DMS-20PC-2-LM - Murata Power Solutions

DMS-20PC-2-LM
www.murata-ps.com
Self-Powered LED Display High-Voltage,
50/60/400Hz AC Line Monitor
C
FEATURES

Self-powered, two-terminal operation

Dual operating ranges: 240-310Vac at 50/60Hz or
85-140Vac at 400Hz

Half-wave averaging, rms calibrated

Large, easy-to-read, bright red LED display

Rugged, epoxy-encapsulated construction

Built-in bezel for panel mounting

Reliable screw terminals for easy installation

Small 1.38" x 0.88" x 1.0" package

Approvals to UL/cUL/IEC/61010-1
Functional Specifications
Input
Voltage Range ➀
Current Consumption
240-310Vrms (47-99Hz)
85-140Vrms (350-450Hz)
50mArms (max.)
UL/IEC61010-1
Measurement category II
Performance
Sampling Rate
Measurement Type
2.5 readings/second
Half-wave average, rms
calibrated for sinusoidal input
±1V (typ.), ±2V (max.)
Accuracy @ +25°C
Temperature Drift
(–25 to +60°C)
±0.15 Volts/°C (max.)
Mechanical
Dimensions
Display Type
Weight
Case Material
6-32 screw torque
Environmental
Operating Temperature
Storage Temperature
Humidity (Non-condensing)
1.38” x 0.88” x 1.00”
3 digit, red LED, 0.37”/9.4mm
1 ounce (28 grams)
Polycarbonate
6-8 in-lb (0.7 – 0.9N-m)
®
US E156931
DATEL’s DMS-20PC-2-LM is a component-size, self-contained, low-cost ac voltmeter
specifically designed for high-voltage or high-frequency operation. The DMS-20PC-2-LM’s
unique power-supply circuitry allows a single model
to operate from either 240 to 310Vac with 50/60Hz
inputs or from 85 to 140Vac with 400Hz inputs. The
meter requires no external components or auxiliary
power for full operation! Its large, 0.37"/9.4mm,
bright red LED display is easily readable under virtually all lighting conditions.
DMS-20PC-2-LM employs half-wave sinusoidal
averaging (rms calibrated) to achieve a display
resolution of 1Vac over its full operating range.
Packaged in a red-filter case with a built-in bezel,
the meter is epoxy encapsulated for ruggedness.
This low-cost, extremely versatile digital voltmeter is ideal for use in emergency power equipment, 277Vac fluorescent lighting systems, 400Hz
aircraft installations, and any other application
requiring accurate, high-voltage or high-frequency,
ac line monitoring.
Typical panel mount installation
Suggested wiring (user supplied)
Ordering Information
DMS-20PC-2-LM-C
DMS-BZL3-C
DMS-BZL4-C
DMS-20-CP
High-voltage ac line monitor with screw terminals and screws
Panel mount bezel
Panel mount bezel with sealing gasket
Panel cutout punch
Brass screws (6-32 thread) and a panel-mount retaining clip are supplied with each meter
–25 to +60°C
–40 to +75°C
0 to 95%
➀ Operation and accuracy at inputs above or below this range are
not specified.
CURRENT
LIMITED
AC SUPPLY
For full details go to
www.murata-ps.com/rohs
Typical Connection Diagram
www.murata-ps.com/support
MPM_DMS-20PC-2LM.B06 Page 1 of 2
DMS-20PC-2-LM
Self-Powered LED Display High-Voltage,
50/60/400Hz AC Line Monitor
Power Supply Polarity, Fusing, Wiring, and Grounding: DMS-20PC-2-LM’s
two ac-supply terminals are not polarity sensitive, that is, they have no “AC LO”
or “AC HI” designations. These units do not include nor require a connection to
earth/chassis ground.
nal circuitry; they must not be used to supply power to external loads. Depending on the ac supply line-voltage in the user’s installation, the supply wires
feeding these voltmeters must be fused with a 0.25A/250V or a 0.25A/600V
time delay/time lag fuse, in accordance with applicable regulatory codes.
All ac-supply wiring must be rated for the voltages and currents they will
conduct and comply with any code or application-mandated requirements
pertaining to the user’s specific installation. 300V UL rated wire suitable for the
intended application is required.
The recommended wire size is 16AWG to 20AWG (1.31mm2 to 0.52mm2)
stranded copper wire. Wires must be properly stripped and attached to the
threaded standoffs such that their insulation is not pinched by the supplied
6-32 screws. Rated tightening torque for the 6-32 screws is 7 to 8 poundinches (0.8 to 0.9N-m).
DMS-20PC-2-LM ac voltmeters are not internally fused. The rear threaded
standoff input-terminals are to be used only for powering the voltmeter’s inter1. Description of safety marks:
Caution, risk of electrical shock
Caution, risk of danger
Equipment is protected throughout by double or reinforced insulation
2. Cleaning Instructions: Gently clean with dry cloth only.
3. Caution: if the equipment is used in a manner not specified by Murata Power Solutions, the protection provided by the equipment may be impaired.
1.30
(33.0)
DMS-20PC-2-LM
®
®
0.04
(1.016)
0.04
(1.016)
#6-32
UNC THD
0.44
(11.2)
0.80
(20.3)
0.88
(22.4)
0.32
(8.1)
0.75
(19.1)
1.38
(35.1)
0.37
(9.4)
1.00
(25.4)
#2-56 INSERT
0.156 (3.96) DEEP
1.07
(27.2)
DMS-BZL3-C
Optional Bezel
0.10
(2.5)
1.63 (41.4)
Murata Power Solutions, Inc.
11 Cabot Boulevard, Mansfield, MA 02048-1151 U.S.A.
ISO 9001 and 14001 REGISTERED
0.04
(1.016)
0.19
(4.8)
1.28
(32.5)
Dimensions in inches (millimeters)
Tolerances: 2 PL Dec ±0.02 (±0.51)
3 PL Dec ±0.010 (±0.254)
Recommended panel cutout dimensions:
1.336 (33.93)W × 0.838 (21.29)H
Internal corner radii 0.032 (0.81) Max.
0.10
(2.5)
1.83 (46.5)
Murata Power Solutions, Inc. makes no representation that the use of its products in the circuits described herein, or the use of other
technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do not imply
the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifications are subject to change without
notice.
© 2014 Murata Power Solutions, Inc.
www.murata-ps.com/support
MPM_DMS-20PC-2LM.B06 Page 2 of 2