Datasheet - Littelfuse

Surge Protection Module
LED Lighting Surge Protection Module > LSP10
LSP10 Module Series
RoHS
Description
The Littelfuse LSP10 thermally protected Surge Protective
Device is a self-protected device which is specially designed
to be used in outdoor and commercial LED lighting fixtures
for transient overvoltage protection. It is constructed with
Littelfuse thermally protected varistor technology. Its built-in
thermal disconnect function provides additional protection
to prevent catastrophic failure and fire hazard even under
the extreme circumstances of varistor end-of-life or sustaining over voltage conditions. LSP10 series connected option
allows clear indication of thermal fault protection by disconnecting power to luminaire thereby signally SPD module
replacement. The LSP10 SPD facilitates customer’s product
compliance to IEEE C62.41.2 Location Category C High and
US Dept of Energy MSSLC Model Spec.
Agency
Standard
Agency File Number
UL1449
E320116
Applications
• Outdoor and Commercial
LED Lighting
• Roadway lighting
• Traffic lighting
• Digital signage
•
•
•
•
•
Wash wall lighting
Parking garage/lot lighting
Flood lighting
Tunnel lighting
Street lighting
Additional Information
Datasheet
Resources
Samples
Features
• Maximum Discharge
Current, 20kA, 8/20us
• Meets ANSI C136.2
Extreme Level 20kV/10kA
and IEEE C62.41.2
Location Category
C High Exposure
• Parallel connected
and Series connected
SPD options
• Thermally protected
Varistor technology
• IP66 Water-proof
and Dust-proof
• Series connected
– Varistor thermal
protection indication
by removal of power
to luminaire
• Indication wire lead
options for Parallel
connected modules
• IEC61643-11 Class
II/ EN61643-11 Type
2 Compliant1
• Compact form factor
(48x48x30mm) with
mounting tabs
• 240Vac and 277Vac
are CE compliant and
available for Class I
and Class II installation
based on IEC luminaire
protection classes.
Please see details in Part
Numbering System.
Notes:
1. Self-declared compliance."
Absolute Maximum Ratings
• For ratings of individual members of a series, see Device Ratings and Specifications chart
LSP10 Series
Units
Continous:
AC Voltage Range (VM(AC)RMS)
Continuous Current*
150 to 510
V
5
A
Transient:
Maximum Discharge Current 8/20μs Waveform (Imax)
20,000
A
Nominal Discharge Current 8/20µs Waveform (In)
10,000
A
Operating Ambient Temperature Range (TA)
-45 to +85
°C
Storage Temperature Range (TSTG)
-45 to +110
°C
Isolation Voltage Capability (When the thermal disconnect opens)
Insulation Resistance
600
V
>1,000
MΩ
Note: * = Max. continuous current for series connection.
CAUTION: Stresses above those listed in "Absolute Maximum Ratings" may cause permanent damage to the device. This is a stress only rating and operation of
the device at these or any other conditions above those indicated in the operational sections of this specification is not implied.
© 2015 Littelfuse, Inc.
Specifications are subject to change without notice.
Revised: 07/06/15
5
LV UltraMOV™ Series
Agency Approvals
Surge Protection Module
LED Lighting Surge Protection Module > LSP10
LSP10 Series Device Ratings & Specifications
Part Number
8
Operating
Voltage
(VAC)
MCOV/Uc
(VAC)6
Maximum
Discharge
Current
(Imax)(A)3
LSP10120*
120
150
20,000
LSP10240*
240
275
20,000
LSP10277*
277
320
20,000
LSP10347*
347
420
20,000
LSP10480*
480
510
20,000
L-L:240
L-L:275
L-N/G:120
L-N/G:150
LSP10240LL*
LSP10480LL*
L-L:480
L-L:510
L-N/G:277
L-N/G:320
20,000
20,000
Nominal
Discharge
Current
(In)(A)2
MLV
(V)4
Up
(V)5
10,000
UL1449
IEC/EN 61643-117
L-N:740
10,000
L-G:740
900
N-G:670
L-N:1130
10,000
L-G:1130
1200
N-G:1060
L-N:1330
10,000
L-G:1330
1400
Typical Dimensions
(mm)
N-G:1260
L-N:1750
10,000
L-G:1750 56.0 ±0.5
1900
N-G:1680
L-N:2020
10,000
L-G:2020
2100
N-G:1960
10,000
Safety Compliance
L-L:1130
L-L:1200
L-N/G:740
L-N/G:900
L-L:2020
L-L:2100
L-N/G:1330
L-N/G:1400
X
X
X
X
X
X
X
48.0±1.5
2x ø4.8±0.2
X
X
X
X
Notes:
1. 5A max. continuous current for series connection.
2. Nominal Discharge Current (In)(A): The nominal discharge current is a measure of the SPDs endurance capability; 15 impulses of discharge current uses the 8/20us current
100 ±20
100 ±20
48.0 ±1.5
waveform.
3. Maximum Discharge Current (Imax)(A): The maximum discharge current is a measure of the SPDs maximum capability; single impulse of discharge current uses the 8/20us current
waveform. All Devices pass maximum discharge current with possible, safe opening of thermal disconnect.
4. MLV – UL1449 Measured limiting voltage; the highest value of residual voltage measurements during the application of impulses of 8/20us nominal discharge current (In); an average
voltage value of 15 impulses.
5. Up – IEC 61643-11 Voltage protection level; the highest value of residual voltage measurements during the application of impulses of 8/20us nominal discharge current
(In);
a rounding
30.0
±1.0
2.3 ±0.2
voltage value of maximum measurement.
6. MCOV/UC: Maximum Continuous Operating Voltage - maximum r.m.s. voltage that could be continuously applied to the SPD.
7. Series module used in parallel connection for indication circuit connection.
6 ±2
6 ±2
8. * = - P or PM
64.0 ±1.5
Dimensions
Typical Dimensions (mm)
56.0 ±0.5
48.0±1.5
2x ø4.8±0.2
100 ±20
48.0 ±1.5
100 ±20
30.0 ±1.0
2.3 ±0.2
6 ±2
6
64.0 ±1.5
6 ±2
LSP10XXXXXP
LSP10XXXXXS
Notes:
1. Black: Line; White: Neutral; Green: Ground.
(P/N with suffix X3333/X3316: Brown: Line; Blue: Neutral; Green-Yellow stripe: Ground)
2. Wire Gauge: AWG14 wire Line in/out; Wire Length: 100mm or customized.
© 2015 Littelfuse, Inc.
Specifications are subject to change without notice.
Revised: 07/06/15
Surge Protection Module
LED Lighting Surge Protection Module > LSP10
Application/Installation Schematic
L
or
N/G
L
L
N
N
AC/DC
Power
Supply
G
LSP 10 480LL P Xxxxx
+
Device Family
Littelfuse Surge Protection Module
-
LED Module
Nominal Discharge
Current (In)
Parallel Connection
SPD
L
L
N
N
AC/DC
Supply
G
Parallel Connection
(for Class II Unearthed)
L
L
or
N/G
N
N
With LED indicating SPD status
- ON (green): SPD is online
- OFF: SPD needs replacement
-
Other non-standard option:
X3333: without GND wire connection, available for
240Vac and 277Vac rating with CE Marking for Class I
unearthed installation.
LED Module
SPD
L
Parallel Connection
P or S
(P: parallel connection; S: series connection)
+
X3316: without GND wire connection, available for
240Vac and 277Vac rating with CE Marking for Class II
unearthed installation.
~X3316
L
G
Power
Operating Voltage
Connection mode
LL: for L,L,N/G
Blank: L-N, L-G, N-G
AC/DC
Power
Supply
+
-
LED Module
LV UltraMOV™ Series
L
Part Numbering System
LED normally on
SPD
LSP10xxxS
R
Notes:
1. Series module used in parallel connection for indication circuit connection.
2.LED indicator and associated circuitry are not included in the module.
3. Black wire is AC line voltage (hot); white wire is AC neutral voltage.
4. Black wire voltage is cut off when SPD needs replacement.
5. R is current limiting resistor; it resistance/wattage is determined by AC line voltage and
desired current driving LED. Example: AC line voltage 240V, LED: 1.6mA, resistor:
150Kohm/0.5W.
L
L
N/G
or
L
L
N
N
Power
Supply
G
Series Connection
AC/DC
+
-
LED Module
SPD
LSP10xxxS
L
L
N
N
(for Class II Unearthed)
Power
Supply
G
Series Connection
AC/DC
+
-
LED Module
SPD
~X3316
© 2015 Littelfuse, Inc.
Specifications are subject to change without notice.
Revised: 07/06/15
7