46-627.3 J52 Level Switches IO

J52 Refrigerant
Level Switches
Instruction Manual and Parts List
OPERATING PRINCIPLE
Figures 1 and 2 illustrate the simple and foolproof
Magnetrol operating principle. Switching action is obtained
through the use of a magnetic attracting sleeve, actuated
by a float, and a switching mechanism. These two basic
component assemblies are separated by a non-magnetic,
pressure tight enclosing tube. The switch and magnet are
assembled to a swinging arm which operates on precision
stainless steel pivot sockets.
Pivot
Mercury Switch
Enclosing Tube
(non-magnetic)
Return
Spring
Magnet
Attracting Sleeve
(magnetic)
Float
Normal Operating Level
Figure 1
Falling Level
Figure 2
DESCRIPTION
The Magnetrol® Model J52 is designed specifically as a
refrigerant level control for applications with commercial
refrigerants including Ammonia, Freon, Methyl Chloride,
and Sulphur Dioxide. Usage may include level alarm and/or
pump control service on liquid accumulators or receivers.
MODEL IDENTIFICATION
Housing
NEMA 4X
NEMA 4X
NEMA 4 Lexan
NEMA 4 Lexan
NEMA 4X/7/9
NEMA 4X/7/9
Switch
Mercury
Dry Contact
Mercury
Dry Contact
Mercury
Dry Contact
Connection
3
⁄4" NPT
⁄4" Socket Weld
J52-4101-001
J52-4111-001
J52-4101-002
J52-4111-002
J52-4107-003
—
J52-4107-004
—
J52-4102-001
J52-4112-001
J52-4102-002
J52-4112-002
3
OPERATING CYCLE
At “Normal Operating Level” of liquid in the chamber
(Figure 1), the float moves the magnetic attracting sleeve up
the enclosing tube and into the field of the switch mechanism magnet. As a result, the magnet is drawn in tightly to
the enclosing tube causing the switch to tilt, “making” or
“breaking” an electrical circuit. As liquid level recedes, the
float pulls the magnetic attracting sleeve downward until, at
a pre-determined “Low Level” (Figure 2), the switch magnet
releases and is drawn outward away from the enclosing
body of the tube by a tension spring. This in turn tilts the
switch in an opposite direction, thus reversing the switch
action. When liquid level returns to normal (Figure 1), the
float once again moves the magnetic attracting sleeve up
at the enclosing tube, causing the switch to assume its
original position.
INSTALLATION
WIRING
PIPING
Figure 3 shows a typical piping schematic of Magnetrol J52
level switches installed on a liquid accumulator. Appropriate
reference mark on control float chamber should be aligned
to correspond with liquid level at which switch control is
desired (switch operates at upper mark on increasing level
and lower mark at decreasing level).
Use pipe of sufficient strength to support the control. All
piping should be straight and free of “low spots” or “pockets” so that the lower liquid line will drain towards the liquid
accumulator (or receiver), and upper vapor line will drain
toward the control. Shut-off valves are recommended for
installation between accumulator (or receiver), and control
float chamber.
If control is to be used with a low temperature liquid (one
which will “boil” in float chamber if outside heat is
absorbed), the chamber and piping should be insulated, as
shown in Figure 5. Such boiling in the chamber will cause
false level indications. Do NOT insulate switch mechanism
housing.
MOUNTING
Adjust piping as required to bring control to a vertical position. Magnetrol controls must be mounted within three (3°)
degrees of the vertical. A three-degree slant is noticeable by
eye, but installation should be checked with a spirit level on
top or sides of float chamber.
CAUTION: Level controls are shipped from the factory with
the enclosing tube tightened and the middle set screw, on
the housing base, locked to the enclosing tube. Failure to
loosen the set screw prior to repositioning the conduit connection may cause the enclosing tube to loosen, resulting
in the possible leakage of the process liquid or vapor.
The standard Model J52 with NEMA 4 housing is furnished
with 24" (610 mm) long lead wires for ease in connection at
a close junction box. Wires are sealed in a conduit outlet
adaptor fitting, color coded and numbered to allow control
wiring without the need to remove the sealed housing
cover. All switch electrical ratings are stamped on the housing cover nameplate. If desired, conduit outlet may be repositioned for wiring convenience by loosening set screw(s)
located under the housing base; however, housing cover
must be removed and switch mechanism locking screw
loosened so that mechanism can be rotated together with
housing base.
NOTE: Before placing control into service, be certain cover
gasketed joints are tight to prevent infiltration of moisture
laden air or corrosive gases to the switch mechanism.
TYPICAL INSTALLATIONS AND WIRING DIAGRAMS
INSTALLATION SHOWING PUMP CONTROL AND HIGH LEVEL ALARM
MODEL J52 MAGNETROL CONTROLS
SUCTION TO
COMPRESSOR
Line
Alarm
High Level Alarm
terminals
4
5
6
High Level Alarm
SUCTION FROM
COOLERS
Chamber mark indicates
actuating levels
Pump On
terminals
4
5
6
Pump On
LIQUID
ACCUMULATOR
Coil
Pump Off
terminals
4
5
6
Pump
Motor
Pump Off
TO PUMP
Line Starter with
3-wire pilot circuit
Figure 3
2
INSTALLATION cont.
WIRING cont.
Terminal connections shown in Figure 4 are for a standard
SPDT switch. Actuating the switch closes one circuit and
simultaneously opens the second circuit. In this diagram,
circuit between contacts 4 and 5 is made and circuit
between contact 5 and 6 is broken at low liquid level. At
high level, circuit between contacts 4 and 5 is broken and
circuit between contact 5 and 6 is made.
Close on
Falling Level
Load
Load
Common
Close on
Rising Level
Assembly B
4 RED
5 YELLOW
6 BLUE
Internal
Circuit
GREEN
Line
Ground
Figure 4
DIFFERENTIAL ADJUSTMENT
The amount of level travel between “switch on” and “switch
off” can be reduced from the maximum factory setting by
raising the lower set of jam nuts. Minimum free play (differential) of magnetic sleeve is 1⁄32".
CAUTION: Before attempting any work on the control,
be certain to pull disconnect switch or otherwise assure
that electrical circuit(s) through control is deactivated.
Close operating medium supply valve on controls equipment with pneumatic switch mechanisms.
1. Disconnect wiring from supply side of switch mechanism and electrical conduit or operating medium line
connections to switch housing.
2. Perform system shut-down as required to relieve pressure from tank or vessel and drain off liquid “head”
above control mounting position. Allow unit to cool.
3. Remove switch housing assembly by loosening enclosing tube nut located immediately below housing base.
Refer to Figure 7.
4. With switch housing removed, jam nuts and magnetic
sleeve are now accessible, as shown in Figure 6.
Raising the lower jam nuts will reduce the differential. As
the first step in any adjustment procedure, the position
of the upper and lower jam nuts should be established.
NEVER CHANGE SETTING OF UPPER JAM NUTS AS
THEY SUPPORT FLOAT ASSEMBLY SO THAT IT CANNOT TOUCH BOTTOM OF CHAMBER.
5. Loosen and remove upper jam nuts, guide washer, and
magnetic sleeve. Lower jam nuts may now be adjusted
to reduce the differential.
NOTE: Be certain to tighten jam nuts securely after adjustment.
6. Replace magnetic sleeve on stem and position upper jam
nuts to their original setting. Lock upper jam nuts to guide
washer.
7. Reassemble control in reverse of steps 1 through 3, previously described.
8. Test switch actuation by varying liquid level in tank or vessel.
INSTALLATION SHOWING LEVEL CONTROL (OR ALARM) ON A RECEIVER
From Condenser
DO NOT Insulate
Switch Housing
Receiver
Chamber mark indicates
actuating level
Jam nuts.
Slight play (gap)
must be allowed
(.03" [.8 mm] typical)
Differential gap
Desired
Actuating Level
Magnetic sleeve
Insulation
To Evaporator
Side View
End View
Figure 6
Mount control so mark on chamber corresponds to level desired
in vessel. When control is used on a low temperature liquid,
chamber and connection lines should be insulated as shown to
prevent “boiling” in the float chamber and false level indications
Figure 5
3
PREVENTIVE MAINTENANCE
Periodic inspections are a necessary means to keep your Magnetrol control in good working
order. This control is, in reality, a safety device to protect the valuable equipment it serves.
Therefore, a systematic program of “Preventive Maintenance” should be implemented when
control is placed into service. If the following sections on “What To Do” and “What To Avoid”
are observed, your control will provide reliable protection of your capital equipment.
What To Do
What To Avoid
1. Keep Control Clean
1. NEVER leave switch housing cover off the control
longer than necessary to make routine inspections.
— Be sure the switch housing cover is always in place
on the control. This cover is designed to keep moisture laden air and corrosive gases as well as dirt
away from the switch mechanism. In addition, it acts
as a safety feature by keeping bare wires and terminals from being exposed. Be sure cover is tightened
all the way down to ensure compression of quad ring
seal. Should the housing cover become damaged or
misplaced, order a replacement immediately.
2. Inspect Switch Mechanisms, Terminals, and
Connections Monthly.
— Mercury switches may be visually inspected for short
circuit damage. Check for small cracks in the glass
tube containing the mercury. Such cracks can allow
entrance or air into the tube causing the mercury to
“oxidize”. This is noticeable as the mercury will
appear dirty and have a tendency to “string out” like
water, instead of breaking into clean round pools. If
these conditions exist, replace the mercury switch
immediately.
Do NOT operate your control with defective or maladjusted
switch mechanisms (refer to bulletin on switch mechanism
furnished for service instructions).
— Magnetrol controls may sometimes be exposed to
excessive heat or moisture. Under such conditions,
insulation on electrical wires may become brittle,
eventually breaking or peeling away. The resulting
“bare” wires can cause short circuits. Check wiring
carefully and replace at first sign or brittle insulation.
— Vibration may sometimes cause terminal screws to
work loose. Check all terminal connections to be
certain that screws are tight.
4
2. NEVER use lubrication on pivots of switch mechanisms.
A sufficient amount of lubricant has been applied at the
factory to ensure a lifetime of service. Further oiling is
unnecessary and will only tend to attract dust and dirt
which can interfere with mechanism operation.
3. NEVER place a jumper wire across terminals to “cutout” the control. If a “jumper” is necessary for test purposes, be certain it is removed before placing control
into service.
4. NEVER attempt to make adjustments or replace switches without reading instructions carefully. Certain adjustments provided for in Magnetrol controls should not be
attempted in the field. When in doubt, consult the factory or your local representative.
TROUBLESHOOTING
Usually the first indication of improper operation is failure of
the controlled equipment to function, i.e. pump will not start
(or stop), signal lights fail to light, etc. When these occur,
whether at time of installation or during routine service thereafter, check the following potential external causes first.
— Fuses may be blown.
— Reset button(s) may need resetting.
— Power switch may be open.
— Controlled equipment may be faulty.
— Wiring lines leading to control may be defective.
If a thorough inspection of these possible conditions fails to
locate the trouble, proceed next to a check of the controls
switch mechanism.
1. Pull disconnect switch or otherwise assure that electrical circuit(s) through control deactivated.
2. Remove switch housing cover.
3. Swing magnet assembly in and out by hand to check
carefully for any sign of binding. Assembly should
require a minimum of force to move it through its full
swing.
4. If binding exists, magnet may be rubbing enclosing tube
or pivot sockets may be overly tight. Readjust pivot
sockets as required until a slight amount of side play is
evident. If magnet is rubbing, loosen magnet clamp
screw and shift magnet position.
5. If switch magnet assembly swings freely and mechanism still fails to actuate, check installation of control to
be certain it is within the specified three (3°) degrees of
vertical (use spirit level on side of enclosing tube in two
places, 90° apart).
6. If mechanism is equipped with a mercury switch, examine glass mercury tube closely as previously described
in “Preventive Maintenance” section. If switch is damaged, replace it immediately.
NOTE: As a matter of good practice, spare switches should
be kept on hand at all times.
If switch mechanism is operating satisfactorily, a test of the
complete controls performance is the next likely step.
1. Reconnect power supply and carefully actuate switch
mechanism manually (using a nonconductive tool) to
determine whether controlled equipment will operate.
CAUTION: With electrical power “on”, care should be
taken to avoid contact with switch leads and connections
at terminal blocks.
2. If controlled equipment responds to manual actuation
test, trouble may be located in the level sensing portion
of the control (float, stem, and magnetic attraction
sleeve).
NOTE: Check first to be certain refrigerant is entering float
chamber. A valve may be closed or pipe line
plugged.
3. Depressurize and remove E-tube, proceed to check
level sensing action by removing switch housing assembly, as described in “Differential Adjustment” instructions.
4. Inspect attraction sleeve and inside of enclosing tube
for excessive corrosion or solids build-up which could
restrict movement, preventing sleeve from reaching field
of switch magnet.
5. If differential adjustment has been changed in the filed
by repositioning the lower jam nuts on the float stem,
check for tightness and position of the jam nuts.
NOTE: Differential adjustment affects a change in the
amount of level travel between “switch-on” and
“switch-off” actuations. Do NOT attempt adjustment
without first consulting factory for assistance in
computing level differential change for your control.
6. Check float to be certain it is buoyant in the refrigerant
(float chamber must have adequate refrigerant level). If
float is determined to be filled with liquid or collapsed, it
must be replace immediately. Do NOT attempt to repair
a float.
If all components in the control are in operating condition,
the trouble must be (and should be) located externally to the
control. Repeat inspection of external conditions previously
described.
NOTE: When in doubt about the condition or performance
of a Magnetrol control, return it to the factory. See
“Our Service Policy” on the back page.
5
SPECIFICATIONS
Basic electrical ratings
Agency approvals
Agency
Model Number
CSA
J52-41X1-00X
J52-41X2-00X
J52-41XX-00X
Non-Hazardous TYPE 4X
FM
J52-41X2-00X
CENELEC
Approval
J52-41X1-00X
J52-41X2-00X
Non-Hazardous NEMA 4X
Class I, Div. 1, Groups C & D
Class II, Div. 1 Groups E, F & G
EEx d IIC T6
Chamber assembly must be fitted with a CENELEC housing.
Dimensional specifications
Switch Type and
Non-inductive Ampere Rating
Voltage
Mercury
Dry Contact
120 Vac
240 Vac
24 Vdc
120 Vdc
240 Vdc
4.00
2.00
—
4.00
2.00
15.00
15.00
6.00
0.50
0.25
Inches (mm)
ROTATION CLEARANCE
NEMA 4X — 4.25 (108)
NEMA 4X/7/9 — 6.00 (152)
15.00
(381)
1/2" NPT Conduit
Connection may
be rotated through 360°
24.00 (610) Long
wires furnished
Actuating
Levels
R
L
10.00
(254)
Liquid Specific Gravity
0.60 0.80 1.00 1.20 1.30 1.40 1.50 1.60 1.70
1.00 1.44 1.69 1.88 1.94 2.00 2.06 2.13 2.13
(25) (37) (43) (48) (49) (51) (52) (54) (54)
2.38 2.63 2.81 2.94 3.00 3.06 3.06 3.13 3.13
(60) (69) (71) (75) (76) (78) (78) (80) (80)
NOTE: Actuating levels are factory set for maximum differential between
switch actuation. Internal adjustment provided for reduced differential.
3/4" NPT
3/4" Socket weld
RISING LEVEL
R
L
NOTES:
1. Float chamber has float cushioning spring.
2. Allow 3.50 (89) NEMA 4 or 4.12 (105) NEMA 7/9 overhead
clearance for cover removal.
3. All dimensions in ( ) are in millimeters.
FALLING LEVEL
2.81
(71)
3/4" NPT
3/4" Socket weld
4.25 (108)
6
5.75
(146)
REPLACEMENT PARTS
Item
Description
J52-4101-001 J52-4101-002 J52-4102-001 J52-4102-002 J52-4107-003 J52-4107-004 J52-4111-001 J52-4111-002 J52-4112-001 J52-4112-002
1
Housing Cover
89-6526-001
2
Housing Base
89-6527-001
3
Switch Mech.
89-7401-078 89-7401-102
89-7401-078
89-7401-102
89-7401-078
89-7401-102
89-7401-078
89-7401-102
89-7401-078 89-7401-102
4
Switch Bulb
89-7101-015 89-7101-020
89-7101-015
89-7101-020
89-7101-015
89-7101-020
89-7101-015
89-7101-020
89-7101-015 89-7101-020
5
E-Tube
6
E-Tube Gasket
7
Attraction Sleeve
8
Chamber Asbly.
9
Jam Nuts (4)
10-2106-004
10
Guide Washer
10-3351-001
89-6582-001
Z032-6301-038
Z032-6325-001
89-6522-001
89-6526-001
89-6527-001
89-6527-001
Z032-6325-007
89-6582-001
Z032-6301-038
Z032-6325-001
Z033-3107-001
Z033-3105-001
12-1301-002
32-4101-013
Z033-3105-001
NOTES:
1. Replacement assemblies listed are furnished in kit form only
for standard base model. Consult local representative for
ordering assistance on special model replacement parts or
accessories not included in above listing.
2. Conduit compression type seal fitting parts not available form
factory for explosion proof housing which has 1" NPT outlet.
IMPORTANT:
When ordering, please specify:
A. Model and Serial number of control.
B. Name and Number of replacement assembly.
1
9
4
3
10
2
5
6
7
8
Figure 7
7
IMPORTANT
PRODUCT WARRANTY
QUALITY ASSURANCE
All Magnetrol mechanical level and flow controls are warranted free of defects in materials or workmanship for five
full years from the date of original factory shipment.
The quality assurance system in place at
Magnetrol guarantees the highest level of
quality throughout the company. Magnetrol
is committed to providing full customer
satisfaction both in quality products and
quality service.
If returned within the warranty period; and, upon factory
inspection of the control, the cause of the claim is
determined to be covered under the warranty; then,
Magnetrol will repair or replace the control at no cost to the
purchaser (or owner) other than transportation.
Magnetrol shall not be liable for misapplication, labor
claims, direct or consequential damage or expense arising
from the installation or use of equipment. There are no other
warranties expressed or implied, except special written
warranties covering some Magnetrol products.
Magnetrol’s quality assurance system is registered to ISO
9001 affirming its commitment to known international
quality standards providing the strongest assurance of
product/service quality available.
ASSURED QUALITY & SERVICE COST LESS
SERVICE POLICY
RETURN MATERIAL PROCEDURE
Owners of Magnetrol may request the return of a control or
any part of a control for complete rebuilding or replacement. They will be rebuilt or replaced promptly. Controls
returned under our service policy must be returned by
Prepaid transportation. Magnetrol will repair or replace the
control at no cost to the purchaser (or owner) other than
transportation if:
So that we may efficiently process any materials that are
returned, it is essential that a “Return Material
Authorization” (RMA) number be obtained from the factory,
prior to the material’s return. This is available through
Magnetrol local representative or by contacting the factory.
Please supply the following information:
1. Returned within the warranty period; and
2. The factory inspection finds the cause of the claim to
be covered under the warranty.
If the trouble is the result of conditions beyond our control;
or, is NOT covered by the warranty, there will be charges for
labor and the parts required to rebuild or replace the equipment.
In some cases it may be expedient to ship replacement
parts; or, in extreme cases a complete new control, to
replace the original equipment before it is returned. If this is
desired, notify the factory of both the model and serial numbers of the control to be replaced. In such cases, credit for
the materials returned will be determined on the basis of the
applicability of our warranty.
1.
2.
3.
4.
5.
Company Name
Description of Material
Serial Number
Reason for Return
Application
Any unit that was used in a process must be properly
cleaned in accordance with OSHA standards, before it is
returned to the factory.
A Material Safety Data Sheet (MSDS) must accompany
material that was used in any media.
All shipments returned to the factory must be by prepaid
transportation.
All replacements will be shipped F.O.B. factory.
No claims for misapplication, labor, direct or consequential
damage will be allowed.
For use in Category II installations. If equipment is used in a
manner not specified by manufacturer, protection provided
by equipment may be impaired.
LOW VOLTAGE DIRECTIVE
5300 Belmont Road • Downers Grove, Illinois 60515-4499 • 630-969-4000 • Fax 630-969-9489 • www.magnetrol.com
145 Jardin Drive, Units 1 & 2 • Concord, Ontario Canada L4K 1X7 • 905-738-9600 • Fax 905-738-1306
Heikensstraat 6 • B 9240 Zele, Belgium • 052 45.11.11 • Fax 052 45.09.93
Regent Business Ctr., Jubilee Rd. • Burgess Hill, Sussex RH15 9TL U.K. • 01444-871313 • Fax 01444-871317
Copyright © 2009 Magnetrol International, Incorporated. All rights reserved. Printed in the USA.
BULLETIN: 46-627.3
EFFECTIVE: August 2006
SUPERSEDES: August 2001