1370/1379 Contactors - Connection Guide and Parts List

1370/1379 Contactors Connection Guide and Parts List Description The Bulletin 1370 DC Contactors are electromagnetically held contactors specially designed to switch the armature current form the DC Drive module to at shunt wound DC motor. When used with the appropriate control logic design, these contactors can disconnect the motor armature from the DC Drive module when a stop is initiated or in the event of a power failure. The contactors feature a topwired design with all power connections at the top of the contactor. This document contains the information needed to install, connect and maintain the Bulletin 1370 DC Contactor. WARNING: The National Electric Code (NEC) and local codes outline provisions for safely installing electrical equipment. Installation must comply with specifications regarding wire types, conductor sizes, branch circuit protection and disconnect devices. Failure to do so may result in personal injury and/or equipment damage. CAUTION: Incorrectly applied of installed DC contactors can result in component damage or a reduction in product life. Wiring of application errors, such as improper wire sizing or excessive ambient temperatures may result in a malfunction of these devices. Bulletin 1370 DC Contactors have the following features: Contacts - the double break silver cadmium oxide contacts are weld resistant for improved reliability. Movable contacts are wedge shaped, while the stationary contacts have a unique “fold back” design. On contact opening, this “fold back” design generates a strong magnetic field which quickly throws the arc off the contact surface of the chamber. Coil - The contactor coils are hot pressure molded in thermoset epoxy to protect against mechanical damage and harmful environments. The coil shunt plate is designed to retard the magnetic flux until the voltage applied reaches the “pick up” voltage. Each coil is provided with an exclusive thermal cutout which is designed to open on excessive currents of misapplied voltages. Magnet - The high efficiency magnet has a permanent air gap. Pole face wear cannot affect the air gap and cause magnetic sticking due to residual magnetism. Each magnet lamination is phosphate coated to provide ample resistance to corrosion. Faxback Document # 1570 Web location http://www.ab.com/drives Page 1 of 12 Specifications Table A provides the electrical and environmental specifications for the DC Loop Contactors Table A Contactor Specifications Contact Rating - N.O. Voltage: 56A through 280A - 550V DC maximum, 360A - 500V DC maximum Full Load Steady State Current: 56A contactor - 56A DC maximum 110A contactor - 110A DC maximum 180A contactor - 180A DC maximum 280A contactor - 280A DC maximum 360A contactor - 360A DC maximum Contact Break Current(at 550V DC motor load): 56A contactor - 112A DC maximum 110A contactor - 220A DC maximum 180A contactor - 360A DC maximum 280A contactor - 560A DC maximum 360A contactor - 900A DC maximum Contact Rating - N.C. Voltage: Contact Make Current (at 550V DC motor load): 550V DC maximum (500V DC maximum for 360A) 56A contactor - 112A DC 110A contactor - 220A DC 180A contactor - 360A DC 280A contactor - 560A DC 360A contactor - 900A DC Auxiliary Contact Rating Voltage: 115V AC, 50/60 Hz Continuous Current (all contactors): 10A AC maximum Contact Break Current (all contactors): Coil Ratings Voltage (all contactors): 6A AC maximum Operate: Pickup: 75% of nominal (maximum) Dropout: 55% of nominal (maximum) 2,100V RMS (all electrical elements to ground) 0 to 65°C (32 to 149°F) Vertical Breakdown Voltage Ambient Operating Temperature Mounting Orientation Contact Termination Line and Load Terminals for N.O. Contact: Dynamic Braking Terminals for N.C. Contact: Coil Termination Contact Material Auxiliary Contact Faxback Document # 1570 115V AC, 50/60 Hz 56A contactor - 10-32 x 25/64” screw, 35 lb-in torque 110A contactor - 1/4-28 x 3/8” bolt, 45 lb-in torque 180A contactor - 5/16-24 x 1/2” bolt, 150 lb-in torque 280A contactor - 1/2-13 stud with nut, 400 lb-in torque 360A contactor - 4 lugs-#4 AWG to 500 MCM 56A contactor - 10-32 x 25/64” screw, 35 lb-in torque 110A contactor - 1/4-28 x 3/8” bolt, 45 lb-in torque 180A contactor - 5/16-24 x 1/2” bolt, 150 lb-in torque 280A contactor - 3/8-24 x 5/8 bolt, 240 lb-in torque 360A contactor - 2 lugs-#4 AWG to 500 MCM Captive Pressure Plate for 2 - #12 AWG wires maximum Silver Cadmium Oxide with Captive Pressure Plate for 2 - #14 AWG wires maximum Web location http://www.ab.com/drives Page 2 of 12 Dimensions NOMINAL DIMENSIONS AND WEIGHTS - NON-REVERSING CONTACTOR
In inches (millimeters) and pounds (kilograms)
Current Rating (Continuous) 56A 56A 110A 110A 180A 180A 280A 280A 360A 360A Power Poles 2 - N.O. 1 - N.O. 2 - N.O. 2 - N.O. 1 - N.O. 2 - N.O. 2 - N.O. 1 - N.O. 2 - N.O. 2 - N.O. 1 - N.O. 2 - N.O. 2 - N.O. 1 - N.O. 2 - N.O. Faxback Document # 1570 Catalog Number 1370-DC56 1370-NC56 1370-DC110 1370-NC110 1370-DC180 1370-NC180 1370-DC280 1370-NC280 1379-DC360 1379-NC360 A B C D E J 3.56 (90.4) 3.56 (90.4) 3.94 (100.1) 3.94 (100.1) 6.13 (155.7) 6.13 (155.7) 7.00 (177.8) 7.00 (177.8) 9.50 (241.3) 9.50 (241.3) 6.00 (152.4) 6.00 (152.4) 6.81 (173.0) 6.81 (173.0) 10.04 (255.0) 10.04 (255.0) 11.40 (289.6) 11.40 (289.6) 15.40 (391.2) 15.40 (391.2) 4.47 (113.5) 4.47 (113.5) 4.63 (117.6) 4.63 (117.6) 6.09 (154.7) 6.09 (154.7) 7.66 (194.6) 7.66 (194.6) 7.50 (190.5) 7.50 (190.5) 1.38 (35.0) 1.38 (35.0) 1.58 (40.1) 1.58 (40.1) 2.75 (69.8) 2.75 (69.8) 3.16 (80.3) 3.16 (80.3) 3.50 (88.9) 3.50 (88.9) 5.50 (139.7) 5.50 (139.7) 6.31 (160.3) 6.31 (160.3) 8.66 (220.0) 8.66 (220.0) 9.84 (250.0) 9.84 (250.0) 13.50 (342.9) 13.50 (342.9) #10(0.5) Approximate Weight 3.0(1.4) #10(0.5) 3.0(1.4) #10(0.5) 4.0(1.8) #10(0.5) 4.0(1.8) 3-1/4 (6.4) 3-1/4 (6.4) 3-5/16 (7.9) 3-5/16 (7.9) 3-0.406 (10.3) 3-0.406 (10.3) 12.0(5.4) Web location http://www.ab.com/drives 12.0(5.4) 22.0(10.0) 22.0(10.0) 45.0(20.5) 45.0(20.5) Page 3 of 12 Nominal Dimensions and Weights - Reversing Contactor
In inches (millimeters) and pounds (kilograms)
Current Rating (Continuous) 56A 110A 180A 280A 360A ➀
Power Poles Catalog Number 4 - N.O. 2 - N.C. 4 - N.O. 2 - N.C. 4 - N.O. 2 - N.C. 4 - N.O. 2 - N.C. 1370-RC56 4 - N.O. 2 - N.C. 1370-RC360 1370-RC110 1370-RC180 1370-RC280 A B C D E F J Approximate Weight 8.00 (203.2) 9.06 (230.1) 12.88 (327.2) 14.84 (376.9) 7.59 (192.8) 8.38 (212.9) 10.66 (270.8) 12.72 (323.1) 4.63 (117.6) 4.88 (124.0) 6.31 (160.3) 7.94 (201.7) 7.09 (180.1) 7.88 (200.2) 11.81 (300.0) 13.78 (350.0) 7.09 (180.1) 7.88 (200.2) 9.84 (250.0) 11.81 (300.0) 3.17 (80.5) 4.34 (110.2) _ #10(0.5) 8.75(3.9) #10(0.5) 11.0(5.0) 4-1/4 (0.64) 4-5/16 (0.79) 30.0(13.6) 19.25 (488.9) 15.38 (390.6) 8.63 (219.2) 17.00 (431.8) 13.50 (342.9) _
_ 2-.406 ➀
(10.3)
47.0(21.3) 90.0(40.9)
360a Contactors Only - Key hole (2 plcs.) at top of contactor is 0.188R, 0.750 Dia. Faxback Document # 1570 Web location http://www.ab.com/drives Page 4 of 12 Unpacking and Inspection Remove all packing material, wedges, or braces form within the contactor. If any part of the equipment will not be installed when it is unpacked, it must be stored in a clean, dry place. The storage temperature must be between - 30°C and +65°C (-22°F and + 149°F) and a humidity range of 5% to 95%, non-condensing, to guard against damage to components. After unpacking, check the material received against the Bill of Lading to assure that the nameplate description of each item agrees with the material ordered. When checking the items received, refer to the Catalog Number Explanations provided in Figures 3 and 4. Inspect the items for physical damage such as cracks in moldings or insulators. 1370 N C 56 First Position Second Position Third Position Fourth Position Bulletin No. Type Contactor Current Rating Letter N Description Non
Reversing D NonReversing w/DB Reversing w/DB R Number 56 Amperes 56 110 110 180 180 280 280 360 360 Figure 3 - Contactor Catalog Number Explanation 1370 LG 40 First Position Second Position Third
Position
Bulletin No. Lug Kit Lug Current Rating Number 40 52 56 68 92 104 110 120 140 160 180 204 228 248 268 280 Amperes 40 52 56 68 92 104 110 120 140 160 180 204 228 248 268 280 Figure 4 - Lug Kit Catalog Number Explanation Operation Faxback Document # 1570 Web location http://www.ab.com/drives Page 5 of 12 When the coil is energized, the magnet closes. The contact carrier moves upward into place and closes the power contacts. Movable contact springs are used to provide proper contact seating. Shock absorbing pads are provided in the cover and base assemblies to reduce the impact of pickup and drop-out. Installation The contactor must be vertically mounted in a clean, dry location. Oils, coolants and other debris must be kept from settling on the contactor. The choice of an appropriate NEMA enclosure type for the application is important. Special considerations should also be given to the wire bend radius and wire clearances. WARNING: The contactor must be mounted in a vertical position. Failure to observe this mounting practice will result in improper operation of the contactor and personal injury. Refer to the National Electrical Code and Local Codes for specific installation guidelines. The supplied surge suppressor will reduce noise interference that could adversely affect Drive performance. Install the suppressor on the contactor coil using the instructions provided below. Reversing contactors are supplied with factory installed suppressors on each coil. CAUTION: Component damage may occur if more than 132V AC is applied to the suppressor. Suppressor Installation 1. 2. 3. 4. Loosen coil terminal clamps. Slide surge suppressor onto coil terminals. Place coil circuit conductors between suppressor terminals and coil terminal clamps. Tighten coil terminal clamps securely. Wiring Figure 5 shows the typical wiring diagrams for the DC contactors. Refer to Figures 6 and 7 for specific terminal identification.
When wiring Dynamic Braking Resistors, use wire with a current capacity at least 1/2 that of the full load current rating of the motor.
IMPORTANT: Consult the National Electrical Code and local codes for specific guidelines on wire size and type for dynamic
braking resistor application.
All DC Drive module power connections (Keps-nuts) are to be installed to the following torque settings:
1/4 inch bolt - 35 in-lbs.
3/8 inch bolt - 75 in-lbs.
1/2 inch bolt - 150 in-lbs.
3/4 inch bolt - 300 in-lbs.
Faxback Document # 1570 Web location http://www.ab.com/drives Page 6 of 12 Faxback Document # 1570 Web location http://www.ab.com/drives Page 7 of 12 Auxiliary Contact Installation Auxiliary contact assemblies can be used on all contactor ratings, 56 through 280 amperes. The N.O. auxiliary contact is designed to be open when the contactor is de-energized. The N.C. auxiliary contact is designed to be closed when the contactor is de-energized. A (1) N.O. auxiliary contact assembly is supplied on the contactor in position P1 for use with the DC Drive module enable function. Reversing contactors have an additional N.O. and N.C. auxiliary contact position P4. The N.C. contact is used to electrically interlock the forward and reverse contactor coil circuits. The N.O. contact is used with the control circuit forward and reverse selection function to prevent changing the direction once the Drive is in operation. Additional auxiliary contact assemblies may be installed in positions P2, P3 and P4 on non-reversing contactors. On reversing 180 and 280 ampere contactors, additional contact assemblies may be installed in all P2 and P3 positions. Placement on 56 and 110 ampere contactors will depend on the type of contact assembly that can be installed in the vacant P2 and P3 positions between the forward and reverse contactors. Installation WARNING: Open and lock-out main supply disconnect and all other power source disconnects to avoid hazard of electrical shock or injury form unintended actuation of controlled equipment. 1. 2. 3. 4. Turn the Drive circuit breaker OFF and remove cabinet power. Align arrows on the reverse side of the contact and locate the tabs. Insert the auxiliary contact, tabs first, into the appropriate position on the side of the contactor. Push, to lock the contact in place. Select the desired terminals and connect the corresponding wires. Replacement Refer to the following steps if replacement of the Auxiliary contact becomes necessary. 1. 2. Turn the Drive circuit breaker OFF and remove cabinet power. Loosen the Coil Cover and pull the auxiliary contact straight out. Maintenance The Bulletin 1370 DC Contactors are constructed such that a minimum amount of maintenance is needed. As a result of normal use, the contacts will eventually begin to deteriorate. Periodic inspection of these contacts should be part of any Drive system preventative maintenance program. If contact inspection reveals severe erosion on the power pole contacts, it is recommended that the power poles (if possible) or contactor be replaced. Replacing the contactor will help reduce the effects of uneven and unequal contact closings. If the contactor has not been used for extended period of time, a brief inspection for mechanical integrity and contact corrosion should be made before use. Faxback Document # 1570 Web location http://www.ab.com/drives Page 8 of 12 Bulletin 1370/1379
Drive Contactor Cross Reference Note and Contactor Renewal Parts
The following lists cross reference the catalog number, Mequon part number and the Milwaukee part number for DC contactors. Also included are the renewal parts needed for the contactors. OBSOLETE CONTACTOR CROSS REFERENCE Mequon Catalog Number * 1379-NC30 1379-NC56 1379-NC110 1379-NC210 1379-DC30 1379-DC56 1379-DC110 1379-DC210 1379-RC30 1379-RC56 1379-RC110 1379-RC210 * Mequon Part Number 101287 101288 101289 101290 101277 101278 101279 101280 101281 101282 101283 101284 Allen-Bradley Catalog Number 202AC-ZOD-X532 202AC-ZOD-X533 202AC-ZOD-X534 202AC-ZOD-X535 202AC-ZOD-X537 202AC-ZOD-X538 202AC-ZOD-X539 202AC-ZOD-X540 202AC-ZOD-X557 202AC-ZOD-X558 202AC-ZOD-X559 202AC-ZOD-X560 NC = Non-Reversing, DC = Dynamic Braking, RC = Reversing CURRENT 1379 CONTACTOR KITS (Includes surge suppressor and instructions) Catalog Number 1379-NC360 1379-DC360 1379-RC360 Kit Number 101246 102251 102256 Contactor Number 101291 101300 101301 CURRENT CONTACTOR CROSS REFERENCE Catalog Number
1370-NC56 1370-NC110 1370-NC180 1370-NC280 1370-NC360 1370-DC56 1370-DC110 1370-DC180 1370-DC280 1370-DC360 1370-RC56 1370-RC110 1370-RC180 1370-RC280 1379-RC360 Old Mequon Part Number 107753 107763 107773 107783 101291 107748 107758 107768 107778 101300 113801 113802 113803 113804 101301 Faxback Document # 1570 New Mequon Part Number 123142 123141 123140 123139 101291 123146 123145 123144 123143 101300 123195 123196 123197 123198 101301 Allen-Bradley Part Number 40411-672-01 40411-672-02 40411-672-03 40411-672-04 202AC-ZOD-X536 40411-672-05 40411-672-06 40411-672-07 40411-672-08 202AC-ZOD-NX12 40444-616-01 40444-616-02 40444-616-03 40444-616-04 205AC-NX2 Web location http://www.ab.com/drives
Page 9 of 12 Contactor Spare Parts List Single Pole N.O. Contact Kit Includes: One each: front and rear stationary contact, contact spring and movable contact. Normally Closed Contact(DB Pole) Kit Includes: Front or rear stationary contact; contact spring, spanner guide, spanner assembly and screws. 56 amp list
Single Pole N.O. Contact Part Kit Number Normally Closed Contact (DB Pole) Kit number: Part Number 40410-331-54
40410-857-01
110 Amp List Single Pole N.O. Contact Part Kit Number Normally Closed Contact (DB Pole) Kit number 40420-322-52
40420-850-01
180 Amp List Single Pole N.O. Contact Part Kit Number Normally Closed Contact (DB Pole) Kit number 40430-300-52
40430-850-01
280 Amp List Single Pole N.O. Contact Part Kit Number Normally Closed Contact (DB Pole) Kit number 40440-325-52
40440-850-01
360 Amp List Single Pole N.O. Contact Part Kit Number
Normally Closed Contact (DB Pole) Kit numbers:
Z-34042 40450-319-52 Obsolete: Front Terminal Assembly 40450-320-52 Obsolete: Rear Terminal Assembly 40450-318-52 Obsolete: Moveable Contact Contactor Listing Catalog Number 1370-NC56, 1370-DC56, 1370-RC56 1370-NC110, 1370-DC110, 1370-RC110 1370-NC180, 1370-DC180, 1370-RC180 1370-NC280, 1370-DC280, 1370-RC280 1370-NC360, 1370-DC360, 1370-RC360 Contactor Size (refer to above for contact kit part number) 56 Amp 110 Amp 180 Amp 280 Amp 360 Amp AUXILIARY CONTACTS Part Number 107482 101905 101242 115015 Description 1 N.O. -1 N.C. 1 N.O. 1 N.C. 2 N.O. Faxback Document # 1570 Allen-Bradley Catalog Number Bulletin 595-AB Bulletin 595-A Bulletin 595-B Bulletin 595-AA Web location http://www.ab.com/drives
Page 10 of 12 Cross Reference by Part Number
Contactor Part Number 101291 101300 101301 123139 123140 123141 123142 123143 123144 123145 123146 123148 123149 123152 123154 123155 123158 123160 123161 123164 123166 123167 123170 123172 123173 123176 123178 123179 123182 123185 123188 123190 123191 123194 123195 123196 123197 123198 147703 147704 163440 170858 170861 172002 Faxback Document # 1570 Description and Current Rating 1379-NC360 1379-DC360 1379-RC360 1370-NC280 1370-NC180 1370-NC110 1370-NC56 1370-DC280 1370-DC180 1370-DC110 1370-DC56 56 amps; 115v coil, w/o DB 56 amps; 230v coil, w/o DB 56 amps, 460v coil, w/o DB 110 amps, 115v coil, w/o DB 110 amps, 230v coil, w/o DB 110 amps, 460v coil, w/o DB 180 amps, 115v coil, w/o DB 180 amps, 230v coil, w/o DB 180 amps, 460v coil, w/o DB 280 amps, 115v coil, w/o DB 280 amps, 230v coil, w/o DB 280 amps, 460v coil, w/o DB 56 amps,115v coil, DB 56 amps, 230v coil, DB 56 amps, 460v coil, DB 110 amps, 115v coil, DB 110 amps, 230v coil, DB 110 amps, 460v coil, DB 180 amps, 230v coil, DB 180 amps, 460v coil, DB 280 amps, 115v coil, DB 280 amps, 230v coil, DB 280 amps, 460v coil, DB 1370-RC56 1370-RC110 1370-RC180 1370-RC280 1800 amps, 100vdc coil, w/o DB 3000 amps, 100vdc coil, w/o DB 180 amps, 115v coil, DB 360 amps, 115v coil, w/o DB 360 amps, 115v coil, DB 1250 amps, Spare Parts Reference 360 Amp List 360 Amp List 360 Amp List 280 Amp List 180 Amp List 110 Amp List 56 Amp List 280 Amp List 180 Amp List 110 Amp List 56 Amp List 56 Amp List 56 Amp List 56 Amp List 110 Amp List 110 Amp List 110 Amp List 180 Amp List 180 Amp List 180 Amp List 280 Amp List 280 Amp List 280 Amp List 56 Amp List 56 Amp List 56 Amp List 110 Amp List 110 Amp List 110 Amp List 180 Amp List 180 Amp List 280 Amp List 280 Amp List 280 Amp List 56 Amp List 110 Amp List 180 Amp List 280 Amp List C-H Contactor C-H Contactor 180 Amp List 360 Amp List 360 Amp List Siemens Contactor Web location http://www.ab.com/drives Page 11 of 12 Cross reference by Description
Description and Current Rating 56 amps, 230v coil, DB 56 amps, 460v coil, DB 56 amps, 460v coil, w/o DB 56 amps,115v coil, DB 56 amps; 115v coil, w/o DB 56 amps; 230v coil, w/o DB 110 amps, 115v coil, DB 110 amps, 115v coil, w/o DB 110 amps, 230v coil, DB 110 amps, 230v coil, w/o DB 110 amps, 460v coil, DB 110 amps, 460v coil, w/o DB 180 amps, 115v coil, DB 180 amps, 115v coil, w/o DB 180 amps, 230v coil, DB 180 amps, 230v coil, w/o DB 180 amps, 460v coil, DB 180 amps, 460v coil, w/o DB 280 amps, 115v coil, DB 280 amps, 115v coil, w/o DB 280 amps, 230v coil, DB 280 amps, 230v coil, w/o DB 280 amps, 460v coil, DB 280 amps, 460v coil, w/o DB 360 amps, 115v coil, DB 360 amps, 115v coil, w/o DB 1250 amps, 1800 amps, 100vdc coil, w/o DB 3000 amps, 100vdc coil, w/o DB 1370-NC56 1370-DC56 1370-RC56 1370-NC110 1370-DC110 1370-RC110 1370-NC180 1370-DC180 1370-RC180 1370-NC280 1370-DC280 1370-RC280 1379-DC360 1379-NC360 1379-RC360 Faxback Document # 1570 Contactor Part Number 123173 123176 123152 123172 123148 123149 123178 123154 123179 123155 123182 123158 163440 123160 123185 123161 123188 123164 123190 123166 123191 123167 123194 123170 170861 170858 172002 147703 147704 123142 123146 123195 123141 123145 123196 123140 123144 123197 123139 123143 123198 101300 101291 101301 Spare Parts Reference 56 Amp List 56 Amp List 56 Amp List 56 Amp List 56 Amp List 56 Amp List 110 Amp List 110 Amp List 110 Amp List 110 Amp List 110 Amp List 110 Amp List 180 Amp List 180 Amp List 180 Amp List 180 Amp List 180 Amp List 180 Amp List 280 Amp List 280 Amp List 280 Amp List 280 Amp List 280 Amp List 280 Amp List 360 Amp List 360 Amp List Siemens Contactor C-H Contactor C-H Contactor 56 Amp List 56 Amp List 56 Amp List 110 Amp List 110 Amp List 110 Amp List 180 Amp List 180 Amp List 180 Amp List 280 Amp List 280 Amp List 280 Amp List 360 Amp List 360 Amp List 360 Amp List Web location http://www.ab.com/drives Page 12 of 12