KYL-816 Analog Wireless Acquisition module User

Shenzhen KYL Communication Equipment Co., Ltd
KYL-816 Analog Wireless Acquisition module User Manual
Shenzhen KYL Communication Equipment Co., Ltd
Add: 3705-3707, Building C, Huangdu Square, Yitian Road, Futian District,
Shenzhen, Guangdong, China 518048
Tel: 86-755-83410815;
86-755-82943662
Email: [email protected]; [email protected]
Fax: 86-755-83408785
Web: www.rf-data.com
Fax: +86-755-83408785
www.rf-data.com
Shenzhen KYL Communication Equipment Co., Ltd
Before using our products, please read the user manual carefully.
Any questions, please contact us at the above mentioned ways.
I. About KYL-816
KYL-816 Analog Wireless Acquisition Module has the function of analog
acquisition and wireless transmission. It is widely used for wireless remote control
and data collection. Designed with an industrial standard, it can work under wide
range of temperatures to meet client’s requirement for whole day using. Besides,
KYL-816 adopts narrowband FM and has high anti-jamming functions.
Ⅱ. Features of KYL-816:
1. Analog: two channels 0-5V voltage input and two channels 0-5V voltage output
2. Power supply: 12-14V, providing protection for power supply in reverse
3. There are power monitor circuit and watch dog circuit in the CPU to ensure that
this module can operate at adverse circumstances.
4. with indicator light for power supply and data transmission.
5. Can work by Modbus RTU protocol.
Ⅲ、Technical Parameters of KYL-816
1. Analog:12 bit ADC; Precision:0.5% ;
input type:voltage 0-5V。
2. Impedance Input:20MΩ.
3. Frequency:433MHz
4. Modulation: FSK
5. Output power: ≤500mW
6. Transmit current: <350mA
7. Receive sensitive:-123dBm (1200bps)
Fax: +86-755-83408785
www.rf-data.com
Shenzhen KYL Communication Equipment Co., Ltd
8. Receive current: <50mA
9. Antenna impedance:50Ω
10. Communication distance:Above 3Km (BER=10-5@1200bps,in the open air)
11. Work temperature:-35~+75(industrial standard)
12. Size:13.8*9.0*4.0cm
IV. Instruction of the indicator lights
1. Indicator light for power supply:indicating power is on or off;
2. Indicator light for working:indicating that the equipment works normally, the
blinker period is 4S when equipment works normally.
3. Indicator light for transmitting:indicating that data send out.
4. Indicator light for receive:indicating receiving data.
Ⅴ.How to use KYL-816
1. Transmission mode of KYL-816
1)point to point transmission mode initiatively:
The transmission equipment acquires 0-5V voltage analog signal timing, then
codes and wireless transmits those. The receiving equipment receives those,
codes and outputs the voltage analog signals. That is to say the input voltage
from the receiving equipment will be changed with the output voltage from
the transmission equipment.
The transmitting interval can be set from 10mS to 60S. When it is set as
“000”, KYL-816 acquisition module just works as receiving equipment. It
will not transmit any data. Otherwise, KYL-816 acquisition module works
as transmission equipment which can transmit acquired data according to
the transmitting interval you set. The minimum transmitting interval has
Fax: +86-755-83408785
www.rf-data.com
Shenzhen KYL Communication Equipment Co., Ltd
something to do with the transmitting distance. So please specify this when
you placing an order.
2)Principal and subordinate acquisition mode.
When the receive equipment doesn’t need to show the input voltage from the
transmission equipment, just need to transmit the acquired data to a PC or
other terminal equipments, you can choose Principal and subordinate mode.
The Principal equipment is the PC or other terminal equipments which
connecting with a wireless transceiver module (such as KYL-320I). And the
subordinate equipments can be acquisition units having address codes with the
number of 0-255(the transmitting interval for KYL-816 set as”0”). Under this
mode, the wireless transceiver module transmits acquisition command so that
the principal equipment can take charge of 255 acquisition modules.
2. Parameters setting
Fax: +86-755-83408785
www.rf-data.com
Shenzhen KYL Communication Equipment Co., Ltd
Picture one : Software for setting parameter
As the above picture shows:
Clients can set some parameters by the KYL-80X software, including the below
parameters:
1)Module address: from 000 to 255;
2)Channel: total eight channels, each channel have different frequency;
3)Transmitting interval: it will be in effect only when the module is under point to
point transmitting mode. The minimum transmitting interval is different subject
to baud rate of the module. When it is set as “000”, the module works at the
subordinate mode and just takes charge in receiving the output data.
Fax: +86-755-83408785
www.rf-data.com
Shenzhen KYL Communication Equipment Co., Ltd
3. How to use the software
1)Connect the module to a PC and open the software of KYL-80X, then choose the
right port.
2)Electrify, if connect successfully, the software will show “ read success”. Then
“read ID”, read success, then you can change the parameter.
Note:
1)When you read or set parameter, please fill in the appointed ID first, which is the
current module address; also can know the current module address by “read ID”,
the “ write ID” command can help you change the current module address.
2)When you set the channel, the maximum channels can’t be changed to eight.
Then you should set two modules at the same channel, otherwise they will not
communicate.
3)You can also change the parameter by wireless. Connect the wireless data module
with PC by UART port (not the UART port of KYL-816), and then you can
change the parameter of the KYL-816.
4)Under point to point mode, many double equipments work at the same time,
different double equipments should be set different channels.
Picture two: connection for setting parameter
Ⅵ. Connection Definition
1. Pin Definition
Fax: +86-755-83408785
www.rf-data.com
Shenzhen KYL Communication Equipment Co., Ltd
Pin No.
Function
Definition
Remarks
1
VCC (Power supply input)
DC:12-24V
2
GND
Grounding of power supply
3
ON-OFF output
power controlling output
(5V)
4
GND
Signal Ground
5
Relay no power output
6
Relay no power output
7
NC
-
8
GND
Signal Ground
9
Second channel analog voltage
10
GND
11
First channel analog voltage input
12
GND
13
Second channel analog voltage
14
GND
15
First
16
GND
Signal Ground
Signal Ground
Signal Ground
channel
Fax: +86-755-83408785
analog
voltage
Signal Ground
www.rf-data.com
Shenzhen KYL Communication Equipment Co., Ltd
Ⅶ. Connection sketch map
Picture three: Connection sketch map
Fax: +86-755-83408785
www.rf-data.com