K3MA-J - OMRON Industrial Automation

Process Meter
K3MA-J
CSM_K3MA-J_DS_E_11_2
Highly Visible LCD Display with 2-color
(Red and Green) LEDs
• Multi-range DC voltage/current input.
• Front-panel key operation for easy setting.
• Average processing function suppresses flicker.
• Scaling, front-panel forced-zero, zero-limit functions.
• Easy confirmation of max/min display.
• Short 80-mm depth (measured from edge of face plate).
• Finger protective cover (standard equipment) guards against electric
shock.
• Water- and dust-proof NEMA4X (IP66 equivalent) front panel.
• Recognized to U.S. and Canadian requirements under the Component Recognition Program of UL.
• CE marking.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Refer to Safety Precautions for All Digital Panel
Meters.
Model Number Structure
■ Model Number Legend
K3MA-J-@
1 2
3
3. Supply Voltage
100-240VAC: 100 to 240 VAC
24VAC/VDC: 24 VAC/VDC
1. Input Type
J:
DC voltage/current
2. Comparative Output Model
None: No output
A2: 2 relay contact outputs (SPST-NO)
Ordering Information
■ List of Models
Input type
DC voltage/current
Supply voltage
100 to 240 VAC
24 VAC/VDC
Comparative Output Model
None *
Model
K3MA-J 100-240VAC
2 relay contact outputs (SPST-NO)
K3MA-J-A2 100-240VAC
None *
K3MA-J 24VAC/VDC
2 relay contact outputs (SPST-NO)
K3MA-J-A2 24VAC/VDC
* Changing the display color based on comparison with a reference value is not possible.
1
K3MA-J
■ Accessories (Order Separately)
Name
Shape
Model
Splash-proof Soft Cover
K32-49SC
Hard Cover
K32-49HC
Watertight Cover
Y92A-49N
Rubber Packing
K32-P1
Note: Rubber packing is provided with the Controller.
Specifications
■ Ratings
Model
K3MA-J 100-240VAC, K3MA-J-A2 100-240VAC
K3MA-J 24VAC/VDC, K3MA-J-A2 24VAC/VDC
Supply voltage
100 to 240 VAC
24 VAC/VDC
Operating voltage range
85% to 110% of the rated supply voltage
Power consumption
(under maximum load)
6 VA max.
Insulation resistance
20 MΩ min. (at 500 VDC) between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
Dielectric strength
2,000 VAC for 1 min between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
Noise immunity
±1,500 V on power supply terminals in normal or com- ±480 V on power supply terminals in normal mode.
mon mode.
±1,500 V in common mode.
±1 μs, or 100 ns for square-wave noise with 1 ns.
±1 μs, or 100 ns for square-wave noise with 1 ns.
Vibration resistance
Vibration: 10 to 55 Hz, Acceleration: 50 m/s2
5 min each in X, Y, and Z directions for 10 sweeps.
4.5 VA max. (24 VAC)
4.5 W max. (24 VDC)
Shock resistance
150 m/s2 (100 m/s2 for relay contact outputs) 3 times each on 3 axes, 6 directions.
Ambient temperature
Operating: −10°C to 55°C (with no condensation or icing)
Storage: −25°C to 65°C (with no condensation or icing)
Ambient humidity
Operating: 25% to 85% (with no condensation)
Approved safety standards
UL61010-1, CSA C22.2 No.61010-1-04, conforms to EN61010-1 (Pollution degree 2/overvoltage category II)
Conforms to VDE0106/P100 (finger protection)
EMC
(EMI)
Emission Enclosure:
Emission AC Mains:
(EMS)
Immunity ESD:
EN61326-1
Industrial electromagnetic environment
CISPR 11 Group 1 class A: CISRP16-1/-2
CISPR 11 Group 1 class A: CISRP16-1/-2
EN61326-1
Industrial electromagnetic environment
EN61000-4-2: 4 kV contact discharge
8 kV air discharge
Immunity RF-interference:
EN61000-4-3: 10 V/m (amplitude-modulated, 80 MHz to 1 GHz)
Electrical Fast Transient Noise:
EN61000-4-4: 2 kV (power line)
Immunity Burst Noise:
1 kV line to line (I/O signal line)
Immunity Surge:
EN61000-4-5: 1 kV (power line)
2 kV line to ground (power line)
Immunity Conducted Disturbance: EN61000-4-6: 3 V (0.15 to 80 MHz)
Immunity Voltage Dip/Interrupting: EN61000-4-11: 0.5 cycle, 0, 180°, 100% (rated voltage)
Weight
Approx. 200 g
2
K3MA-J
■ Characteristics
Input signal
DC voltage/current (0 to 20 mA, 4 to 20 mA, 0 to 5 V, 1 to 5 V, ±5 V, ±10 V)
A/D conversion
Double integral method
Sampling period
250 ms
Display refresh period
Sampling period (sampling times multiplied by number of measurements for averaging if average processing is selected.)
Max. displayed digits
5 digits (−19999 to 99999)
Display
7-segment digital display, Character height: 14.2 mm
Polarity display
“−” is displayed automatically with a negative input signal.
Zero display
Leading zeros are not displayed.
Scaling function
Programmable with front-panel key inputs (range of display: −19999 to 99999). The decimal point position can be set as desired.
Hold function
Max. hold (maximum value), Min. hold (minimum value)
Hysteresis setting
Programmable with front-panel key inputs (0001 to 9999).
Other functions
Forced-zero (with front-panel key)
Zero-limit
Scaling teach function
Display color change (green (red), green, red (green), red)
OUT type change (upper limit, lower limit, upper/lower limit)
Average processing (simple average)
Output
Relays: 2 SPST-NO
Delay in comparative outputs
750 ms max.
Degree of protection
Front panel: NEMA4X for indoor use (equivalent to IP66)
Rear case: IEC standard IP20
Terminals: IEC standard IP00 + finger protection (VDE0106/100)
Memory protection
Non-volatile memory (EEPROM) (possible to rewrite 100,000 times)
■ Measuring Ranges
Process Voltage/Current Inputs
Input
Measuring range
DC voltage
1.000 to 5.000 V
0.000 to 5.000 V
–10.00 to 10.00 V
±0.1% FS ±1 digit max.
(at 23±5°C)
4.00 to 20.00 mA/
0.00 to 20.00 mA
±0.1% FS ±1 digit max.
(at 23±3°C)
–5.000 to 5.000 V
DC current
Measuring accuracy
±0.1% FS ±1 digit max.
(at 23±3°C)
Input impedance
1 MΩ min.
Displayable range
–19999 to 99999
(with scaling function)
45 Ω
■ Input/Output Ratings
Relay Contact Output
Item
Resistive load (cosφ = 1)
Inductive load (cosφ = 0.4, L/R=7 ms)
Rated load (UL ratings)
5 A at 250 VAC, 5 A at 30 VDC
1.5 A at 250 VAC, 1.5 A at 30 VDC
Max. contact voltage
250 VAC, 150 VDC
1,250 VA, 150 W
250 VA, 30 W
Max. switching capacity
Min. permissible load
(P level, reference value)
10 mA at 5 VDC
Mechanical life
5,000,000 times min. (at a switching frequency of 1,200 times/min)
Electrical life
(at an ambient temperature of 20°C)
100,000 times min. (at a rated load switching frequency of 10 times/min)
3
K3MA-J
Connections
■ Terminal Arrangement
Power
supply
A1
Output
terminals
A2
100- to 240-VAC
type or 24-VAC/
VDC type
(No polarity for
24-VDC
connection.)
Input
terminals
Models with
comparative
output
E1
E2
OUT1
OUT2
E3
E4
E4
Voltage input
E5
E5
COM
E6
For voltage input
Terminal No.
Name
A1 - A2
E4 , E6 - E5
E1 , E2 - E3
COM
Current input
E6
For current input
Description
Operation power
Connects the operation power supply.
Analog input
Connects the voltage or current analog input.
Outputs
Outputs the relay outputs.
■ Block Diagram
Input
Key
Input circuit
Microcomputer
EEPROM
Display
Output
circuit
5V
X
Contact output
(See note.)
12 V
Constant voltage circuit
Power supply circuit
Note: Relay output models only.
■ Input Circuits
Analog Input (DC Voltage/Current)
−
A
Voltage input 4
COM 5
−
To A/D
Current input 6
+
To A/D
+
45 Ω
B
A+B=1 MΩ
COM 5
4
K3MA-J
Operation
■ Main Functions
Input Types and Ranges
Input type (setting parameter)
Input range (in-t)
Function
Input range
(setting parameters)
Selects DC voltage/current signal
input
Setting range
0 to 20 mA
(0-20)
4 to 20 mA
(4-20)
0 to 5 V
(0-5)
1 to 5 V
(1-5)
±5 V
(5)
±10 V
(10)
Displayable from −19999 to 99999
with scaling function.
The position of the decimal point
can be set as desired.
Note: The initial value for the input range is “4 to 20 mA (4-20).”
Scaling
• Analog (Process) Inputs
The K3MA-J converts input signals into desired physical values.
INPUT2:
DISPLAY2:
INPUT1:
DISPLAY1:
Any input value
Displayed value corresponding to INPUT2
Any input value
Displayed value corresponding to INPUT1
When DISPLAY1 is set for INPUT1, and DISPLAY2 is set for INPUT2, a line will be displayed joining the two points. (Raise shift, reverse scaling,
plus/minus display, etc., can be adjusted as desired.)
Parameter
Setting value
inp.1
-19999 to 99999
Meaning
Parameter
Input value for dsp.1
dp
Setting value
%.%%%%
Meaning
Display four digits after decimal point
dsp.1
-19999 to 99999
Input value for inp.1
%%.%%%
Display three digits after decimal point
inp.2
-19999 to 99999
Input value for dsp.2
%%%.%%
Display two digits after decimal point
dsp.2
-19999 to 99999
Input value for inp.2
%%%%.%
Display one digit after decimal point
%%%%%
No decimal point
Display value
DISPLAY 2
(
)
DISPLAY 1
(
)
Display value
DISPLAY 1
(
)
Reverse scaling also possible.
The decimal point can be optionally displayed.
When displaying the decimal point, consider the
number of digits to follow the decimal point prior to
setting the scaling display value.
DISPLAY 2
(
)
INPUT 1 INPUT 2 Input value
(
) (
)
(
INPUT 1
)
INPUT 2
Input value
(
)
Reverse scaling, where the display value decreases as
the input value increases, is also possible.
Teaching with actual values is possible.
Instead of setting by inputting with the
Up Key and
Shift Key, current values can be
input as scaling input values for teaching. This is useful for making settings while checking the
operation status of the K3MA-J.
5
K3MA-J
Convenient Functions
Scaling Teach
The parameters (inp.1, inp.2) for the K3MA-J’s initial setting level can be set using actual input values with the teaching function. After displaying
the parameters, the actual input settings can be made with the following operation.
Teaching mode
Use
to shift to
the next parameter
without registering.
“T” flashes.
Monitor mode
Use
to register
and shift to monitor
mode.
Normal change
“T” lights to
indicate that the
parameter is
valid for teaching.
“T” turns OFF.
Next parameter
OUT Types (Comparative Output Models Only)
OUT 1 and OUT 2 can be set to operate in one of the three following modes in accordance with the compared values:
• Upper limit (High Acting):
The output is turned ON when the measurement value is greater than its set value.
• Lower limit (Low Acting):
The output is turned ON when the measurement value is less than its set value.
• Upper and lower limits (Outside Band Acting):
An upper limit (H set value) and lower limit (L set value) can be set independently.
The output is turned ON when the measurement value is greater than upper-limit set value or less than the lower-limit set value.
Upper Limit (High Acting)
OUT1/2 value
Lower Limit (Low Acting)
OUT1/2 upper-limit value
Hysteresis
Measurement value
Measurement value
ON
Output
OFF
Hysteresis
Measurement value
Hysteresis
OUT1/2 value
Output
Upper and Lower Limits
(Outside Band Acting)
Hysteresis
OUT1/2 lower-limit value
ON
Output
OFF
ON
OFF
The three types of output operations shown above can be combined as desired. The following are examples of possible combinations.
Upper Limit 2-stage Output
OUT2
value
Measurement
value
OUT1
value
Threshold Output
OUT2 upper-limit
value
OUT1 upper-limit
value
OUT1 lower-limit
value
OUT2 lower-limit
value
Measurement
value
Combination of Upper Limit and
Upper/Lower Limits
OUT2 Upper-limit
value
OUT1 value
Measurement
value
OUT2 Lower-limit
value
ON
OUT2 OFF
OUT2
ON
OFF
ON
OUT2 OFF
ON
OUT1 OFF
OUT1
ON
OFF
ON
OUT1 OFF
6
K3MA-J
Parameter Initialization
Changing the Display Color
This function returns all of the parameters to their initial values.
The color of the value displayed can be set to either red or green. For
comparative output models (K3MA-J-A2), the display color can be
set to change from green to red, or from red to green, according to
the status of the comparison criterion.
Parameter
Setting value
init
Meaning
off
---
on
Initializes all parameters.
Use this to reset the K3MA-J after returning it to its factory-set condition.
Red
113.36
OUT1 value
Green
100.05
Average Processing
OUT2 value
Average processing stabilizes displayed values to minimize flicker by
averaging the fluctuating input signals. Average processing can be
performed for the measurement values in either of four steps (OFF, 2
times, 4 times, or 8 times).
8.781
Red
Display Auto-return Time
This function automatically returns the display to the operation level’s
current value if no keys are pressed for a preset time (called the display auto-return time).
This is useful for ignoring rapid fluctuations, e.g., eliminating spike
noise.
Hysteresis (Comparative Output
Models Only)
The hysteresis of comparative outputs can be set to prevent chattering in the output when the measurement value fluctuates finely near
the OUT value.
Move-to-Protect-Level Time
The time required to shift to the protect level can be set as desired.
Forced-zero Function
It is possible to shift from a value to the zero point with one touch of
the Up Key on the front panel (for example, when adjusting reference
values).
Upper limit (high acting)
Set value
MAX/MIN
Hysteresis
LEVEL
MODE
SHIFT
UP
Measurement value
Note: Used only for releasing the forced-zero with the Protect menu.
MAX/MIN Display
ON
Output
The maximum and minimum measurement (display) values from the
time the power is turned ON until the current time can be stored and
displayed. This is useful, for example, when measuring the maximum
value.
OFF
Zero-limit Function
The zero-limit function changes any value below the set value to
zero. This is useful when you want to change negative values to zero
rather than display them, or when you want to make the display in the
smallest part of the input range zero.
Current value
MAX/MIN
MAX/MIN
Parameter
Setting value
LEVEL
MODE
SHIFT
UP
Meaning
=-lim
off
OFF: No zero-limit
on
ON: Zero-limit
lim-p
0 to 99
0 to 99: Zero-limit value
MAX value
Max
MAX/MIN
MAX/MIN
LEVEL
MODE
SHIFT
UP
Display
MIN value
Min
MAX/MIN
MAX/MIN
LEVEL
MODE
SHIFT
UP
Zero-limit
setting value
Input
7
K3MA-J
Nomenclature
2. Operation indicators
1
2
Max
Min
1. Main indicator
SV
3. Level indicator
Z
T
MAX/MIN
LEVEL
MODE
SHIFT
UP
4. MAX/MIN key
8. Up key
5. Level key
7. Shift key
6. Mode key
Name
Functions
1. Main indicator
Displays current values, parameters, and set values.
2. Opera- 1
tion indica- 2
tors
SV
Lit when output 1 is ON.
Lit when output 2 is ON.
Lit when a set value is being displayed or changed.
Max
Lit when the main indicator is showing the MAX value.
Min
Lit when the main indicator is showing the MIN value.
Z
Lit during the forced-zero operation.
T
Lit when the teaching function is operable. Blinks while the teaching function is operating.
3. Level indicator
Displays the current level that the K3MA-J is in. (See below for details.)
4. MAX/MIN Key
Used to display the MAX and MIN values when a measurement value is being displayed.
5. Level Key
Used to change the level.
6. Mode Key
Used to allow the main indicator to indicate parameters sequentially.
7. Shift Key
Used to enable a set value to be changed. When changing a set value, this key is used to move along the digits.
8. Up Key
Used to change a set value. Used to set or clear a forced-zero function when a measurement value is being displayed.
Level indicator
Level
p
Protect
Not lit
Operation
s
f
Initial setting
Advanced-function setting
Dimensions
Finger protective
cover (provided)
101.2
91
Main indicator
character size
Panel cut-out
120 min.
A
14.2 mm
B
C
D
E
85
97
75 min.
7.6 mm
0
92+0.5
+0.5
45 0
12
1.3
80
96
44.8
48
MAX/MIN
LEVEL
MODE
SHIFT
Mounting Recommended Panel Thickness
1 to 8 mm.
Mount the product horizontally.
The K3MA-J uses M3 terminals.
UP
8
K3MA-J
Application Examples
Monitoring interior
tank pressure
E8AA Pressure Sensor
Displaying/outputting
liquid level
Pa
4 to 20 mA
K3MA-J
Pump
4 to 20 mA
or 0 to 10 V
Flowrate sensor
m/min
mm
K3MA-J
E4PA Ultrasonic Displacement
Sensor
4 to 20 mA
K3MA-J
Pump
Tank
Flowrate Sensor
Discharge valve
• Monitoring gas pressure
• Inspection instruments in food or pharmaceutical plants
• Monitoring liquid level in cleaning tanks
• Water tanks, devices using chemicals,
etc.
• Monitoring send-out flowrate
• Water processing devices, etc.
Installation
1. Insert the K3MA-J into the panel cut-out hole.
2. For a waterproof installation, insert the rubber gasket onto the
body of the K3MA-J.
■ Rubber Packing
K32-P1
If the rubber packing is lost or damaged, it can
be ordered using the following model number:
K32-P1.
(Depending on the operating environment, deterioration, contraction, or hardening of the rubber
packing may occur and so, in order to ensure
the level of waterproofing specified in NEMA4,
periodic replacement is recommended.)
Note: Rubber packing is provided with the
Controller.
3. Fit the adaptor into the grooves on the left and right sides of the
rear case, then push it until it contacts the panel to secure the
K3MA-J.
■ Wiring Precautions
• Use crimp terminals.
• Tighten the terminal screws to a torque of approximately 0.5 N⋅m.
• To avoid the influence of noise, route signal lines and power lines
separately.
■ Wiring
• Use the following M3 crimp terminals.
5.8 mm max.
■ Angle of View
The K3MA is designed to provide the best visibility at the angles
shown in the following diagram.
5.8 mm max.
■ Unit Labels (Provided)
• The unit labels are not attached to the K3MA-J. Select the desired
labels from the provided sheet.
10°
30°
■ Watertight Cover
Y92A-49N
Note: For scales and gauges, use the unit labels that are specified by
the relevant laws or regulations.
9
K3MA-J
Operating Procedures
■ Operations in Run Mode
Setting and Releasing a
Forced Zero
Checking the Maximum and Minimum Values
The maximum and minimum values can be displayed by pressing the MAX/MIN Key while
the measurement is being displayed.
Setting a Forced Zero
Any reference point can be easily set to zero.
Measurement
value
Displayed value
MAX/MIN Key
MIN value
MAX/MIN Key
Measured value
after setting
forced zero
Checking and Setting Comparative Set Values (for
Models with the Comparative Output Function)
ON
Each time the Mode Key is pressed when the measurement value, maximum value, or
minimum value is displayed, the comparative values will be displayed in the following
order: OUT1 value (or OUT1 upper-limit value, OUT1 lower-limit 1), OUT 2 value (or OUT
2 upper-limit value, OUT2 lower-limit value 2).
Forced zero input
OFF
MAX value
The maximum and minimum values can be reset by pressing the MIN/MAX Key for 1 s
min. when the maximum or minimum value is displayed.
Measured value
Z indicator
MAX/MIN Key
• Press the Up Key while the measurement is
being displayed. The displayed value will be
shifted to 0 and measurement will be
continued.
If forced-zero protection is turned ON in the
protect level, the Up Key cannot be used to
set a forced zero. Forced-zero protection is
ON in the default settings.
• The Z indicator will light when a forced zero
has been set.
• The shifted measurement value after a forced
zero has been set will be maintained even
after power is turned OFF.
OUT1 value
Measurement
value
MAX value
MIN value
OUT1
upper-limit
value
Mode Key
OUT2 value
OUT1
lower-limit
value
Mode Key
OUT2
upper-limit
value
Mode Key
OUT2
lower-limit
value
Mode Key
Mode Key
Note: When a comparative value is displayed, it can be changed by pressing the Shift Key
and the Up Key (when key protection is OFF).
Releasing a Forced Zero
• Press the Up Key for 1 s min. to release the
forced zero. The Z indicator will turn OFF.
■ Levels
“Level” refers to a grouping of parameters. The following table lists the operations that are possible in each of the levels, and the diagram tells how
to move between levels. There are some parameters that are not displayed for certain models.
Level name
Function
Measurement
Protect
Setting lockouts.
Continue
Operation
Displaying current values, setting/clearing forced-zero function, and Continue
setting OUT 1/2 values.
Initial setting
Making initial settings of input type, scaling, output operating action, Stopped
and other parameters.
Advanced-function setting
Setting average processing, display color settings, and other advanced-function parameters.
Stopped
10
K3MA-J
Power ON
Operation level
+
Time set
by user
(See note.)
1 s min.
Protect level
Flashing stops if key
is released.
1 s min.
+
1 s min.
-1234.5
Indicates change of level.
Continue to press the key for 2 s min.
Initial setting level
Password "-0169"
1 s min.
Advanced-function
setting level
Note: The move-to-protect-level time can be set in the advanced-function setting level.
11
K3MA-J
■ Parameters
Some parameters are not displayed for certain models.
The K3MA-J will stop measurement if the level is changed to the initial setting level or
advanced-function setting level.
the input range is changed, some parameters are set to default values. Therefore,
et the input range first.
Settings displayed in reversed colors are defaults.
Power ON
Operation level
Current value
For models with the
comparative output
function
MODE
OUT1 value
−
MODE
Set one of these.
OUT1
upper-limit
value
−
MODE
OUT1
lower-limit
value
−
MODE
OUT2 value
−
MODE
Set one of these.
OUT2
upper-limit
value
−
MODE
OUT2
lower-limit
value
−
MODE
12
K3MA-J
To change a setting, press the Shift Key
make the change with the Up Key
.
Press Level
Key
for
more than 3 s.
Press Level Key
again, and then
for more than 1 s.
Advanced-function
setting level
Initial setting level
Press Level
Key
for
more than 1 s.
/
Input type
/
/ /
Enter
password
"-0169"
MODE
Parameter
initialization
/
Average
processing
/
MODE
Scaling
input value 1
−
/ /
Unit: times
MODE
MODE
Scaling
display
value 1
−
Scaling
input value 2
−
Models with
the comparative
output
function
MODE
OUT1
hysteresis
OUT2
hysteresis
−
Decimal
point
position
−
−
−
−
MODE
MODE
Scaling
display
value 2
−
MODE
Zero-limit
MODE
Zero-limit
/
MODE
MODE
OUT1
type
Upper Limit
OUT2
type
Upper Limit
MODE
MODE
Move to
advancedfunction
MODE setting level
Zero-limit
value
When zerolimit is ON
Lower Limit
Upper/Lower
Limits
−
MODE
Display
color
change
Lower Limit
Upper/Lower
Limits
Green (red)
Green
Red (green)
MODE
Red
−
−
Display
auto-return
time
−
−
Unit: s
MODE
Move-toprotectlevel time
MODE
−
−
Unit: s
13
K3MA-J
Press
Level Key +
Mode Key for more than 1 s.
Operation level
Protect level
Press
Level Key +
for more than preset time.
Mode Key
Operation/adjustment
lockouts
/ /
MODE
Setting level lockout
/
/
MODE
Setting change lockout
/
MODE
Forced-zero shift
lockout
/
MODE
Operation/Adjustment Lockouts
■ Initial Settings
Restricts key operations for operation level and adjustment level.
Parameter
Setting
Power ON
Operation level
Current value display Set value display
oapt
0
Allowed
Allowed
1
Allowed
Allowed
2
Allowed
Prohibited
• Initial setting is 0.
• This cannot be displayed on models not equipped with the comparative output function.
Press the Level Key
level.
for 3 s min. to move to the initial setting
Select the input type.
Set the scaling values and specify output operating action as
required.
Setting Level Lockout
Restricts shifting to initial setting level or advanced-function setting
level.
Parameter Setting
icpt
Shift to initial
setting level
Shift to advancedfunction setting level
0
Allowed
1
Allowed
Prohibited
2
Prohibited
Prohibited
Allowed
Setting Change Lockout
If required, shift to the advanced-function setting level to set
the number of measurements for averaging, hysteresis
values, auto-zero limit value, display color change, display
auto-return time, or move-to-protect-level time.
Press the Level Key
operation level.
for less than 1 s min. to return to the
Restricts setting changes by key operation. When this lockout is set,
it is no longer possible to shift to a setting change mode.
Parameter
wtpt
Setting
Setting change by key
operation
off
Allowed
on
Prohibited
However, all protect level parameters can still be changed.
Specify set value of OUT 1 and 2.
Measurement starts.
Forced-zero Lockout
Restricts the setting or release of a forced-zero by front-panel key
operation.
Parameter
=rpt
Setting
Setting/release of forced-zero
by key operation
off
Allowed
on
Prohibited
14
K3MA-J
■ Setting Example
Initial Settings
Display value
DISPLAY 2
(
)
The settings for the following example are shown here.
Example: Tank pressure display
4 to 20 mA
1
0 to 980 kPa
2
DISPLAY 1
(
)
Max
Min
SV
Pressure Sensor
MAX/MIN
LEVEL
MODE
SHIFT
Input value
UP
INPUT 1
(
)
K3MA-J-A2 24VAC/VDC
Here, the pressure inside the tank is to be displayed in units of 0.1
kPa.
• Pressure Sensor
Measuring range: 0 to 980 kPa, output 4 to 20 mA
INPUT 2
(
)
1. Set the K3MA-J input type to the 4 to 20 mA input range.
Parameter: in-t (input type), Setting value: 4-20
2. Set the display values for the corresponding input values.
Set the scaling as shown below for the following correspondence:
input 4 mA-->display 0.0, input 20 mA-->display 980.0
Parameter
Setting value
inp.1 (scaling input value 1)
4.00
dsp.1 (scaling display value 1)
00000
inp.2 (scaling input value 2)
20.00
dsp.2 (scaling display value 2)
09800
dp (decimal point position)
%%%%.%
Note: The decimal point position here refers to the position in the
number after scaling. When setting the scaling display value, it
is necessary to consider the number of digits to be displayed
past the decimal point.
■ Troubleshooting
When an error occurs, error details will be displayed on the main indicator. Confirm the error from the main indicator and take the appropriate countermeasures.
Level
display
Main indicator
Error contents
Countermeasures
Not lit
e111
RAM memory error
Repair is necessary.
Consult your OMRON sales representative.
5
e111
EEPROM memory error
When this error is displayed, press the Level Key for 3 seconds, and the settings will be restored to the factory settings.
If the error cannot be recovered, repair is necessary. Consult your OMRON sales representative.
Not lit
Flashes s.err
You will see this indication when turning ON the At the initial setting level, set the input type and other paproduct the first time after purchase. This is be- rameters according to your application.
cause the input signal value is 0 mA at that time
even though the range is factory set to 4 to 20 mA.
For the K3MA-J-A2, the relay output will be OFF.
Not lit
Flashes 99999
Input error
Promptly change the input voltage/current to a value that
falls within the measurement range.
If the error cannot be recovered, repair is necessary. Consult your OMRON sales representative.
The scaling display value exceeds 99999.
Promptly change the input to a value that falls within the
specified range.
The scaling value may be inappropriate. Review the scaling value at the initial setting level.
Not lit
Flashes -19999
The scaling display value is lower than −19999.
Promptly change the input to a value that falls within the
specified range.
The scaling value may be inappropriate. Review the scaling value at the initial setting level.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
15
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2015.8