DMS-20PC-FM Series - Murata Power Solutions

DMS-20PC-FM Series
www.murata-ps.com
Self-Powered, 3-Digit LED Display
AC Line Frequency Monitors
FEATURES
■
Self-powered, no external supplies required
■
3 models:
■
Screw terminals simplify panel mounting
■
Ideal for emergency power equipment
■
Small 1.38" x 0.88" x 1.0" packages
■
Epoxy encapsulated for harsh environments
■
Large (0.40"/10.2mm) red LED displays
47.0-99.0Hz (85-140Vac)
47.0-99.0Hz (170-264Vac)
350-450Hz (85-140Vac)
DATEL's new DMS-20PC-FM Series are the world’s smallest, self-powered, ac frequency meters. Simply connect the ac line to the two rear input terminals, and the unit is
fully operational with no additional components or auxiliary power required! Two, 50/60Hz
models operate over input voltage ranges of 85-140Vac or 170-264Vac. A third, 400Hz
model operates over an input voltage range of 85-140Vac. Despite their small size (1.38"
x 0.88" x 1.0"), DMS-20PC-FM meters feature large 0.40"/10.2mm red LED's that can be
read easily from 15 feet away.
DMS-20PC-1-FM-F
(Blade Terminals)
An ultra-stable, quartz-crystal-controlled,
embedded microcomputer provides accuracies
8C48
of ±0.1Hz (50/60Hz models) or ±1.0Hz (400Hz
model) over the entire operating temperature
range of –25 to +60°C. Epoxy encapsulated
plastic packages provide excellent protection against the harsh environments normally
encountered by emergency backup power
generators. DMS-20PC-FM meters are the exact
DMS-20PC-1-FM
same size as DATEL's popular AC Line Voltage
(Panel Mount)
Monitors (models DMS-20PC-X-LM).
®
Functional Specifications
Input
Freq. Range (Voltage Range): ➀
DMS-20PC-1-FM
DMS-20PC-2-FM
DMS-20PC-3-FM
Current Consumption
47.0-99.0Hz (85-140Vac)
350-450Hz (85-140Vac)
47.0-99.0Hz (170-264Vac)
50mArms (max.)
UL/IEC61010-1
Measurement Category II
Performance
Sampling Rate
Accuracy (–25 to +60°C):
DMS-20PC-1/3-FM
DMS-20PC-2-FM
Mechanical
Dimensions
Display Type
4 readings/second
±0.1Hz
±1.0Hz
Weight
Case Material
6-32 screw torque
1.38" x 0.88" x 1.00"
3 digit, red LED,
0.4"/10.2mm
1 ounce (28 grams)
Polycarbonate
6-8 in-lb (0.7 – 0.9N-m)
Environmental
Operating Temperature
Storage Temperature
Humidity (Non-condensing)
–25 to +60°C
–40 to +75°C
0 to 95%
C
®
US E156931
Suggested wiring (user supplied)
Ordering Information
DMS-20PC-1-FM-C
DMS-20PC-1-FM-F-C
DMS-20PC-2-FM-C
DMS-20PC-3-FM-C
DMS-20-CP
DMS-BZL3-C
DMS-BZL4-C
47-99Hz / 120Vac frequency monitor with threaded standoffs ➁
47-99Hz / 120Vac frequency monitor with blade terminals
350-450Hz / 120Vac frequency monitor with threaded standoffs ➁
47-99Hz / 220Vac frequency monitor with threaded standoffs ➁
Optional panel cutout punch
Optional panel mount bezel
Optional panel mount bezel with sealing gasket
➁ Brass screws (6-32 thread) and a panel-mount retaining clip are supplied with meter.
➀ Operation and accuracy at inputs above or below these
ranges are not specified.
CURRENT
LIMITED
AC SUPPLY
For full details go to
www.murata-ps.com/rohs
Typical Connection Diagram
www.murata-ps.com/support
MPM_DMS-20PC-FM.G06 Page 1 of 2
DMS-20PC-FM Series
Self-Powered, 3-Digit LED Display
AC Line Frequency Monitors
Power Supply Polarity, Grounding, Fusing, and Wiring
1. Polarity and Grounding:
DMS-20PC-FM’s two ac-supply input terminals are not polarity sensitive, that
is, they have no “AC LO” or “AC HI” designations. These units do not include
nor require a connection to earth/chassis ground. All ac-supply wiring must be
rated for the voltages and currents they will conduct and comply with any code
or application-mandated requirements pertaining to the user’s specific installation. Additional model-specific information is provided below.
3. UL Listed Models with “Plug-in” Blade Terminals:
2. UL Recognized Panel Mount Models with Screw Terminals:
4. Description of the safety marks:
Caution, risk of electrical shock
C
®
Plug-in DMS-20PC-1-FM-XF models are not internally fused and must be
protected by an external current limiting circuit breaker or fuse in accordance
with applicable regulatory codes. These models are designed to be plugged
into NEMA 1-15R, NEMA 5-15R, and NEMA 5-20R receptacles.
US E156931
Caution, risk of danger
DMS-20PC-FM AC frequency meters are not internally fused. The supply
wires feeding these meters must be fused with a 0.25A/250V time delay/time
lag fuse, in accordance with applicable regulatory codes. The rear threaded
standoff input-terminals are to be used only for powering the meter’s internal
circuitry; they must not be used to supply power to external loads.
The recommended wire size is 16AWG to 20AWG (1.31mm2 to 0.52mm2)
stranded copper wire. Wires must be properly stripped and attached to the
threaded standoffs such that their insulation is not pinched by the supplied
6-32 screws. Rated tightening torque for the 6-32 screws is 7 to 8 poundinches (0.8 to 0.9N-m). 300V UL rated wire suitable for the intended application is required.
Equipment is protected throughout by double or reinforced insulation
5. Cleaning Instructions: Gently clean with dry cloth only.
6. Caution: if the equipment is used in a manner not specified by Murata
Power Solutions, the protection provided by the equipment may be
impaired.
1.30
(33.0)
0.04
(1.016)
0.04
(1.016)
#6-32
UNC THD
0.44
(11.2)
0.80
(20.3)
0.32
(8.1)
0.75
(19.1)
1.38
(35.1)
0.44
0.88
(20.4) (10.2)
1.00
(25.4)
0.44
(10.2)
#2-56 INSERT
0.156 (3.96 DEEP
1.07
(27.2)
DMS-BZL3-C
Optional Bezel
0.10
(2.5)
1.63 (41.1)
0.44
(10.2)
0.10
(2.5)
Dimensions in inches (millimeters)
Tolerances: 2 PL Dec ±0.02 (±0.51)
3 PL Dec ±0.010 (±0.254)
Recommended panel cutout dimensions:
1.336 (33.93)W × 0.838 (21.29)H
Internal corner radii 0.032 (0.81) Max.
1.83 (46.5)
Murata Power Solutions, Inc.
11 Cabot Boulevard, Mansfield, MA 02048-1151 U.S.A.
ISO 9001 and 14001 REGISTERED
Murata Power Solutions, Inc. makes no representation that the use of its products in the circuits described herein, or the use of other
technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do not imply
the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifications are subject to change without
notice.
© 2013 Murata Power Solutions, Inc.
www.murata-ps.com/support
MPM_DMS-20PC-FM.G06 Page 2 of 2