Download

Terminal SSR
G3S4
CSM_G3S4_DS_E_7_2
Compact Terminal SSR with 4 Outputs
• Easy-to-use SSR block that combines four compact G3S SSRs,
sockets, and heat sink in one unit.
• Easy wiring with separate I/O terminal construction.
• LED operation indicator.
• Special socket used for easy Relay replacement.
• Mounts either on DIN track or with screws.
Ordering Information
When your order, specify the rated voltage.
■ List of Models
Contact configuration Heat sink
Four SPST-NO relays
Yes
Built-in SSRs
G3S-201PL-PD
Zero cross function Applicable output load
No
Model
1 A at 75 to 264 VAC
(See note 1.)
G3S4-A
0.6 A at 75 to 264 VAC
(See note 1.)
G3S4-A1
Rated voltage
5 VDC
12 VDC
24 VDC
No
5 VDC
12 VDC
24 VDC
Yes
G3SD-Z01P-PD
1 A at 3 to 26 VDC (See G3S4-D
note 2.)
5 VDC
12 VDC
24 VDC
No
0.6 A at 3 to 26 VDC
(See note 2.)
G3S4-D1
5 VDC
12 VDC
24 VDC
Note: 1. Given as "250 VAC" on the G3S4.
2. Given as "24 VDC" on the G3S4.
■ Accessories (Order Separately)
Connection Sockets (Can be
Purchased Individually)
Model
P6BF-4BND
Rated voltage
Replacement Relays
Model
G3S-201PL-PD
12 VDC
5 VDC
12 VDC
24 VDC
Heat Sinks (Can be Purchased
Individually)
Rated voltage
5 VDC
24 VDC
G3SD-Z01P-PD
5 VDC
12 VDC
24 VDC
Model
Y92B-S10
1
G3S4
Specifications
■ Ratings
Input (per G3S Relay)
Rated
voltage
DC
Operating
voltage
5V
Must operate
level
4 to 6 VDC
4 VDC max.
12 V 9.6 to 14.4 VDC
Must release
voltage level
1 VDC min.
9.6 VDC max.
24 V 19.2 to 28.8 VDC 19.2 VDC max.
Input impedance
G3S4-A,
G3S4-A1
Rated current
G3S4-D,
G3S4-D1
G3S4-A,
G3S4-A1
G3S4-D,
G3S4-D1
440 Ω±20%
550 Ω±20%
19.2 mA±20%
15.8 mA±20%
1 kΩ±20%
1.2 kΩ±20%
15.8 mA±20%
12.5 mA±20%
2.1 kΩ±20%
2.3 kΩ±20%
15.7 mA±20%
13.2 mA±20%
Note: The rated current includes the terminal's LED current.
Output (per G3S Relay)
Model
Applicable load
G3S4-A
Load voltage
Load current
75 to 264 VAC
Inrush current resistance
0.1 to 1 A
G3S4-A1
15 A (60 Hz, 1 cycle)
0.1 to 0.6 A
G3S4-D
3 to 26 VDC
0.01 to 1 A
G3S4-D1
3 A (10 ms)
0.01 to 0.6 A
■ Characteristics
Item
Model
G3S4-A, G3S4-A1
Must operate time
1 ms max.
G3S4-D, G3S4-D1
Release time
0.5 × load power cycle + 1 ms max.
1 ms max.
Output ON voltage drop
1.6 V max. (RMS)
1.5 V max.
Leakage current
2 mA max.
0.1 mA max. (at 26 VDC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min
Vibration resistance
10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Shock resistance
1,000 m/s2
Storage temperature
−30 to 100°C (with no icing)
Ambient operating temperature −30 to 80°C (with no icing)
Ambient operating humidity
45% to 85%
Weight
Approx. 95 g (-A model)
Approx. 95 g (-D model)
Engineering Data
■ Reference Data
(per G3S Relay)
Load Current vs. Ambient Inrush Current Resistance
Non-repetitive (Keep the inrush current to half the rated value if inrush current occurs
Rated Temperature
repetitively.)
G3S4-A, G3S4-D
1
0.75
G3S4-A1, G3S4-D1
G3S4-D, G3S4-D1
Inrush current (A. Peak)
Inrush current (A. Peak)
Load current (A)
G3S4-A, G3S4-A1
15
10
5
0
3
2
1
0
0.6
0.5
0.25
0.1
0
−30
−20
0
20
40
60
80
100
Ambient temperature (°C)
10
30 50 100 200
500 1,000
5,000
Energizing time (ms)
10
30 50 100 200
500 1,000
5,000
Energizing time (ms)
Note: Measurement values taken from production line samples have been plotted in graphs to provide this data. Use this data only as a guide.
Relays are mass-produced, so allowances must be made for a certain amount of variation in measurement data.
2
G3S4
Dimensions
Note: All units are in millimeters unless otherwise indicated.
■ Relays
With Heat Sinks
16-M3.5
43 max.
G3S4-A
G3S4-D
78 max.
Mounting Holes
(Top View)
4
Two, 4-dia. holes or M3.5 screw holes
43 max.
28 max.
33 max.
65±0.3
Without Heat Sinks
16-M3.5
36±0.2
G3S4-A1
G3S4-D1
78 max.
Terminal Arrangement/Internal
Connections
(Top View)
4
43 max.
28 max.
33 max.
8
Output side
■ Accessories (Order Separately)
Connection Socket (Can be Purchased Individually)
−
4
7
+
+
3
−
6
+
2
−
5
1
+
12 (+) 11 (+) 10 (+)
9 (+)
16 (−) 15 (−) 14 (−) 13 (−)
Note: Make sure that the polarity of
the input terminal is correct.
The polarity given inside
parentheses ( ) is for G3S4-D
and G3S4-D1 Relays. There
is no indication of polarity
when Connection Sockets
are used alone.
16-M3.5
P6BF-4BND
(with operation indicator)
−
Input side
78 max.
4
43 max.
28 max.
Heat Sinks (Can be Purchased Individually)
Y92B-S10
Mounting Brackets
0
25−0.2
(3.5)
25
8.2
8.2
8.2
8.2
(7.5)
8.2
20
1+0.5
0
0
17−0.3
8
2
5
0
10−0.3
0.7
0.5
0
42−0.3
1
1
2
36±1
2
1
2
0.5
3
G3S4
Replacement Relays
10 max.
20 max.
G3S-201PL-PD
G3SD-Z01P-PD
Terminal Arrangement/Connections
(Bottom View)
Relay Removal Tool
and Short Bar (Order
Separately)
(−)
16.5 max.
16 max.
Input
voltage
4
0.8
10.16
7.62
1
(−)
−
INPUT
(+)
Load
Load power
supply
(+)
LOAD
+
6
0.4
7.62
Refer to Options for the G6B-4CB, G6B4@@ND, and G3S4.
Note: 1. The polarity given inside
parentheses ( ) is for DC loads.
2. The load can be connected to
ether the positive or negative
SSR output terminal.
Relay Mounting
Products (Order
Separately)
Safety Precautions
Refer to Safety Precautions for All Relays.
■ Precautions for Correct Use
• The four SSRs are mounted individually. Use standard SSR
connection methods.
• There is almost no differences based on the mounting direction.
Mount the Terminal SSR with the best air flow.
• Apply a silicon grease for heat radiation (e.g., YG6260 or G746
from Shin-Etsu Chemical Co. Ltd.) between the heat sink and the
SSR if the heat sink is removed during maintenance of the G3S4-A
or G3S4-D Terminal SSR (with external heat sinks) or if an external
heat sink that was purchased separately is mounted.
• The load voltage cannot be increased by connecting the G3S4 load
terminals in serial. This is because there is a small difference in the
SSR operating time
• The load current cannot be increased by connecting the G3S4 load
terminal in parallel. This is because there is a small difference in
the SSR operating time.
• The P6BF-4BND Connection Socket has an operation indicator
and is available in 5-VDC, 12-VDC, and 24-VDC models.
• Use the P6B-Y1 Relay Removal Tool to remove SSRs.
Mounted Relays
Relays and SSRs cannot be mounted together.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
4
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2015.10
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company