DR-60 series

60W Single Output Industrial DIN Rail Power Supply
DR-60
series
■
‧
‧
‧
‧
‧
‧Ⅱ
‧
‧
‧
..
SPECIFICATION
MODEL
OUTPUT
INPUT
DR-60-5
DR-60-12
DR-60-15
DR-60-24
DC VOLTAGE
5V
12V
15V
24V
RATED CURRENT
6.5A
4.5A
4A
2.5A
CURRENT RANGE
0 ~ 6.5A
0 ~ 4.5A
0 ~ 4A
0 ~ 2.5A
RATED POWER
32.5W
54W
60W
60W
RIPPLE & NOISE (max.) Note.2 80mVp-p
120mVp-p
120mVp-p
150mVp-p
VOLTAGE ADJ. RANGE
11.1 ~ 13.2V
13.5 ~ 16.5V
21.6 ~ 26.4V
VOLTAGE TOLERANCE Note.3 ±2.0%
±1.0%
±1.0%
±1.0%
LINE REGULATION
±1.0%
±1.0%
±1.0%
±1.0%
LOAD REGULATION
±1.0%
±1.0%
±1.0%
±1.0%
SETUP, RISE TIME
100ms, 30ms/230VAC
HOLD UP TIME (Typ.)
100ms/230VAC
VOLTAGE RANGE
88 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
83%
84%
76%
1.2A/115VAC
0.8A/230VAC
COLD START 18A/115VAC
36A/230VAC
OVERLOAD
105 ~ 160% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
5.75 ~ 6.9V
13.8 ~ 16.2V
17.25 ~ 20.25V
27.6 ~ 32.4V
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
(Note 4)
OTHERS
82%
Protection type : Shut down o/p voltage, re-power on to recover
-20 ~ +60℃ (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
±0.03%/℃ (0 ~ 50℃)
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL60950-1, TUV EN60950-1 approved, Design refer to EN50178
ISOLATION RESISTANCE
EMC EMISSION
I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH
Compliance to EN55011, EN55022 (CISPR22) Class B, EN61000-3-2,-3
EMC IMMUNITY
MTBF
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
DIMENSION
PACKING
NOTE
23ms/115VAC at full load
124 ~ 370VDC
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
OVER VOLTAGE
EMC
200ms, 30ms/115VAC at full load
EFFICIENCY (Typ.)
PROTECTION
SAFETY &
4.75 ~ 5.5V
I/P-O/P:3KVAC
216.2K hrs min. MIL-HDBK-217F (25℃)
78*93*56mm (W*H*D)
0.3Kg; 48pcs/15.4Kg/1.02CUFT
℃




File Name:DR-60-SPEC 2011-06-17
DR-60
60W Single Output Industrial DIN Rail Power Supply
Mechanical Specification
series
Case No.918B Unit:mm
68
45
47
56
27.4
Terminal Pin No. Assignment
Assignment
AC/N
AC/L
+V
Pin No.
5,6
7
8
Assignment
-V
LED
+V ADJ.
3
Pin No.
1
2
3,4
46.5
46.5
93
12.2 5 5 5
8
6
5
4
3
7
37.75
78
35
5
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
2
1
Block Diagram
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
POWER
SWITCHING
O.L.P.
PWM
CONTROL
RECTIFIERS
&
FILTER
+V
-V
DETECTION
CIRCUIT
O.V.P.
Derating Curve
100
80
LOAD (%)
60
40
20
-20
0
10
20
30
40
50
60
70 (VERTICAL)
AMBIENT TEMPERATURE (℃)
File Name:DR-60-SPEC 2011-06-17