BTE/PTE/PTU5000 pressure transmitter

BTE5000 / PTE5000 / PTU5000 Series
Precision differential pressure transmitters
FEATURES
· 25 mbar to 10 bar, 0.3 to 150 psi
differential pressure
· 1...6 V or 4...20 mA output12
· Precision temperature compensated
and calibrated
· Rugged aluminium housing
· Female 1/8" BSP and 1/8" NPT fittings
MEDIA COMPATIBILITY
Pressure inlet:
Non-corrosive, non-ionic media such as air, dry gases
and the like
Housing:
Aluminium, protection class IP 67 (according to
DIN EN 60529, NEMA 6)1
SPECIFICATIONS10,11
ELECTRICAL CONNECTION
Maximum ratings
1...6 V output version
Supply voltage
12...32 V
Output current BTE(M)/PTE/PTU5...D1...
Source
Sink
20 mA
10 mA
Output current BTE(M)/PTE/PTU5...D4...
30 mA
Temperature limits
Storage
Operating
Compensated
Pressure at any port
BTEM5x025... / PTx5000.3...
all others
Vout
2
-Vs
4
case
3
3.5 bar / 50 psi
12 bar / 175 psi
12 to 32 V
GND
V
4...20 mA output version
+Vs 1
Sensor
12 to 32 V
V
-Vs
3
E / 11101 / B
Sensor
-40...85 °C
-25...85 °C
0...70°C
Proof pressure2
BTEM5x025... / PTx5000.3...
0.35 bar / 5 psi
BTEM5x070..., BTEM5x350... /
1.4 bar / 20 psi
PTx5001..., PTx5005...
all others
2 x rated pressure
1
+Vs
4
RL
GND
case 3
1/5
www.first-sensor.com
www.sensortechnics.com
BTE5000 / PTE5000 / PTU5000 Series
Precision differential pressure transmitters
COMMON PERFORMANCE CHARACTERISTICS8
Characteristics
Thermal effects
(0 to 70°C)6
Offset
Min.
all ≤ 70 mbar / 1 psid devices
all 350 mbar / 5 psid devices
all others
Span
Non-linearity and hysteresis4
5
Typ.
Max.
Unit
±0.025
±0.008
±0.005
±0.001
±0.125
±0.040
±0.025
±0.045
%FSO/°C
±0.2
±1
Long term stability
±0.2
Output noise (0 ≤ f ≤ 1 kHz)
0.04
Response time (10 to 90 %)
1
%FSO
ms
INDIVIDUAL PERFORMANCE CHARACTERISTICS8
1...6 V output versions (VS = 15 V, tamb = 25°C, RL > 100 kΩ, com. mode pressure = 0)
Characteristics
Zero pressure offset
BTE(M)5P... / PTx5P...
all others
BTE(M)5P... / PTx5P...
all others
Full scale span7
Min.
Typ.
Max.
3.4
0.9
2.4
4.9
3.5
1.0
2.5
5.0
6.0
3.6
1.1
2.6
5.1
Full scale output
Power supply rejection
Offset
Span
0.05
0.03
Output impedance
V
%FSO/V
50
Power consumption
Unit
60
Ω
mW
4...20 mA output versions (VS = 15 V, tamb = 25°C, RL = 100 Ω, com. mode pressure = 0)
Characteristics
Zero pressure offset
Full scale span7
BTE(M)5P... / PTx5P...
all others
BTE(M)5P... / PTx5P...
all others
Full scale output
Power supply rejection
Offset
Span
Min.
Typ.
Max.
11.9
3.9
7.9
15.9
12.0
4.0
8.0
16.0
20.0
12.1
4.1
8.1
16.1
0.05
0.03
Output impedance
Power consumption (IL = 20 mA)
E / 11101 / B
mA
%FSO/V
0.1
260
Unit
Ω
mW
2/5
www.first-sensor.com
www.sensortechnics.com
BTE5000 / PTE5000 / PTU5000 Series
Precision differential pressure transmitters
LOAD LIMITATION
4...20 mA output versions
1200
Ohm
1000
800
600
operating
range
400
200
0
10
20
30 V
Vsupply
ELECTROMAGNETIC CAPABILITY9
Test conditions
Radiated, radio frequency
EN61000-4-3: 10 V/m, 80 to 1000 MHz
electromagnetic field immunity (RFI)
80 % AMC (1 kHz)
Electrical fast transient /
EN61000-4-4: ±2 kV
burst immunity (EFT)
Electrostatic discharge immunity
EN61000-4-2: ±4 kV, contact discharge
test (ESD)
±8 kV, air discharge
Immunity to conducted disturbances EN61000-4-6: 0.15 to 80 MHz
induced by radio-frequency fields
10 V, 80 % AMC (1 kHz)
Criterion Interference
A
<1 %FSO
B
<1 %FSO
B
<1 %FSO
A
<1 %FSO
Specification notes:
1. IP 67 protection for BTE(M)5...A / PTx5...A is given with locked connector only.
2. Proof pressure is the maximum pressure which may be applied without causing damage to the sensing element.
3. This is the highest pressure which can be applied to any port at any time. At the same time the differential pressure between
the ports H and L must not exceed the maximum proof pressure.
4. Non-linearity refers to the Best Straight Line fit measured for offset, full scale span and 1/2 full scale span.
5. Long term stability is the change in output after one year or 1 million pressure cycles.
6. Thermal effects tested and guaranteed from 0 - 70 °C relative to 25°. All specifications shown are relative to 25°C.
7. Full scale span is the algebraic difference between the positive full scale output and zero pressure offset.
8. Higher pressure applied to port H.
9. Test are in accordance with EN 61000-6-2.
10. CE-labelling is in accordance with 2004/108/EC.
11. The pressure transmitters must not be used as safety accessories according to article 1, 2.1.3 of the directive 97/23/EC.
12. 0...10 V square rooting output signal on special request.
E / 11101 / B
3/5
www.first-sensor.com
www.sensortechnics.com
BTE5000 / PTE5000 / PTU5000 Series
Precision differential pressure transmitters
OUTLINE DRAWING
Connector version
40.0
(1.58)
NOM 86.0 (3.39)
20.0
(0.79)
13.5 diam. (0.53)
72.0 (2.84)
H: high pressure port
L: low pressure port
mating plug
8.0 (0.31) min.
4
M12 x 1
(0.47)
9.0
(0.35)
BTE.../PTE...: 2 x 1/8" BSP
PTU...: 2 x 1/8" NPT
3
2
8.0 (0.31) min.
2 x M5
(UNC 10-24)
1
ELECTRICAL CONNECTION
mass: typ. 170 g
Pin
1
2
3
4
Connection
1-6V
4 - 20 mA
output
output
+Vs
+Vs
Vout
NC
case
case
-Vs
-Vs
dimensions in mm
(inches)
Cable version
40.0
(1.58)
90.0 (3.54)
H: high pressure port
L: low pressure port
72.0 (2.84)
20.0
(0.79)
13.5 diam. (0.53)
1 m (3.3 ft) shielded cable
4 x 0.25 mm² (AWG24)
8.0 (0.31) min.
8.0 (0.31) min.
2 x M5
(UNC 10-24)
9.0
(0.35)
BTE.../PTE...: 2 x 1/8" BSP
PTU...: 2 x 1/8" NPT
ELECTRICAL CONNECTION
mass: typ. 220 g
bare
brown
white
green
yellow
E / 11101 / B
Connection
1-6V
4 - 20 mA
output
output
case/shield case/shield
+Vs
+Vs
NC
NC
Vout
NC
-Vs
-Vs
dimensions in mm
(inches)
4/5
www.first-sensor.com
www.sensortechnics.com
BTE5000 / PTE5000 / PTU5000 Series
Precision differential pressure transmitters
RECOMMENDED CABLE/CONNECTOR ACCESSORY
for connector version
Order number ZK000101, other cable length on special request
NOM 2 m
36.5
PIN CONNECTION
Pin
1
2
3
4
NOM
60
Flying lead end
brown
green
white + shield
yellow
Included in delivery!
M12 x 1
Ø 20
ORDERING INFORMATION
BT/PT
x
(M)
5xxx
D
x
x
Calibration
BT: calibration in mbar/bar
PT: calibration in psi
Electrical connection
A: connector version
C: cable version
Pressure connection
E: 1/8" BSP female
U: 1/8" NPT female
Output signal
1: 1...6 V
4: 4...20 mA
For mbar ranges only
Differential pressure
Pressure range
BTE5000 series
0025:
0...25 mbar
P025:
-25...+25 mbar
0070:
0...70 mbar
P070:
-70...+70 mbar
0350:
0...350 mbar
P350: -350...+350 mbar
001:
0...1 bar
P01:
-1...+1 bar
002:
0...2 bar
005:
0...5 bar
010:
0...10 bar
PTE/PTU5000 series
000.3:
0...0.3 psi
001:
0...1 psi
P01:
-1...+1 psi
005:
0...5 psi
P05:
-5...+5 psi
015:
0...15 psi
P15: -15...+15 psi
030:
0...30 psi
100:
0...100 psi
150:
0...150 psi
Other pressure ranges and options are widely available. Please contact First Sensor.
First Sensor reserves the right to make changes to any products herein. First Sensor does not assume any liability arising out of the application
or use of any product or circuit described herein, neither does it convey any license under its patent rights nor the rights of others.
E / 11101 / B
5/5
www.first-sensor.com