diesel generator set air charge-air cooling

DIESEL GENERATOR SET
AIR CHARGE-AIR COOLING
1120kVA/50 Hz/Prime Power (TAL)
380 - 415V
Optional equipment shown. Standard equipment may vary.
BENEFITS
//
//
//
//
Industry-leading average load factor
Outstanding fuel economy
Optimized maintenance intervals
Low installation costs
//
//
//
Best-in-class reliability and availability
Lifting vertically or with diagonal pull
Compact design
SYSTEM RATINGS➀
Prime Power
MTU 18V2000 DS1250
MTU 18V2000 DS1250
MTU 18V2000 DS1250
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
Generator model
Temp rise
Connection
380V
3
0.8
50
896
1120
1702
740RSL7076
125°C/40°C
6 LEAD HI WYE
400V
3
0.8
50
896
1120
1617
740RSL7076
125°C/40°C
6 LEAD HI WYE
415V
3
0.8
50
896
1120
1558
740RSL7076
125°C/40°C
6 LEAD HI WYE
➀ Power available up to 25°C/100 m
2
/ // / 50 Hz 1120 kVA
CERTIFICATIONS AND STANDARDS
Engine-generator set is designed and manufactured in
facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
// Performance Assurance Certification (PAC)
- Engine-generator set tested according to ISO 8528-5 for
transient response
- Verified product design, quality and performance integrity
- All engine systems are type and factory tested
//
//
Power Rating
- Permissible average power output during 24 hours of
operation up to 75%
//
Generator
STANDARD EQUIPMENT➀
//
Engine
Air cleaners
Oil pump for draining
Full flow oil filters
Closed crankcase ventilation
Jacket water pump
Thermostats
Exhaust manifold – dry
Belt driven radiator fan
Radiator – unit mounted
Electric starting motor – 24V
Governor – electronic isochronous
Base – formed steel
SAE flywheel & bell housing
Charging alternator
Flexible fuel connectors
Flexible exhaust connection
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor
VDE 0530, IEC 60034-1, BS4999, BS5000, CSA22.2-100, AS 1359
Sustained short circuit current of up to 250%
Self-ventilated and drip-proof IP23
Superior voltage waveform
Digital, volts-per-hertz regulator
No load to full load regulation
Brushless alternator with brushless pilot exciter
4 Pole, rotating field
125°C maximum prime temperature rise
Heavy duty shielded ball bearings with a minimum B-10 life of
40,000 hrs
Flexible coupling
Full amortisseur windings
3-phase voltage sensing
±0.25% voltage regulation
100% of rated load – one step according to NFPA 110
3% maximum harmonic content
➀ Represents standard product only. Consult Factory/MTU Onsite Energy distributor for additional configurations.
/ // / 50 Hz 1120 kVA
3
STANDARD FEATURES➀
//
//
//
//
//
//
//
The engine-generator set complies to G3
Engine generator set tested according to ISO 8528-5 for
transient response
Accepts rated load in one step as per NFPA 110
All engine-generator sets are type and factory tested
MTU Onsite Energy is a single source supplier
Global product support
Cooling System (integral set-mounted; engine driven fan)
//
//
18V2000 diesel engine (35,82 liter (2186 cu inch)
displacement; 4-stroke)
Engine-generator resiliently mounted
Complete range of accessories
Brushless, rotating field generator (PMG excitation;
250% short circuit capability; 2/3 pitch stator windings)
Complete system metering
LCD display
//
Fuel Consumption➁
//
//
//
//
APPLICATION DATA
//
Engine
Manufacturer
Model
Type
Arrangement
Displacement/cylinder: l (cu inch)
Bore: mm (inch)
Stroke: mm (inch)
Compression ratio
Rated speed rpm
Engine governor
Max power: kWm (bhp)
Speed regulation
Air filter
//
MTU
18V2000G65TD
4-Stroke
18-V
1.99 (121)
130 (5.1)
150 (5.9)
16:1
1500
Electronic isochronous
1000 (1341)
±0.25%
Dry
Lube Oil Capacity
Total oil system: l (gal)
//
130 (34)
Electrical
Electric Volts DC
Cold cranking amps under -17.8 °C (0 °F)
24
1000
At 100% of power rating:
At 75% of power rating:
At 50% of power rating:
//
//
l/hr
270
197
131
g/kwh
224
218
218
Cooling/Radiator System
Ambient capacity of radiator: °C
Max. restriction of cooling air, intake,
and discharge side of rad.: kPa (in. H20)
Water pump capacity: l/min (gpm)
Heat rejection to coolant: kW (BTUM)
Heat rejection to after cooler: kW (BTUM)
Heat radiated to ambient: kW (BTUM)
Engine coolant capacity: l (gal)
Coolant to cooler temperature: °C (°F)
32
0,2 (0,803)
667 (176)
440 (25,022)
300 (17,060)
50 (2,843)
120 (32)
95 (203)
Air Requirements➂
Aspirating: m3/min (SCFM)
Air flow required for rad.
cooled unit: m3/min
//
//
gal/hr
71
52
35
90 (3177)
1157 (40854)
Exhaust System
Fuel System
Fuel supply connection size
Fuel return connection size
Maximum fuel lift: m (ft)
Recommended fuel
Total fuel flow: l/hr (gal/hr)
M22x1,5 - 60°/Male
M12x1,5 - 60°/Male
3 (9,84)
see MTU fluids & lubrication spec.
600 (159)
Gas temp. (stack): °C (°F)
Gas volume flow
temp: m3/min (SCFM)
Maximum allowable
back pressure: kPA
➀ Represents standard product only. Consult Factory/MTU Onsite Energy distributor for additional configurations.
➁ Values in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml.
➂ Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
540 (1004)
246 (8687)
5
4
/ // / 50 Hz 1120 kVA
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based an standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.
System
Open Power Unit (OPU)
Dimensions (L x W x H)
4916 x 2140 x 2346 mm (194 x 84 x 92 inch)
Weight (dry)
6920 kg (15,256 lbs)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific engine-generator set.
SOUND DATA
//
Consult your local MTU Onsite Energy distributor for sound data.
EMISSIONS DATA
//
Consult your local MTU Onsite Energy distributor for emissions data.
RATING DEFINITIONS AND CONDITIONS
Prime power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number
of generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in
accordance with ISO 8528-1, ISO 3046-1, BS 5514 and AS 2789. Average load factor: ≤ 75%.
// Deration factor:
Altitude: Consult your local MTU Onsite Energy distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy distributor for temperature derations.
Materials and specifications subject to change without notice.
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
Subject to change. | 3236651 | Edition 02/14 | ENC 2014-07.
//