Bulletin 1305, .5

Bulletin 1305, .5 - 5 Hp
Fuses
Based on testing of a number of different fuse classes, the following recommendation
should be observed in order to avoid nuisance blowing of fuses.
For 460 V drives .5 Hp and .75 Hp where Table 2.A on page 2-4 in the manual indicates
that 3 A fuses should be used, this statement must be added to the text so the table and
text would look something like this:
3∅
∅ Rating
kW (Hp)
.37 (1/2)
.55 (3/4)
.75 (1)
1.5 (2)
2.2 (3)
4 (5)
1∅
∅ Rating
kW (Hp)

.37 (1/2)
.55 (3/4)
.75 (1)
1.5 (2)

Fuse
230 V Rating
6
6
10
15
25

Fuse
460 V Rating
3*
3*
6
10
15
20
* Must be of the type “ Dual Element Time Delay”, e.g. Bussmann “LPJ” or
equivalent. In case other drive sizes display problems with blown fuses, use the
“Dual Element Time Delay” type. A typical example would be if an installation
has a permanent high line voltage condition.