGITAL INPUT 4
PRESET
FREQ
SELECT 1
15
DI5
DIGITAL INPUT 5
PRESET
FREQ
SELECT 2
START FWD
DIGITAL INPUT 2
START REV
DIGITAL INPUT 3
FAULT
I/O GROUND
16
17
DI6
DIGITAL INPUT 6
C
COMMON A FOR DIN1-DIN6**
18
AO1
ANALOG SIGNAL (+OUTPUT)
FAULT RESET
19
AO-/GND
ANALOG OUTPUT COMMON
5 LOW SPEED FAN IS CONFIGURED BY SETTING “MINIMUM FREQUENCY” WITH PARAMETER M1.8 OF THE STARTUP
WIZARD OF THE SMARTVFD HVAC.
30
+24 Vin
24V AUXILIARY INPUT VOLTAGE
A
RS485
DIFFERENTIAL RECEIVER/
TRANSMITTER
6
B
RS485
DIFFERENTIAL RECEIVER/
TRANSMITTER
HIGH SPEED FAN IS CONFIGURED BY SETTING “PRESET FREQUENCY 1” WITH PARAMETER M3.3.12 OF THE
SMARTVFD HVAC.
7 WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B
AND W2 MAY BE LABELED W.
8
CURRENT
7
2 RELAY 2, DPST RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 4 FOR HIGH SPEED FAN WITH Y2 CALL.
3
VOLTAGE
OP FREQ
I/O BOARD ON SMARTVFD
HVAC DRIVE HVFDSD
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
M35159A
Fig. 13. Jade with Prestige IAQ thermostat, communicating actuator, CO2 and VFD.
11
63-2700—10
JADE™ ECONOMIZER MODULE
M7215
ON JADE CONTROLLER:
1. Y2-O CONNECT TO STAGE 2 MECHANICAL COOLING
2. Y1-O CONNECT TO STAGE 1 MECHANICAL COOLING
3. MAT IS MIXED AIR SENSOR C7250A1001
4. OAT IS TEMPERATURE CHAGEOVER C7250A1001
SENSOR OR S-BUS OA ENTHALPY SENSOR C7400S1000
5. AUX1 OUT PROGRAM TO SYS IN SYSTEM SETUP MENU
JADE W7220A1000
AUX2-I
OCC
E-GND
ACT (2-10V)
ACT COM
ACT 24V
TR
TR1
IN
IN
AUX1 OUT
Y2I
Y2O
Y1I
Y1O
C
R
+
–
C
R
PRESTIGE
THX9421R5013
TO THERMOSTAT
EIM
CONV
POWER
HEAT
STATUS
LEDS
COOL
FAN
U1
U2
U3
A
RELAY
R822N1011
1
3
KIT WITH PRESTIGE AND EIM
YTHX9421R5051
1
EIM
THM5421R1013
R
C
SENSORS
1
TRANSFORMER
24
VAC
120
VAC
THE TRANSFORMER NEEDS
TO BE 100VA.
M35157
Fig. 14. Jade with Prestige IAQ thermostat and EIM, communicating actuator, CO2 and VFD.
63-2700—10
12
JADE™ ECONOMIZER MODULE
EXH1 and EXH2 wiring:
Relay Digital Output Rating at 30 Vac (maximum powerfrom Class 2 input only): 1.5A run;
3.5A inrush @ 0.45PF (200,000 cycles) or
7.5A inrush @ 0.45PF (100,000 cycles)
If the inrush or FLA amps is above listed limits OR if the fan is a line voltage fan, an external relay will be required.
If no relay is required, the EXH1 or AUX1 out is wired to one side of the fan and the other side is wired to system common "C" on
the W7220 or equipment terminal board. (W7220 powered off the system transformer).
If a relay is required, the coil of the relay would be wired between the EXH1 or AUX1 and the C terminal of the W7220.
MA TEMP
SENSOR
20K NTC
ROOF TOP UNIT
W7220 ECONOMIZER CONTROLLER MODULE
Y1
O/B
OCC
1
MAT
MAT
OAT
OAT
OAT TEMP
SENSOR
20K NTC
CO2
SENSOR
2-10 VDC
(OPTIONAL)
G
W1
Y2
W2
3
1K1
AUX2-I
OCC
E-GND
AUX1-0
Y2I
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
Y2O
Y1I
Y1O
C R
1K1
24 VAC
R(+)
C(-)
MS7503 OR MS7505
2
3
1
NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OAT TERMINALS ONLY IN THIS CONFIGURATION.
2
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O
OR B AND W2 MAY BE LABELED W.
3
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
THERMOSTAT
M32564D
Fig. 15. Stand-alone dry-bulb Economizer configuration with Honeywell MS7503 or MS7505 Direct Coupled Actuator.
13
63-2700—10
JADE™ ECONOMIZER MODULE
MA TEMP
SENSOR
20K NTC
ROOF TOP UNIT
W7220 ECONOMIZER CONTROLLER MODULE
Y1
O/B
OCC
1
CO2
SENSOR
2-10 VDC
(OPTIONAL)
W2
3
1K1
AUX2-I
OCC
E-GND
MAT
MAT
OAT
OAT
OAT TEMP
SENSOR
20K NTC
G
W1
Y2
AUX1-0
Y2I
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
Y2O
Y1I
Y1O
C R
1K1
1
2
24 VAC
MS3103J
3 S-BUS
OR MS3105J
R(+)
C(-)
4 S-BUS
2
5
1
NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OAT TERMINALS ONLY IN THIS CONFIGURATION.
2
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O
OR B AND W2 MAY BE LABELED W.
3
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
THERMOSTAT
M32650D
Fig. 16. Stand-alone dry-bulb Economizer configuration with Honeywell MS3103J or MS3105J communicating actuators.
63-2700—10
14
JADE™ ECONOMIZER MODULE
Economizer with Sylk Bus Sensors
A standalone economizer with Sylk Bus sensors uses Sylk Bus communications (see Fig. 17, Fig. 18 and Fig. 19). The Sylk Bus
reduces wiring requirements while providing additional functionality.
2
MA TEMP
SENSOR
20K NTC
ROOF TOP UNIT
W7220 ECONOMIZER CONTROLLER MODULE
O/B
Y1
OCC
MAT
MAT
AUX2-I
OCC
E-GND
S-BUS
Y2O
Y1I
ACT (2-10V)
ACT COM
ACT 24V
Y1O
R(+)
24 VAC
M7215
+
IN
-
C(-)
3
OUTSIDE AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
1
1K1
C R
TR
IN
4
1K1
Y2I
IAQ (2-10V)
IAQ COM
IAQ 24V
TR1
W2
AUX1-0
S-BUS
CO2
SENSOR
2-10 VDC
(OPTIONAL)
G
W1
Y2
RETURN AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
THERMOSTAT
1
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY
(ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL
AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.
2
DO NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN THIS
CONFIGURATION.
3
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS
MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION
RELAY BETWEEN O AND C.
4
M32565D
Fig. 17. Economizer with Sylk Bus sensors for enthalpy configuration with Honeywell M7215 black motor.
15
63-2700—10
JADE™ ECONOMIZER MODULE
2
MA TEMP
SENSOR
20K NTC
ROOF TOP UNIT
W7220 ECONOMIZER CONTROLLER MODULE
O/B
Y1
OCC
MAT
MAT
AUX2-I
OCC
E-GND
S-BUS
S-BUS
CO2
SENSOR
2-10 VDC
(OPTIONAL)
W2
4
1K1
AUX1-0
Y2I
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
Y2O
Y1I
Y1O
1K1
C R
R(+)
24 VAC
MS7503 OR MS7505
3
C(-)
3
OUTSIDE AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
1
G
W1
Y2
RETURN AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
THERMOSTAT
1
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY
(ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL AS
SHOWN IN THE LOWER LEFT OF THIS FIGURE.
2
DO NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN THIS
CONFIGURATION.
3
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER:
W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
4
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION
RELAY BETWEEN O AND C.
M32566D
Fig. 18. Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS7503 or MS7505 Direct
Coupled Actuator.
63-2700—10
16
JADE™ ECONOMIZER MODULE
ROOF TOP UNIT
MA TEMP
SENSOR
20K NTC
W7220 ECONOMIZER CONTROLLER MODULE
O/B
Y1
OCC
MAT
MAT
CO2
SENSOR
2-10 VDC
(OPTIONAL)
AUX1-0
Y2I
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
Y2O
Y1I
Y1O
1K1
C R
R(+)
24 VAC
1
2
2
3 S-BUS
W2
4
1K1
AUX2-I
OCC
E-GND
S-BUS
S-BUS
G
W1
Y2
C(-)
MS3103J
OR MS3105J
3
4 S-BUS
5
THERMOSTAT
C7400S
OUTSIDE AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
C7400S
RETURN AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
1
1
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEM/HUMIDITY
(ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED
CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.
2
THE S-BUS COMPONENTS MAY BE DAISY CHAINED TO ANOTHER S-BUS
COMPONENT.
3
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS
MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
4
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN
ISOLATION RELAY BETWEEN O AND C.
M32653D
Fig. 19. Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS3103J or MS3105J
communicating actuators.
MAT
MAT
OAT
OAT
S-BUS
S-BUS
S-BUS
S-BUS
S-BUS
S-BUS
2-PIN CONNECTOR
NEEDED (VHR-2N)
3-PIN CONNECTOR
NEEDED (VHR-3N)
JADE CONTROLLER
OCC
E-GND
EXH1
AUX1 OUT
AUX1-O
Y2-I
Y2-O
Y1-I
Y1-O
R
C
Y2-I
Y2-O
Y1-I
Y1-O
C
R
RIGHT TERMINAL
BLOCK LABEL
LEFT TERMINAL
BLOCK LABEL
PART NUMBER
JST VH CONNECTOR PLASTIC HOUSING VHR-2N PLUS 2 PIECES
JST VH CONNECTOR PLASTIC HOUSING VHR-3N PLUS 3 PIECES
JST VH CONNECTOR PLASTIC HOUSING VHR-4N PLUS 4 PIECES
JST VH CONNECTOR PLASTIC HOUSING VHR-6N PLUS 6 PIECES
TYPE 42743-2
AUX2 IN
AUX2-I
6-PIN CONNECTOR
NEEDED (VHR-6N)
IAQ 2-10
IAQ COM
IAQ 24V+
ACT 2-10
ACT COM
ACT 24V+
NOT USED
4-PIN CONNECTOR
NEEDED (VHR-4N)
NOT USED
AUX2-1
OCC
E-GND
EXH1
AUX1-O
SVH-21T-P1.1 METAL CONTACT
SVH-21T-P1.1 METAL CONTACT
SVH-21T-P1.1 METAL CONTACT
SVH-21T-P1.1 METAL CONTACT
PIN COUNT
2
3
4
6
1
NOTE: THOSE ARE NOT HONEYWELL PART NUMBERS. TO PLACE AN ORDER - CONTACT YOUR SALES REPRESENTATIVE.
MANUFACTURER
JST VH
JST VH
JST VH
JST VH
AMP
1/4 INCH QUICK CONNECT
FOR M7215 BLACK MOTOR
M31402E
Fig. 20. OEM wiring harness information. Refer to previous wiring diagrams for detailed application wiring.
17
63-2700—10
JADE™ ECONOMIZER MODULE
INTERFACE OVERVIEW
• Press the  button to increase (change) the displayed
parameter value.a
• Press the  button to decrease (change) the displayed
parameter value.a
• Press the  button to accept the displayed value and store it
in non-volatile RAM.
• CHANGE STORED displays.
This section describes how to use the Economizer’s user
interface for:
• Keypad and menu navigation
• Settings and parameter changes
• Menu structure and selection
User Interface
• Press the
button (MenuUp/Exit) to return to the
previous menu.
The user interface consists of an LCD display and a 4-button
keypad on the front of the Economizer module. The LCD is a
16 character by 2 line dot matrix display.
a
When values are displayed, pressing and holding the  or 
button causes the display to automatically increment.
Menu Structure
Table 5 on page 19 illustrates the complete hierarchy of menus
and parameters for the JADE™ Economizer system.
2 LINE
LCD
MENU UP
(EXIT)
BUTTON
SCROLL
(UP/DOWN)
BUTTONS
The Menus in display order are:
• STATUS
• SETPOINTS
• SYSTEM SETUP
• ADVANCED SETUP
• CHECKOUT
• ALARMS
SELECT (ENTER)
BUTTON
IMPORTANT
Table 5 on page 19 illustrates the complete hierarchy.
Your menu parameters will be different depending on
your configuration.
M32274A
Fig. 21. Economizer LCD and Keypad Layout.
Keypad
For example if you do not have a DCV (CO2) sensor,
then none of the DCV parameters appear and only
MIN POS will display. If you have a CO2 sensor, the
DCV MIN and DCV MAX will appear AND if you have
2 speed fan DCV MIN (high and low speed) and DCV
MAX (high and low speed will appear).
The four navigation buttons illustrated in Fig. 21 are used to
scroll through the menus and menu items, select menu items,
and to change parameter and configuration settings.
Using the Keypad with Menus
To use the keypad when working with menus:
• Press the  button to move to the previous menu.
• Press the  button to move to the next menu.
• Press the  button (Enter) to display the first item in the
currently displayed menu.
SETUP AND CONFIGURATION
Before being placed into service, the JADE™ Economizer
module must be setup and configured for the installed system.
• Press the
button (Menu up) to exit a menu’s item and
return to the list of menus.
IMPORTANT
During setup, the Economizer module is live at all
times.
Using the Keypad with Settings and
Parameters
The setup process uses a hierarchical menu structure that is
easy to use. You press the  and  arrow buttons to move
forward and backward through the menus and press the 
button to select and confirm setup item changes.
To use the keypad when working with Setpoints, System and
Advanced Settings, Checkout tests, and Alarms:
• Navigate to the desired menu.
• Press the  button (Enter) to display the first item in the
currently displayed menu.
• Use the  and  buttons to scroll to the desired
parameter.
• Press the  button (Enter) to display the value of the
currently displayed item.
63-2700—10
Time-out and Screensaver
When no buttons have been pressed for 10 minutes, the LCD
displays a screen saver, which cycles through the Status items.
Each Status items displays in turn and cycles to the next item
after 5 seconds.
18
JADE™ ECONOMIZER MODULE
Table 5. Menu Structurea.
Menu
STATUS
Parameter
Parameter
Default
Value
Parameter
Range and
Incrementb
Notes
ECON AVAIL
NO
YES/NO
YES = economizing available; the system can use Outdoor Air for
free cooling when required.
ECONOMIZING
NO
YES/NO
YES = Outdoor Air being used for 1st stage cooling.
OCCUPIED
NO
YES/NO
YES = OCC signal received from space thermostat or unitary
controller.
YES = 24 Vac on terminal OCC
No = 0 Vac on terminal OCC.
HEAT PUMP
n/ac
COOL
HEAT
Displays COOL or HEAT when system is set to heat pump (nonconventional)
COOL Y1-IN
OFF
ON/OFF
Y1-I signal from space thermostat or unitary controller for
cooling stage 1.
ON = 24 Vac on term Y1-I
OFF = 0 Vac on term Y1-I
COOL Y1-OUT
OFF
ON/OFF
Cool Stage 1 Relay Output to mechanical cooling (Y1-OUT
terminal).
COOL Y2-IN
OFF
ON/OFF
Y2-I signal from space thermostat or unitary controller for
second stage cooling.
ON = 24 Vac on term Y2-I
OFF = 0 Vac on term Y2-I
COOL Y2-OUT
OFF
ON/OFF
Cool Stage 2 Relay Output to mechanical cooling (Y2-OUT
terminal).
MA TEMP
_ _._ ºF
-40 to 150 ºF
Displays value of measured mixed air from MAT sensor.
Displays --.- if not connected, short, or out- of-range.
DA TEMP
_ _._ ºF
-40 to 150 ºF
Displays when Discharge Air Sylk Bus sensor is connected and
displays measured discharge air temperature.
Displays --.-°F if sensor sends invalid value, if not connected,
short or out-of-range.
OA TEMP
_ _._ ºF
-40 to 140 ºF
Displays measured value of outdoor air temperature.
Displays --°F if sensor sends invalid value, if not connected,
short or out-of-range.
OA HUM
__%
0 to 100%
Displays measured value of outdoor humidity from OA Sylkbus
sensor. Displays --% if not connected, short, or out- of-range.
RA TEMP
_ _._ ºF
0 to 140 ºF
Displays measured value of return air temperature from RA
Sylkbus sensor. Displays --°F if sensor sends invalid value, if not
connected, short or out-of-range.
RA HUM
__%
0 to 100%
Displays measured value of return air humidity from RA Sylkbus
sensor. Displays --% if sensor sends invalid value, if not
connected, short or out-of-range.
IN CO2
_ _ _ ppm 0 to 2000 ppm
Displays value of measured CO2 from CO2 sensor. Invalid if not
connected, short or out-of-range. May be adjusted in Advanced
menu by Zero offset and Span. See note on page 6 concerning
C7632 sensor.
DCV STATUS
n/a
ON/OFF
Displays ON if above setpoint and OFF if below setpoint, and
ONLY if a CO2 sensor is connected.
DAMPER OUT
2.0V
2.0 to 10.0 V
Displays output voltage or position to the damper actuator.e
ACT POS
n/a
0 to 100%
Displays actual position of actuator.
ACT COUNT
n/a
1 to 65,535
Displays number of times actuator has cycled. 1 Cycle equals
the sum of 180° of movement in any direction.
ACTUATOR
n/a
OK/Alarm (on
Alarm menu)
Displays Error if voltage or torque is below actuator range
EXH1 OUT
OFF
ON/OFF
Output of EXH1 terminal. Displays ON when damper position
reaches programmed percentage setpoint.
ON = 24 Vac Output; OFF = No Output.
19
63-2700—10
JADE™ ECONOMIZER MODULE
Table 5. Menu Structurea. (Continued)
Menu
Parameter
Parameter
Default
Value
Parameter
Range and
Incrementb
Notes
OFF
ON/OFF
Output of AUX1 O terminal Displays ON when damper position
reaches programmed percentage setpoint
ON = 24 Vac Output, OFF = No Output; displays only if AUX1 O =
EXH2
ERV
OFF
ON/OFF
Output of AUX1 O terminal, ON = 24 Vac Output, OFF = No
Output; displays only if AUX1 O = ERV
MECH COOL ON
or
HEAT STAGES ON
0
0, 1, or 2
Displays number of mechanical cooling stages that are active.
FAN SPEED
n/a
LOW or HIGH
Displays speed of fan on a 2-speed fan unit
STATUS
EXH2 OUT
CONTINUED
Displays the stage of heat pump heating that is active.
n/a
ON/OFF
Displays status of heat on a 2-speed fan unit.
53ºF
38 to 70 ºF;
increment by 1
The economizer will modulate the OA damper to maintain the
mixed air temperature at the setpoint.
LOW T LOCK
32ºF
-45 to 80 ºF;
increment by 1
Setpoint determines outdoor temperature when the mechanical
cooling cannot be turned on. Commonly referred to as the
Compressor lockout. At or below the setpoint the Y1-O and
Y2-O will not be energized on the controller.
DRYBLB SET
63ºF
48 to 80 ºF;
increment by 1
Dry bulb setpoint will only appear if using dry bulb change over.
Setpoint determines where the economizer will assume outdoor
air temperature is good for free cooling; e.g.; at 63 ºF setpoint
unit will economizer at 62 ºF and below and not economize at
64 ºF and above. There is a a 2 ºF deadband.
ENTH CURVE
ES3
ES1, ES2, ES3, ES curve will only appear if using enthalpy changeover.
ES4, or ES5
Enthalpy boundary “curves” for economizing using single
enthalpy.
See page 22 for description of enthalpy curves.
DCV SET
1100ppm
500 to 2000
ppm
increment by
100
Displays ONLY if a CO2 sensor is connected.
Setpoint for Demand Control Ventilation of space. Above the
setpoint, the OA dampers will modulate open to bring in
additional OA to maintain a space ppm level below the setpoint.
MIN POS
2.8 V
2 to 10 Vdc
Displays ONLY if a CO2 sensor is NOT connected.
W (HEAT IN)
SETPOINTS MAT SET
With 2-speed fan units MIN POS L (low speed fan) and MIN POS
H (high speed fan) settings are required. Default for MIN POS L
is 3.2V and MIN POS H is 2.8V.
VENTMAX
2.8 V
2 to 10 Vdc
Displays only if a CO2 sensor is connected.
Used for Vbz (ventilation max cfm) setpoint. VENTMAX is the
same setting as MIN POS would be if you did not have the CO2
sensor.
100 to 9990 cfm If OA, MA RA and CO2 sensors are connected and DCV CAL
increment by 10 ENABLE is set to AUTO mode, the OA dampers are controlled by
CFM and displays from 100 to 9990 cfm.
VENTMIN
2.25 V
2 to 10 Vdc
With 2-speed fan units VENTMAX L (low speed fan) and
VENTMAX H (high speed fan) settings are required. Default for
VENTMAX L is 3.2V and VENTMAX H is 2.8V.
2 to 10 Vdc
Displays only if CO2 sensor is connected.
Used for Va (ventilation min cfm) setpoint. This is the ventilation
requirement for less than maximum occupancy of the space.
100 to 9990 cfm If OA, MA RA and CO2 sensors are connected and DCV CAL
increment by 10 ENABLE is set to AUTO mode, the OA dampers are controlled by
CFM and displays from 100 to 9990 cfm.
ERV OAT SPd
63-2700—10
32ºF
2 to 10 Vdc
With 2-speed fan units VENTMIN L (low speed fan) and
VENTMIN H (high speed fan) settings are required. Default for
VENTMIN L is 2.5V and VENTMIN H is 2.25V.
0 to 50 ºF;
increment by 1
Only when AUX1 O = ERV
20
JADE™ ECONOMIZER MODULE
Table 5. Menu Structurea. (Continued)
Menu
Parameter
Parameter
Default
Value
Parameter
Range and
Incrementb
Notes
SETPOINTS EXH1 SET
CONTINUED
50%
0 to 100%;
increment by 1
Setpoint for OA damper position when exhaust fan 1 is powered
by the economizer.
With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high
speed fan) settings are required. Default for Exh1 L is 65% and
Exh1 H is 50%
EXH2 SET
75%
0 to 100%;
increment by 1
Setpoint for OA damper position when exhaust fan 2 is powered
by the economizer. Only used when AUX1 O is set to EHX2.
With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high
speed fan) settings are required. Default for Exh2 L is 80% and
Exh2 H is 75%
INSTALL
01/01/11
UNITS DEG
ºF
ºF or ºC
Sets economizer controller in degrees Fahrenheit or Celsius.
EQUIPMENT
CONV
CONV
HP
CONV = conventional.
HP O/B = Enables Heat Pump mode. Use AUX2 I for Heat Pump
input from thermostat or controller.
AUX2 IN
n/a
Shutdown (SD) In CONV mode:
SD = Enables configuration of shutdown (default);
Heat (W1)
W = Informs controller that system is in heating mode.
HP(O)
HP(B)
NOTE: If using 2-speed fan mode, you must program CONV mode for W. Shutdown is not
available in the two-speed fan mode.
SYSTEM
SETUP
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on Heat.
FAN SPEED
1 speed
1 speed/
2 speed
Sets economizer controller for operation of 1 speed or 2 speed
supply fan. The controller does not control the fan but positions
the OA and RA dampers to the heating or cooling mode. See
page 23 for modes and position.
NOTE: 2-speed fan option also needs Heat (W1) programmed in AUX 2 In.
FAN CFM
5000cfm
100 to 50000
cfm;
increment by
100
This is the capacity of the RTU. The value is found on the label
from the RTU manufacturer. The cfm of the fan is only used with
DCV CAL ENABLE AUO
AUX1 OUT
NONE
NONE
ERV
EXH2
SYS
• NONE = not configured (output is not used)
• ERV= Energy Recovery Ventilatord
• EXH2 = second damper position 24 Vac out for second
exhaust fan.
• SYS = use output as an alarm signal
OCC
INPUT
INPUT or
ALWAYS
When using a setback thermostat with occupancy out (24 Vac),
the 24 Vac is input “INPUT” to the OCC terminal. If no
occupancy output from the thermostat then change program to
“ALWAYS” OR add a jumper from terminal R to OCC terminal.
FACTORY DEFAULT
NO
NO or YES
Resets all set points to factory defaults when set to YES. LCD
will briefly flash YES and change to NO but all parameters will
change to factory default values.
21
63-2700—10
JADE™ ECONOMIZER MODULE
Table 5. Menu Structurea. (Continued)
Menu
Parameter
Parameter
Range and
Incrementb
Notes
45 ºF
35 to 65 ºF;
Temp to activate Freeze Protection (close damper or modulate to
increment by 1º MIN POS if temp falls below set value)
FREEZE POS
CLO
CLO
MIN
CO2 ZERO
0ppm
0 to 500 ppm; CO2 ppm level to match CO2 sensor start level.
increment by 10
CO2 SPAN
2000ppm
CO2 ppm span to match CO2 sensor; e.g.; 500-1500 sensor
1000 to 3000
output would be 500 CO2 zero and 1000 CO2 span. See note on
ppm;
increment by 50 page 6 for C7632 CO2 sensor.
STG3 DLY
2.0h
0 min, 5 min, 15
min, then 15
min intervals.
Up to 4h or OFF
Delay after stage 2 for cool has been active. Turns on 2nd stage
of mechanical cooling when economizer is 1st stage call and
mechanical cooling is 2nd stage call. Allows three stages of
cooling, 1 economizer and 2 mechanical.
OFF = no Stage 3 cooling.
SD DMPR POS
CLO
CLO
OPN
Indicates shutdown signal from space thermostat or unitary
controller. When controller receives 24 Vac input on the SD
terminal in conventional mode, the OA damper will open if
programmed for OPN and OA damper will close if programmed
for CLO. All other controls, e.g., Y1-O, Y2-O, EXH1, etc. will shut
off.
DA LO ALM
45 ºF
NONE
Used for alarm for when the DA air temperature is too low. Set
35ºF to 65ºF in lower range of alarm, below this temperature the alarm will
5ºF increments show on the display.
DA HI ALM
80 ºF
NONE
Used for alarm for when the DA air temperature is too high. Set
70 ºF to 180 ºF high range of alarm, above this temperature the alarm will show
on the display
in 5º F
increments
DCVCAL ENA
MAN
MAN (manual)
AUTO
Turns on the DCV automatic control of the dampers. Resets
ventilation based on the RA, OA and MA sensor conditions.
Requires all sensors (RA, OA, MA and CO2).
This operation is not operable with a 2-speed fan unit.
MAT T CAL
0.0 F°
+/-2.5F°
Allows for the operator to adjust for an out of calibration
temperature sensor
OAS T CAL
0.0F°
+/-2.5F°
Allows for the operator to adjust for an out of calibration
temperature sensor
OAS H CAL
0% RH
+/-10% RH
Allows for the operator to adjust for an out of calibration
humidity sensor
RA T CAL
0.0F°
+/-2.5F°
Allows for the operator to adjust for an out of calibration
temperature sensor
RA H CAL
0% RH
+/-10% RH
Allows for the operator to adjust for an out of calibration
humidity sensor
DA T CAL
0.0 F°
+/-2.5F°
Allows for the operator to adjust for an out of calibration
temperature sensor
2SP FAN DELAY
5 Minutes
0 to 20 minutes When in economizing mode this is the delay for the high speed
in 1 minute
fan to try to satisfy the call for second stage cooling before the
increments.
first stage mechanical cooling is enabled.
ADVANCED MA LO SET
SETUP
63-2700—10
Parameter
Default
Value
Damper position when freeze protection is active (closed or MIN
POS).
22
JADE™ ECONOMIZER MODULE
Table 5. Menu Structurea. (Continued)
Menu
Parameter
CHECKOUT DAMPER MINIMUM
POSITION
f
DAMPER OPEN
Parameter
Default
Value
Parameter
Range and
Incrementb
Notes
n/a
n/a
The checkout for the damper minimum positions is based on the
system. See Table 6.
n/a
n/a
Positions damper to the full open position.
Exhaust fan contacts enable during the DAMPER OPEN test.
Make sure you pause in this mode to allow for exhaust contacts
to energize due to the delay in the system.
DAMPER CLOSE
n/a
n/a
Positions damper to the fully closed position.
CONNECT Y1-O
n/a
n/a
Closes the Y1-O relay (Y1-O).
See CAUTION on page 30
CONNECT Y2-O
n/a
n/a
Closes the Y2-O relay (Y2-O).
See CAUTION on page 30
CONNECT AUX1-O
n/a
n/a
Energizes the AUX1-O output. If AUX1-O setting is:
• NONE – no action taken
• ERV – 24 Vac out. Turns on or signals an ERV that the
conditions are not good for economizing but are good for
ERV operation.d
• SYS – 24 Vac out. Issues a system alarm.
CONNECT EXH1
n/a
n/a
Closes the power exhaust fan 1 relay (EXH1)
Alarms display only when they are active. The menu title
“ALARMS (#)” includes the number of active alarms in
parenthesis (). When using SYLK bus sensors, "SYLK" will
appear on the screen, and when using 20k OA temperature
sensors, "SENS T" will appear on the screen.
ALARMS(#)
MA T SENS ERR
n/a
n/a
Mixed air sensor has failed or become disconnected - check
wiring then replace sensor if the alarm continues
CO2 SENS ERR
n/a
n/a
CO2 sensor has failed, gone out of range or become
disconnected - check wiring then replace sensor if the alarm
continues
Outdoor air enthalpy sensor has failed or become disconnected check wiring then replace sensor if the alarm continues
OA SYLK T ERR
n/a
n/a
OA SYLK H ERR
n/a
n/a
RA SYLK T ERR
n/a
n/a
RA SYLK H ERR
n/a
n/a
DA SYLK T ERR
n/a
n/a
Discharge air sensor has failed or become disconnected - check
wiring then replace sensor if the alarm continues
OA SENS T ERR
n/a
n/a
Outdoor air temperature sensor has failed or become
disconnected - check wiring then replace sensor if the alarm
continues
ACT ERROR
n/a
n/a
Actuator has failed or become disconnected - check for stall,
over voltage, under voltage and actuator count. Replace actuator
if damper is moveable and supply voltage is between 21.6 V and
26.4 V. Check actuator count on STATUS menu.
FREEZE ALARM
n/a
n/a
Check if outdoor temperature is below the LOW Temp Lockout
on setpoint menu. Check if Mixed air temperature on STATUS
menu is below the Lo Setpoint on Advanced setup menu. When
conditions are back in normal range then the alarm will go away.
SHUTDOWN ACTIVE
n/a
n/a
AUX2 IN is programmed for SHUTDOWN and 24 V has been
applied to AUX 2IN terminal
DMP CAL RUNNING
n/a
n/a
If DCV Auto enable has been programmed, when the Jade is
completing a calibration on the dampers, this alarm will display.
Wait until the calibration is completed and the alarm will go
away. Must have OA, MA and RA sensors for DCV calibration;
set up is in the Advanced setup menu
DA SENS ALM
n/a
n/a
Discharge air temperature is out of the range set in the
ADVANCED SETUP Menu. Check the temperature of the
discharge air.
Return air enthalpy sensor has failed or become disconnected check wiring then replace sensor if the alarm continues
23
63-2700—10
JADE™ ECONOMIZER MODULE
Table 5. Menu Structurea. (Continued)
Menu
Parameter
Parameter
Default
Value
Parameter
Range and
Incrementb
Notes
n/a
n/a
When AUX1-O is set to SYS and there is any alarm (e.g., failed
sensors, etc.), the AUX1-O terminal has 24 Vac out.
ACT UNDER V
n/a
n/a
Voltage received by Actuator is above expected range
ACT OVER V
n/a
n/a
Voltage received by Actuator is below expected range
ACT STALLED
n/a
n/a
Actuator stopped before achieving commanded position
ALARMS(#) SYS ALARM
CONTINUED
FEATURES ADJUSTABLE ONLY BY USE OF THE W7220 PC MOD TOOL
a
If enabled this feature allows the operator to suppress the stall
alarm in a specific range of the actuator stroke.
ACT STALL ALARM
SUPPRESSION
Disabled
Enabled or
Disabled
SELECT TYPE OF
CONTROLLER
W7220
W7220, W7218 The operator can configure a program for a customer or job and
or Presave the program in the file. Found on the configuration page of
programmed
the Trade version
special
ACTUATOR SLIPPAGE
ALARM
Enabled
Enabled or
Disabled
Alarms if the actuator becomes disconnected from the damper
or is slipping on the shaft.
If Enabled, the Jade system will complete a system air
temperature check.
If there is the expected change in system air temperature, then
Jade assumes the actuator is connected to the damper.
If the expected system air temperature changes do not occur,
then an actuator slippage alarm is displayed on the Jade LCD.
Found on the configuration page of the Trade version.
ACTUATOR SLIPPAGE
ALARM SENSITIVITY
Low
Low, Standard
or High
Sensitivity can be set to HIGH, STANDARD or LOW. High means
the system will check 5 times for the damper to move before
displaying the alarm. Standard is 10 times before the alarm is
displayed. Low is 20 times before the alarm is displayed. Found
on the economizer page of the Trade version.
LOCATION OF
ECONOMIZER
CONTROL SENSOR
Before the Before coil or
cooling
AUTO
coil
DAMPER AIA
THRESHOLD
15
degrees
The operator can choose if the economizer control sensor
(normally referred to as the Mixed air sensor) is placed in the
mixed air (before the coil) or Auto in the case the sensor is
placed after the cooling coil. Found on the configuration page of
the Trade version.
5 to 40 degrees Damper threshold feature (Adaptive Integral Action) is the
difference in the mixed air temperature reported by the MAT
sensor and the MAT setpoint. Lower (2 degrees) transfer rate
between the actual MAT sensor reading and the MAT setpoint
normally means the damper is closing and opening faster.
Larger transfer rate (up to 20 degrees) between the sensor
reading and the setpoint normally means the damper is opening
and closing slower. Used in applications where there is a large
MA space or there is a long duct between the OA and the MA
causing a delay. Found on the economizer page of the Trade
version.
Table 5 illustrates the complete hierarchy. Your menu parameters may be different depending on your configuration.
For example if you do not have a DCV (CO2) sensor, then none of the DCV parameters appear.
b When
values are displayed, pressing and holding the  or  button causes the display to automatically increment.
n/a = not applicable
d ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing - the ERV terminal will be energized. In
the Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.
e When used with Honeywell communicating actuator the damper out is reported in XX.X% open versus XX.X Vdc.
f
After 10 minutes without a command or mode change, the controller will change to normal operation.
c
63-2700—10
24
JADE™ ECONOMIZER MODULE
Table 6. Damper minimum position settings and readings on checkout menu.
Fan Speed
Demand Control Ventilation
(CO2 Sensor)
Setpoints
Checkout
1
NO
MIN POS
VMAX-HS
1
NO
N/A
N/A
2
NO
MIN POS H
VMAX-HS
2
NO
MIN POS L
VMAX-LS
1
YES
VENT MIN
VMIN-HS
1
YES
VENT MAX
VMAX-HS
2
YES
VENT MIN H
VMIN-HS
2
YES
VENT MAX H
VMAX-LS
2
YES
VENT MINL
N/A
2
YES
VENT MAX L
N/A
SEQUENCE OF OPERATION
Table 7. Dry Bulb Operation No DCV (CO2 sensor) - 1 Speed Fan.
DCV
None
None
OA Good to
economize?
No
Yes
Y1-I
Off
Y2-I
FAN SPD
Y1-O
0-v/Off
Y2-O
0-v/Off
Occupied
MIN POS
Unoccupied
Off
High
Closed
On
Off
High
24-v/On
0-v/Off
MIN POS
Closed
On
On
High
24-v/On
24-v/On
MIN POS
Closed
Off
Off
High
0-v/Off
0-v/Off
MIN POS
Closed
On
Off
High
0-v/Off
0-v/Off
MIN POS to FullOpen
Closed to Full-Open
On
On
High
24-v/On
0-v/Offa
MIN POS to FullOpen
Closed to Full-Open
a With
stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the
call for Y1-I and Y2-I have not been satisfied.
Table 8. Dry Bulb Operation With DCV (CO2 sensor) - 1 Speed Fan.
DCV
OA Good to
economize?
Below CO2 No
set
Yes
Above CO2 No
set
Y1-I
Y2-I
FAN SPD
Y1-O
Y2-O
Occupied
Unoccupied
Off
Off
High
0-v/Off
0-v/Off
VENTMIN
Closed
On
Off
High
24-v/On
0-v/Off
VENTMIN
Closed
On
On
High
24-v/On
24-v/On
VENTMIN
Closed
Off
Off
High
0-v/Off
0-v/Off
VENTMIN
Closed
On
Off
High
0-v/Off
0-v/Off
VENTMIN to FullOpen
Closed to Full-Open
On
On
High
24-v/On
0-v/Offa
VENTMIN to FullOpen
Closed to Full-Open
Off
Off
High
0-v/Off
0-v/Off
VENTMIN to
VENTMAX
Closed
On
Off
High
24-v/On
0-v/Off
VENTMIN to
VENTMAX
Closed
25
63-2700—10
JADE™ ECONOMIZER MODULE
DCV
OA Good to
economize?
Yes
a
Y1-I
Y2-I
FAN SPD
Y1-O
Y2-O
Occupied
Unoccupied
On
On
High
24-v/On
24-v/On
VENTMIN to
VENTMAX
Closed
Off
Off
High
0-v/Off
0-v/Off
VENTMIN to
VENTMAX
Closed
On
Off
High
0-v/Off
0-v/Off
VENTMIN to FullOpen
Closed to Full-Open
On
On
High
24-v/On
0-v/Offa
VENTMIN to FullOpen
Closed to Full-Open
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the
call for Y1-I and Y2-I have not been satisfied.
Table 9. Enthalpy Operation No DCV (CO2 sensor) - 1 Speed Fan.
DCV
None
None
OA Good to
economize?
No
Yes
Y1-I
Y2-I
FAN SPD
Y1-O
Y2-O
Occupied
Unoccupied
Off
Off
High
0-v/Off
0-v/Off
MIN POS
Closed
On
Off
High
24-v/On
0-v/Off
MIN POS
Closed
On
On
High
24-v/On
24-v/On
MIN POS
Closed
Off
Off
High
0-v/Off
0-v/Off
MIN POS
Closed
On
Off
High
0-v/Off
0-v/Off
MIN POS to FullOpen
Closed to Full-Open
On
On
High
24-v/On
0-v/Offa
MIN POS to FullOpen
Closed to Full-Open
a With
stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the
call for Y1-I and Y2-I have not been satisfied.
Table 10. Enthalpy Operation With DCV (CO2 sensor) - 1 Speed Fan.
DCV
Below set
OA Good to
economize?
No
Yes
Above set
No
Yes
Y1-I
Off
Y2-I
FAN SPD
Y1-O
Y2-O
Occupied
Unoccupied
Off
High
0-v/Off
0-v/Off
VENTMIN
Closed
On
Off
High
24-v/On
0-v/Off
VENTMIN
Closed
On
On
High
24-v/On
24-v/On
VENTMIN
Closed
Off
Off
High
0-v/Off
0-v/Off
VENTMIN
Closed
On
Off
High
0-v/Off
0-v/Off
VENTMIN to FullOpen
Closed to Full-Open
On
On
High
24-v/On
0-v/Offa
VENTMIN to FullOpen
Closed to Full-Open
Off
Off
High
0-v/Off
0-v/Off
VENTMIN to
VENTMAX
Closed
On
Off
High
24-v/On
0-v/Off
VENTMIN L to
VENTMAX
Closed
On
On
High
24-v/On
24-v/On
VENTMIN H to
VENTMAX
Closed
Off
Off
High
0-v/Off
0-v/Off
VENTMIN L to
VENTMAX
Closed
On
Off
High
0-v/Off
0-v/Off
VENTMIN to FullOpen
Closed to Full-Open
On
On
High
DELAYb
24-v/On
0-v/Offa
VENTMIN to FullOpen
Closed to Full-Open
a With
stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the
call for Y1-I and Y2-I have not been satisfied.
b With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to
satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage
mechanical cooling is enabled.
63-2700—10
26
JADE™ ECONOMIZER MODULE
Table 11. Dry Bulb Operation No DCV (CO2 sensor) - 2 Speed Fan.
DCV
None
None
OA Good to
economize?
No
Yes
Y1-I
Y2-I
FAN SPD
Y1-O
Y2-O
Occupied
Unoccupied
Off
Off
Low
0-v/Off
0-v/Off
MIN POS L
Closed
On
Off
Low
24-v/On
0-v/Off
MIN POS L
Closed
On
On
High
24-v/On
24-v/On
MIN POS H
Closed
Off
Off
Low
0-v/Off
0-v/Off
MIN POS L
Closed
On
Off
Low
0-v/Off
0-v/Off
MIN POS L to FullOpen
Closed to Full-Open
On
On
High
DELAYb
24-v/On
0-v/Offa
MIN POS H to Full- Closed to Full-Open
Open
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the
call for Y1-I and Y2-I have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to
satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage
mechanical cooling is enabled.
Table 12. Dry Bulb Operation With DCV (CO2 sensor) - 2 Speed Fan.
DCV
Below set
OA Good to
economize?
No
Yes
Above set
No
Yes
Y1-I
Y2-I
FAN SPD
Y1-O
Y2-O
Occupied
Unoccupied
Off
Off
Low
0-v/Off
0-v/Off
VENTMIN L
Closed
On
Off
Low
24-v/On
0-v/Off
VENTMIN L
Closed
On
On
High
24-v/On
24-v/On
VENTMIN H
Closed
Off
Off
Low
0-v/Off
0-v/Off
VENTMIN L
Closed
On
Off
Low
0-v/Off
0-v/Off
VENTMIN L to Full- Closed to Full-Open
Open
On
On
High
24-v/On
0-v/Offa
VENTMIN H to Full- Closed to Full-Open
Open
Off
Off
Low
0-v/Off
0-v/Off
VENTMIN L to
VENTMAX
Closed
On
Off
Low
24-v/On
0-v/Off
VENTMIN L to
VENTMAX
Closed
On
On
High
24-v/On
24-v/On
VENTMIN H to
VENTMAX
Closed
Off
Off
Low
0-v/Off
0-v/Off
VENTMIN L to
VENTMAX
Closed
On
Off
Low
0-v/Off
0-v/Off
VENTMIN L to Full- Closed to Full-Open
Open
On
On
High
DELAYb
24-v/On
0-v/Offa
VENTMIN H to Full- Closed to Full-Open
Open
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the
call for Y1-I and Y2-I have not been satisfied.
b With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to
satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage
mechanical cooling is enabled.
Table 13. Enthalpy Operation No DCV (CO2 sensor) - 2 Speed Fan.
DCV
NO CO2
SENSOR
OA Good to
economize?
No
Y1-I
Y2-I
FAN SPD
Y1-O
Y2-O
Occupied
Unoccupied
Off
Off
Low
0-v/Off
0-v/Off
MIN POS L
Closed
On
Off
Low
24-v/On
0-v/Off
MIN POS L
Closed
27
63-2700—10
JADE™ ECONOMIZER MODULE
DCV
OA Good to
economize?
Yes
Y1-I
Y2-I
FAN SPD
Y1-O
Y2-O
Occupied
Unoccupied
On
On
High
24-v/On
24-v/On
MIN POS H
Closed
Off
Off
Low
0-v/Off
0-v/Off
MIN POS L
Closed
On
Off
Low
0-v/Off
0-v/Off
MIN POS L to FullOpen
Closed to Full-Open
On
On
High
DELAYb
24-v/On
0-v/Offa
MIN POS H to Full- Closed to Full-Open
Open
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the
call for Y1-I and Y2-I have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to
satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage
mechanical cooling is enabled.
Table 14. Enthalpy Operation With DCV (CO2 sensor) - 2 Speed Fan.
DCV
Below set
OA Good to
economize?
No
Yes
Above set
No
Yes
Y1-I
Off
Y2-I
Off
FAN SPD
Low
Y1-O
Y2-O
Occupied
Unoccupied
0-v/Off
0-v/Off
VENTMIN L
Closed
On
Off
Low
24-v/On
0-v/Off
VENTMIN L
Closed
On
On
High
24-v/On
24-v/On
VENTMIN H
Closed
Closed
Off
Off
Low
0-v/Off
0-v/Off
VENTMIN L
On
Off
Low
0-v/Off
0-v/Off
VENTMIN L to Full- Closed to Full-Open
Open
On
On
High
24-v/On
0-v/Offa
VENTMIN H to Full- Closed to Full-Open
Open
Off
Off
Low
0-v/Off
0-v/Off
VENTMIN L to
VENTMAX
Closed
On
Off
Low
24-v/On
0-v/Off
VENTMIN L to
VENTMAX
Closed
On
On
High
24-v/On
24-v/On
VENTMIN H to
VENTMAX
Closed
Off
Off
Low
0-v/Off
0-v/Off
VENTMIN L to
VENTMAX
Closed
On
Off
Low
0-v/Off
0-v/Off
VENTMIN L to Full- Closed to Full-Open
Open
On
On
High
DELAYb
24-v/On
0-v/Offa
VENTMIN H to Full- Closed to Full-Open
Open
aWith
stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the
call for Y1-I and Y2-I have not been satisfied.
b With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to
satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage
mechanical cooling is enabled.
63-2700—10
28
JADE™ ECONOMIZER MODULE
ECONOMIXING
DUAL ENTHALPY
HIGH LIMIT
AVAILABLE
NOT AVAILABLE
SINGLE ENTHALPY
)
RH
(%
P2 (T,RH)
ABSOLUTE HUMIDITY
RA
M
HU
P1
(T,RH)
RA TEMP
EN
TH
AL
PY
ES5
ES4
ES3
ES2
ES1
TEMPERATURE
HL
M32286A
Fig. 22. Single Enthalpy curve and boundaries.
Table 15. Single Enthalpy and Dual Enthalpy High Limit Curves.
Point P1
Point P2
Enthalpy
Curve
Temp.
Dry-Bulb (°F)
Temp.
Dewpoint (°F)
Enthalpy
(btu/lb/da)
Temp. °F
Humidity %RH
Temp. °F
Humidity %RH
ES1
80.0
60.0
28.0
80.0
36.8
66.3
80.1
ES2
75.0
57.0
26.0
75.0
39.6
63.3
80.0
ES3
70.0
54.0
24.0
70.0
42.3
59.7
81.4
ES4
65.0
51.0
22.0
65.0
44.8
55.7
84.2
ES5
60.0
48.0
20.0
60.0
46.9
51.3
88.5
HL
86.0
66.0
32.4
86.0
38.9
72.4
80.3
Two-Speed Fan Operation
The later versions of the W7220 Jade controller have the
capability to work with a system using a 2-speed supply fan.
The W7220 does not control the supply directly but uses the
following input status to determine the speed of the supply fan
and controls the OA damper to the required position.
Enthalpy Settings
When the OA temperature, enthalpy and dew point are below
the respective setpoints, the Outdoor Air can be used for
economizing. Fig. 22 shows the new single enthalpy
boundaries in the W7220. There are 5 boundaries (setpoints
ES1 through ES5), which are defined by dry bulb temperature,
enthalpy and dew point.
State
Refer to Table 15 for the ENTH CURVE setpoint values.
To use enthalpy the W7220 must have a C7400S Sylkbus
sensor for OA. The W7220 calculates the enthalpy and dew
point using the OA temperature and humidity input from the OA
sensor. When the OA temperature, OA humidity and OA dew
point are all below the selected boundary, the economizer sets
the economizing mode to YES, economizing is available.
Fan Speed
OCC
Low
Y1
Low
Y2
High
W
High
The W (heating mode) is not controlled by the W7220 but it
requires the status to know where to position the OA damper
for minimum position for the fan speed.
The 2 speed fan delay is available when the system is
programmed for 2 speed fan (in the System Setup menu item).
The 2 speed fan delay is defaulted to 5 minutes and can be
changed in the Advanced Setup menu item. When the unit has
a call for Y1 In and in the free cooling mode and there is a call
for Y2 In, the 2-speed fan delay starts and the OA damper will
modulate 100% open, the supply fan should be set to high
speed by the unit controller. After the delay one of two actions
will happen:
When conditions are above the selected boundary, the
conditions are not good to economize and the mode is set to
NO.
Fig. 22 shows the 5 current boundaries. There is also a high
limit boundary for differential enthalpy. The high limit boundary
is ES1 when there are no stages of mechanical cooling
energized and HL when a compressor stage is energized.
Table 15 provides the values for each boundary limit.
• The Y2 In call will be satisfied with the damper 100% open
and fan on high speed and the call will turn off
OR
• If the call for additional cooling in the space has not been
satisfied then the first stage of mechanical cooling will be
enabled through Y1 Out or Y2 Out.
29
63-2700—10
JADE™ ECONOMIZER MODULE
CHECKOUT
a
Inspect all wiring connections at the Economizer module’s
terminals, and verify compliance with the installation wiring
diagrams.
Status
Use the Status menu (see Table 5) to check the parameter
values for the various devices and sensors configured.
For checkout, review the Status of each configured parameter
and perform the Checkout tests.
NOTE: See “Interface Overview” on page 18. for
information about menu navigation and use of the
keypad.
NOTE: See “Interface Overview” on page 18. for
information about menu navigation and use of the
keypad.
Checkout Tests
WARNING
Use the Checkout menu (Table 5) to test the damper operation
and any configured outputs. Only items that are configured are
shown in the Checkout menu.
Electrical Shock Hazard.
Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring or
making wiring connections, to prevent electrical shock
or equipment damage.
If any wiring changes are required, first be sure to
remove power from the Economizer module before
starting work. Pay particular attention to verifying the
power connection (24 Vac).
NOTE:
See “Interface Overview” on page 18. for
information about menu navigation and use of the
keypad.
To perform a Checkout test:
1. Scroll to the desired test in the Checkout menu using the
 and  buttons.
2. Press the  button to select the item.
3. RUN? appears on the display.
4. Press the  button to start the test.
5. The unit pauses and then displays IN PROGRESS.
6. When all parameters have been tested, press the
button (Menu up) to end the test (e.g. turn off the relay).
The checkout tests can all be performed at the time of
installation or any time during the operation of the system as a
test that the system is operable.
Power Up
After the module is mounted and wired, apply power.
Initial Menu Display
On initial start up, Honeywell displays on the first line and
Economizer W7220 on the second line. After a brief pause,
the revision of the software appears on the first line and the
second line will be blank.
CAUTION
Equipment damage may result.
Power Loss (Outage or Brownout)
Be sure to allow enough time for compressor startup
and shutdown between checkout tests so that you do
not short-cycle the compressors.
All setpoints and advanced settings are restoreda after any
power loss or interruption.
63-2700—10
All settings are stored in non-volatile flash memory.
30
JADE™ ECONOMIZER MODULE
TROUBLESHOOTING
Clearing Alarms
Once the alarm has been identified and the cause has been
removed (e.g. replaced faulty sensor), the alarm can be
cleared from the display.
Alarms
The Economizer module provides alarm messages that display
on the 2-line LCD.
To clear an alarm, perform the following:
1. Navigate to the desired alarm.
2. Press the  button.
3. ERASE? displays.
4. Press the  button.
5. ALARM ERASED displays.
NOTE: Upon power up, the module waits 60 minutes
before checking for alarms. This allows time for
all the configured devices (e.g. sensors, actuator)
to become operational. The exception is the MA
sensor which will alarm immediately.
6.
If one or more alarms are present and there has been no
keypad activity for at least 5 minutes, the Alarms menu
displays and cycles through the active alarms.
Press the
button (MenuUp/Exit) to complete the
action and return to the previous menu.
NOTE: If an the alarm still exists after you clear it, it redisplays within 5 seconds.
You can also navigate to the Alarms menu at any time.
31
63-2700—10
JADE™ ECONOMIZER MODULE
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification
to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages,
including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark