E5AN-HT/E5EN-HT

Programmable Temperature Controller (Digital Controller)
E5AN-HT/E5EN-HT
(96 x 96 mm and 48 x 96 mm)
CSM_E5AN-HT_E5EN-HT_DS_J_1_7
Programmable Controllers Join the Series!
Program up to 256 segments and take advantage of the high cost performance
of the new LCD that improves both the field of view and contrast.
• Set up to 8 programmed patterns with up to 32 segments (steps) each.
• High-resolution display with 5 digits/0.01°C display.
• High-speed sampling cycle of 60 ms.
• High Accuracy
Thermocouple/Pt input: ±0.1% of PV
Analog input: ±0.1% FS
• Universal inputs on all models (thermocouple, PT, or analog
input) to handle various sensors with one Controller. Models
also available with Remote SP.
• A PV/SV-status display function can be set to automatically alternate
between displaying the status of the Temperature Controller (auto/
manual, RUN/RESET, and alarms) and the PV or SV.
• Flexible contact outputs with logic operations (AND, OR, and
delays) set from the Support Software (CX-Thermo version
4.3). Program settings can be managed.
• An infrared ports enables communications from the front panel.
• Preventive maintenance for relays in the Temperature
Controller using a Control Output ON/OFF Counter.
• Model available with position-proportional control
96 × 96 mm
E5AN-HT
48 × 96 mm
E5EN-HT
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Refer to Safety Precautions for E5@N/E5@N-H/
E5@N-HT.
Refer to Operation for E5@N/E5@N-H/E5@N-HT for
operating procedures.
Main I/O Functions
Remote SP Input
• One
E5AN-HT
E5EN-HT
Three displays
for simultaneous display
of the PV, SV, program, and segment.
Event Inputs
• None
• Two
• Four
Universal Sensor Inputs
• Universal thermocouple/
Pt/analog
(current/voltage) inputs.
Indication Accuracy
• Thermocouple/Pt input:
±0.1% of PV
• Analog input:
±0.1% FS
Sampling Period
• 60 ms
PF Key
(Programmable
key function)
5-digit Display with high resolution of 0.01°C
Auxiliary Outputs
• Two
• Three
Infrared port
USB
Computer Support Software
CX-Thermo
Control Output 2
Output Unit
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
• Programmable function
8 programs × 32
segments
• Auto/manual switching
• Temperature Controller
status display
• Simple program
function
• Logic operations
• Control output ON/OFF
count alarm
• PV change rate alarm
• Models available with
RS-485, RS-422, or
RS-232C
communications
Control Output 1
Output Unit
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
1
E5AN-HT/E5EN-HT
Lineup
E5AN-HT/E5EN-HT
Programmable Type
Terminal block
1 control output
2 auxiliary outputs
2 control outputs
2 auxiliary outputs
Fully universal input
Note: The Controller can be used for heating/cooling control even if only 1 control output is used.
Model Number Structure
Model Number Legend
Controllers
Option Units
E5AN/E5EN-@@@@@@@M@-@-500
1 2 3 4 5 6 7 8 9 10
11
1. Type
HT: Programmable
2. Control Mode
Blank: Standard or heating/cooling control
P: Position-proportional control
3. Control Output 1
A: Control Output Unit
R: Relay output
4. Control Output 2
A: Control Output Unit
R: Relay output
5. Auxiliary Outputs
2: Two outputs
3: Three outputs
6. Option 1
Blank: None
H: Heater burnout/SSR failure/Heater overcurrent detection (CT1)
HH: Heater burnout/SSR failure/Heater overcurrent detection
(CT2)
7. Option 2
B: Two event inputs
BF: Event input + Transfer output
E53-@
1
1. Function
EN01: RS-232C communications
EN02: RS-422 communications
EN03: RS-485 communications
AKB: Event input
Output Units
E53-@@
1 2
1. Control Output
R: Relay output
Q: Voltage output (for driving SSR)
Q3: Voltage output (for driving SSR) + 24 VDC (NPN)
Q4: Voltage output (for driving SSR) + 24 VDC (PNP)
C3: Current output + 4 to 20 mA DC
C3D: Current output + 0 to 20 mA DC
V34: Linear voltage output + 0 to 10 VDC
V35: Linear voltage output + 0 to 5 VDC
2. Version
Blank: Available for E5AN-H/E5EN-H/E5AN-HT/E5EN-HT.
N: Available only for E5AN-H/E5EN-H and E5AN-HT/E5EN-HT.
8. Option 3
M: Option Unit can be mounted.
9. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
10.Case Color
Blank: Black
11.Terminal Cover
-500: With Terminal Cover
Note: Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON representative for details.
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN-HT/E5AN-HT/E5EN-HT Digital Controllers User's Manual Programmable Type (Cat. No. H169)
E5CN-HT/E5AN-HT/E5EN-HT Digital Controllers Communications Manual Programmable Type (Cat. No. H170)
2
E5AN-HT/E5EN-HT
Ordering Information
E5AN-HT
Size
Case
color
Power
supply
voltage
Control Auxiliary
method
output
Control output 1/2
Heater
burnout
Optional functions
Event
inputs
100 to
240 VAC
3
Valve
4 to 20-mA
E5AN-HTAA2HBM-500
input
2
Control Output Unit × 2
2
2
4 to 20-mA 4 to 20-mA
E5AN-HTAA2HHBFM-500
output
input
Control Output Unit × 2
2
4 to 20-mA 4 to 20-mA
E5AN-HTAA3BFM-500
output
input
Relay outputs × 2
2
4 to 20-mA
E5AN-HTPRR2BM-500
input
Relay outputs × 2
2
4 to 20-mA 4 to 20-mA
E5AN-HTPRR2BFM-500
output
input
4 to 20-mA
E5AN-HTAA2HBMD-500
input
Control Output Unit × 2
1
2
Control Output Unit × 2
2
2
4 to 20-mA 4 to 20-mA
E5AN-HTAA2HHBFMD-500
output
input
Control Output Unit × 2
2
4 to 20-mA 4 to 20-mA
E5AN-HTAA3BFMD-500
output
input
Relay outputs × 2
2
4 to 20-mA
E5AN-HTPRR2BMD-500
input
Relay outputs × 2
2
2
Basic
24 VAC/
VDC
3
Valve
Model
1
2
1/4 DIN
96 × 96 × 78 Black
(W × H × D)
RSP
Control Output Unit × 2
2
Basic
Transfer
output
2
4 to 20-mA 4 to 20-mA
E5AN-HTPRR2BFMD-500
output
input
E5EN-HT
Size
Case
color
Power supply
voltage
Control
method
Auxiliary
output
Control output 1/2
Optional Functions
Heater
burn- Event
Transfer
RSP
out
inputs
output
3
100 to 240 VAC
Valve
1
2
Control Output Unit × 2
2
2
4 to 20-mA 4 to 20-mA
E5EN-HTAA2HHBFM-500
output
input
Control Output Unit × 2
2
4 to 20-mA 4 to 20-mA
E5EN-HTAA3BFM-500
output
input
Relay outputs × 2
2
4 to 20-mA
E5EN-HTPRR2BM-500
input
Relay outputs × 2
2
4 to 20-mA 4 to 20-mA
E5EN-HTPRR2BFM-500
output
input
4 to 20-mA
E5EN-HTAA2HBMD-500
input
2
1/8 DIN
48 × 96 × 78 Black
(W × H × D)
Control Output Unit × 2
1
2
Control Output Unit × 2
2
2
4 to 20-mA 4 to 20-mA E5EN-HTAA2HHBFMDoutput
input
500
Control Output Unit × 2
2
4 to 20-mA 4 to 20-mA
E5EN-HTAA3BFMD-500
output
input
Relay outputs × 2
2
4 to 20-mA
E5EN-HTPRR2BMD-500
input
Relay outputs × 2
2
2
Basic
24 VAC/VDC
3
Valve
4 to 20-mA
E5EN-HTAA2HBM-500
input
Control Output Unit × 2
2
Basic
Model
2
4 to 20-mA 4 to 20-mA
E5EN-HTPRR2BFMD-500
output
input
3
E5AN-HT/E5EN-HT
Accessories (Order Separately)
Output unit
Relay
output
Voltage
output
(for driving
SSR)
Current
output
Linear
voltage
output
Model
Specifications
E53-RN
SPST-NO, 250 VAC, 5 A (resistive load),
electrical life: 100,000 operations
E53-QN
12 VDC (PNP), max. load current:
40-mA, with short-circuit protection
E53-Q3
24 VDC (NPN), max. load current:
20-mA, with short-circuit protection
E53-Q4
24 VDC (PNP), max. load current:
20-mA, with short-circuit protection
E53-C3N
4 to 20-mA DC, load: 600 Ω max.,
resolution: approx. 10,000
E53-C3DN
0 to 20-mA DC, load: 600 Ω max.,
resolution: approx. 10,000
E53-V34N
0 to 10 VDC, load: 1 kΩ min., resolution:
approx. 10,000
E53-V35N
0 to 5 VDC, load: 1 kΩ min., resolution:
approx. 10,000
USB-infrared Conversion Cable
Model
E58-CIFIR
USB-Serial Conversion Cable
Model
E58-CIFQ1
Terminal Cover
Connectable models
Model
E5AN-HT
E53-COV16
E5EN-HT
Note: The Terminal Cover comes with the E5AN/E5EN-@@@-500 models.
Waterproof Packing
Connectable models
Model
E5AN-HT
Y92S-P4
E5EN-HT
Y92S-P5
Note: The Waterproof Packing is included with the Controller.
Current Transformers (CTs)
Hole diameter
Model
5.8 dia.
E54-CT1
12.0 dia.
E54-CT3
CX-Thermo Support Software
Model
EST2-2C-MV4
4
E5AN-HT/E5EN-HT
Specifications
Ratings
Power supply voltage
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range
85% to 110% of rated supply voltage
Power consumption
100 to 240 VAC: 12 VA
24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC)
Sensor input
Any of the following can be selected.
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Input impedance
Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.)
Control method
ON/OFF control or 2-PID control (with auto-tuning)
Relay output
Voltage output
(for driving SSR)
Control
output
Auxiliary
output
Event
input
Output Unit (Install the Output Unit (sold separately).)
Current output
Linear voltage output
Relay output for
position-proportional
control
Relay output: Open and close: SPST-NO, 250 VAC, 1 A (including in-rush current), electrical life: 100,000 operations min.
Potentiometer input: Must be between 100 Ω and 2.5 kΩ for maximum open position.
Number of outputs
2 or 3 max.
Output specifications
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V,
10 mA
Number of outputs
2 or 4 (with an E53-AKB)
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
External contact input
specifications
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Number of operations
8 max.
Operations
• Logic operation: Any of the following four patterns can be selected. The input status may be inverted.
(A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D
(A, B, C, and D are four inputs.)
• Delay:
ON delay or OFF delay for the results of the logic operation given above.
Setting time: 0 to 9999 s or 0 to 9999 min
• Output inversion: Possible
Output
One work bit per operation
Work bit
assignment
Any of The following can be assigned to up to eight work bits (logic operation results): operation commands (assigned to event
inputs) *, auxiliary outputs, or control outputs.
* Application is possible with models that do not have event inputs by using an internal assignment.
Number of outputs
1 max. (Depends on model. Models with transfer output (F in model number)
Output specifications
Current output: 4 to 20 mA DC, Load: 600 Ω max., Resolution at 4 to 20 mA: Approx. 10,000
Number of inputs
1
Signal type
Current input: 4 to 20 mA (input impedance: 150 Ω ±10%)
Analog input scaling
Scaling of signal to engineering units (EU)
−19,999 to 30,000 (display: 30,000 max.)
Accuracy
(±0.2% of FS) ±1 digit max.
Input sampling period
60 ms
Current flow: Approx. 7 mA per contact
Logic
operations
Transfer
outputs
RSP
input
Setting method
Set digitally using keys on the front panel or by using the RSP input.
Indication method
11-segment digital display and individual indicators (7-segments displays also possible)
Character height: E5AN-HT: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN-HT: PV: 11.8 mm, SV: 8.1 mm, MV: 5.8 mm
Three displays: PV/SV/Program number/Segment number, PV/SV/MV, or PV/SV/Remaining segment time.
Number of digits: 5 for PV and SV, 4 for MV
Other functions
Manual output, heating/cooling control, loop burnout alarm, other alarm functions, heater burnout detection (including SSR
failure and heater overcurrent detection), 40% AT, 100% AT, MV limiter, input digital filter, temperature input shift, run/reset,
protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display,
automatic cooling coefficient adjustment, program control functions, etc.
Ambient operating temperature
−10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C
Ambient operating humidity
25% to 85%
Storage temperature
−25 to 65°C (with no condensation or icing)
5
E5AN-HT/E5EN-HT
Input Ranges
Thermocouple/Platinum Resistance Thermometer/Analog Input (Fully Universal Inputs)
Input
type
Platinum resistance
thermometer
Name
Pt100
Thermocouple
JPt100
K
J
T
E
Analog input
L
U
N
R
S
B
W
PL
II
4 to
20 m
A
0 to
20 m
A
1 to
5V
0 to
5V
0 to
10 V
2300.0
2300
1800.0
1800
1700.01700.0
1700
1600
1500
Temperature range (°C)
1400
1300.0
1300
1300.0
1300.0
1200
1100
1000
900
850.0
850.0
Usable in the following
ranges by scaling:
−19999 to 32400,
−1999.9 to 3240.0,
−199.99 to 324.00, or
−19.999 to 32.400
850.0
800
700
600.0
600
500.0
500
500.0
500.0
400.0
400
300
200.00
200
100
Setting
number
100.0
0.0
0.0
200.00
400.0 400.0
200.00
100.0
0
−100.0
−200.0
200.00
100.0
400.0 400.0
−50.00
−200.0−199.9
0
1
−20.0 −50.00−100.0 −20.0 −50.00
−199.9
2
24
3
−200.0
4
5
−50.00
−200.0−199.9
6
21
7
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
8
22
9
10
0.0
16
17
0.0
0.0
19
20
−100.0
−200.0
23
0.0
11
−200.0−199.9−200.0
12
13
14
15
18
25
26
27
28
29
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
PL II: According to Platinel II electromotive force charts from BASF (previously
Engelhard)
6
E5AN-HT/E5EN-HT
Alarm Outputs
Each alarm can be independently set to one of the following 15 alarm types. The default is 2: Upper limit.
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the
following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR
failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).
Alarm output operation
Set value
Alarm type
0
Alarm function OFF
1
Upper- and lower-limit *1
ON
OFF
Upper-limit
ON
OFF
2
3
Output OFF
5
6
Upper- and lower-limit range *1
ON
OFF
Upper- and lower-limit with
standby sequence *1
ON
OFF
Lower-limit with standby sequence
8
9
11
Absolute-value upper-limit with
standby sequence
ON
OFF
Absolute-value lower-limit with
standby sequence
ON
OFF
ON
OFF
X
ON
OFF
SP
H
SP
L
X
Set the upward deviation in the set point by setting
the alarm value (X).
SP
X
Set the downward deviation in the set point by setting
the alarm value (X).
SP
*3
Set the deviation in the set point by setting the alarm
upper limit (H) and alarm lower limit (L).
*4
A standby sequence is added to the upper- and
lower-limit alarm (1). *7
H
SP
X
ON
OFF
SP
X
ON
OFF
ON
OFF
Absolute-value lower-limit
10
X
L
Set the deviation in the set point by setting the alarm
upper limit (H) and alarm lower limit (L).
*2
SP
ON
OFF
ON
OFF
Absolute-value upper-limit
No alarm
H
SP
*5
Upper-limit with standby sequence
7
L
ON
OFF
Lower-limit
4
Description of function
When alarm value When alarm value
X is positive
X is negative
ON
OFF
SP
X
ON
OFF
0
X
ON
OFF
0
X
ON
OFF
0
X
ON
OFF
0
X
A standby sequence is added to the upper-limit alarm
(2). *7
SP
X
A standby sequence is added to the lower-limit alarm
(3). *7
SP
X
0
The alarm will turn ON if the process value is larger
than the alarm value (X) regardless of the set point.
0
The alarm will turn ON if the process value is smaller
than the alarm value (X) regardless of the set point.
0
A standby sequence is added to the absolute-value
upper-limit alarm (8). *7
0
A standby sequence is added to the absolute-value
lower-limit alarm (9). *7
X
X
X
12
LBA (alarm 1 type only)
---
*8
13
PV change rate alarm
---
*9
14
RSP absolute value upper limit *6
ON
OFF
RSP absolute value lower limit *6
ON
OFF
15
X
0
X
0
*1. With set values 1, 4 and 5, the upper and lower limit values can
be set independently for each alarm type, and are expressed as
“L” and “H.”
*2. Set value: 1, Upper- and lower-limit alarm
Case 2
Case 1
Case 3 (Always ON)
H < 0, L < 0
L
H SP
H < 0, L > 0
⏐H⏐ < ⏐L⏐
H
SP L H
H > 0, L < 0
⏐H⏐ > ⏐L⏐
H
SP
L
H < 0, L > 0
⏐H⏐ ≥ ⏐L⏐
L SP
SP H
L
*3. Set value: 4, Upper- and lower-limit range
Case 2
Case 1
H > 0, L < 0
⏐H⏐ ≤ ⏐L⏐
ON
OFF
ON
OFF
X
0
X
0
The alarm turns ON when the remote SP (RSP) is
larger than the alarm value (X). This alarm functions
in both Local SP and Remote SP Modes.
The alarm turns ON when the remote SP (RSP) is
smaller than the alarm value (X). This alarm
functions in both Local SP and Remote SP Modes.
*5. Set value: 5, Upper- and lower-limit with standby sequence
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
*6. Displayed when there is a remote SP input.
*7. Refer to the E5CN-HT/E5AN-HT/E5EN-HT Digital Controllers
User's Manual (Cat. No. H169) for information on the operation of
the standby sequence.
*8. Refer to the E5CN-HT/E5AN-HT/E5EN-HT Digital Controllers
User's Manual (Cat. No. H169) for information on the loop burnout
alarm (LBA).
*9. Refer to the E5CN-HT/E5AN-HT/E5EN-HT Digital Controllers
User's Manual (Cat. No. H169) for information on the PV change
rate alarm.
Case 3 (Always ON)
H < 0, L < 0
L
H SP
H < 0, L > 0
⏐H⏐ < ⏐L⏐
H
SP L H
H > 0, L < 0
⏐H⏐ > ⏐L⏐
H
SP
L
H < 0, L > 0
⏐H⏐ ≥ ⏐L⏐
L SP
SP H
L
H > 0, L < 0
⏐H⏐ ≤ ⏐L⏐
*4. Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above
• Case 1 and 2
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
• Case 3: Always OFF
7
E5AN-HT/E5EN-HT
Characteristics
Indication accuracy
Thermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) ±1 digit max. *1
Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) ±1 digit max.
Analog input: ±0.1% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Potentiometer input: ±5% FS ±1 digit max.
Transfer output accuracy ±0.3% FS max.
Influence of temperature
*2
Influence of voltage *2
Influence of EMS.
(at EN 61326-1)
Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: (±1%FS) ±1 digit max.
Input sampling period
60 ms
Hysteresis
Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P)
Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I)
0.0 to 3240.0 s (in units of 0.1 s)
Derivative time (D)
0.0 to 3240.0 s (in units of 0.1 s)
Control period
0.5, 1 to 99 s (in units of 1 s)
Manual reset value
0.0 to 100.0% (in units of 0.1%)
Alarm setting range
−19999 to 32400 (decimal point position depends on input type)
Affect of signal source
resistance
Thermocouple: 0.1°C/Ω max. (100 Ω max.)
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
Vibration
resistance
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Shock
resistance
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Weight
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions
Destruction 300 m/s2, 3 times each in X, Y, and Z directions
E5AN-HT
Controller: Approx. 310 g, Mounting Bracket: Approx. 100 g
E5EN-HT
Controller: Approx. 260 g, Mounting Bracket: Approx. 100 g
Degree of protection
Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection
Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool
CX-Thermo version 4.0 or higher
Setup Tool port
Provided on the bottom of the E5AN-HT and E5EN-HT.
An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5AN-HT and E5EN-HT.
Provided on the front of the E5AN-HT and E5EN-HT. An E58-CIFIR USB-infrared Conversion Cable is required to
connect the computer to the E5AN-HT or E5EN-HT. *4
Standards
Approved
standards
UL 61010-1, CSA C22.2 No. 1010-1
Conformed
standards
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II
EMI:
EN 61326-1 *5
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage:
EN 55011 Group 1, class A
EMS:
EN 61326-1 *5
ESD Immunity:
EN 61000-4-2
EMC
Electromagnetic Field Immunity:
EN 61000-4-3
Burst Noise Immunity:
EN 61000-4-4
Conducted Disturbance Immunity:
EN 61000-4-6
Surge Immunity:
EN 61000-4-5
Power Frequency Magnetic Field Immunity:
EN 61000-4-8
Voltage Dip/Interrupting Immunity:
EN 61000-4-11
*1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of −100°C max., and U
and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.
is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S
thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3% of PV or ±3°C,
whichever is greater, ±1 digit max.
The indication accuracy of PL II thermocouples is ±0.3% of PV or ±2°C, whichever is greater, ±1 digit max.
*2. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage
*3. K thermocouple at −100°C max.: ±10°C max.
*4. External communications (RS-232C, RS-485, or RS-422) and cable communications for the Setup Tool can be used at the same time.
*5. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
8
E5AN-HT/E5EN-HT
Program Control
Number of programs (patterns) 8
Number of segments (steps)
Segment setting method
Segment times
32
Time setting (Segment set with set point and time.)
Gradient setting (Segment type with set point, gradient, and time.)
0 h 0 min to 99 h 59 min
0 min 0 s to 99 min 59 s
Alarm setting
Set separately for each program.
Reset operation
Select either stopping control or fixed SP operation.
Startup operation
Select continuing, resetting, manual operation, or run mode.
PID sets
Alarm SP function
Program status control
Wait operation
Time signals
Program status output
Number of sets
8
Setting method
Set separately for each program (automatic PID group selection also supported).
Select from ramp SP and target SP.
Segment operation
Advance, hold
Program operation
Program repetitions and program links
Wait method
Waiting at segment ends
Wait width setting
Same wait width setting for all programs
Number of outputs
2
Number of ON/OFF
Operations
1 each per output
Setting method
Set separately for each program.
Program end output (pulse width can be set), run output, stage output
PV start
Program startup operation
Standby
Select from segment 1 set point, slope-priority PV start
0 h 0 min to 99 h 59 min
0 day 0 h to 99 day 23h
Operation end operation
Select from resetting, continuing control at final set point, and fixed SP control.
Program SP shift
Same program SP shift for all programs
9
E5AN-HT/E5EN-HT
USB-Serial Conversion Cable
USB-Infrared Conversion Cable
Applicable OS
Windows XP/Vista/7/8
Applicable OS
Windows XP/Vista/7/8
Applicable software
CX-Thermo version 4 or higher
Applicable software
CX-Thermo version 4.0 or higher
Applicable models
E5AN/E5EN/E5CN/E5CN-U/E5AN-H/
E5EN-H/E5CN-H/E5AN-HT/E5EN-HT/
E5CN-HT
Applicable models
E5AN-H/E5EN-H/E5AN-HT/
E5EN-HT
USB interface standard
Conforms to USB Specification 1.1.
USB interface standard
Conforms to USB Specification 1.1.
DTE speed
38400 bps
DTE speed
38400 bps
Computer: USB (type A plug)
Temperature Controller: Setup Tool port
(on bottom of Controller)
Connector specifications
Connector specifications
Computer: USB (type A plug)
Temperature Controller: Infrared port
(on front of Controller)
Bus power (Supplied from USB host
controller.)
Power supply
Power supply
Bus power (Supplied from USB host
controller.)
Power supply voltage
5 VDC
Power supply voltage
5 VDC
Current consumption
80 mA
Current consumption
70 mA
Ambient operating temperature
0 to 55°C (with no condensation or icing)
Ambient operating temperature
0 to 55°C (with no condensation or icing)
Ambient operating humidity
10% to 80%
Ambient operating humidity
10% to 80%
−20 to 60°C (with no condensation or
icing)
Storage temperature
Storage temperature
−20 to 60°C (with no condensation or
icing)
Storage humidity
10% to 80%
Storage humidity
10% to 80%
Altitude
2,000 m max.
Altitude
2,000 m max.
Weight
Approx. 130 g (with mounting adaptor)
Weight
Approx. 100 g
Note: A driver must be installed in the personal computer. Refer to
installation information in the operation manual for the
Conversion Cable.
Communications Specifications
Transmission line
connection method
RS-485, RS-422: Multipoint
RS-232C: Point-to-point
Communications
RS-485 (two-wire, half duplex)
RS-422 (four-wire, half duplex) or RS-232C
Synchronization
method
Note: A driver must be installed in the personal computer. Refer to
installation information in the operation manual for the
Conversion Cable.
Heater Burnout Alarms, SSR Failure
Alarms, and Heater Overcurrent Alarms
CT input
(for heater current detection)
Models with detection for single-phase
heaters: One input
Models with detection for single-phase or
three-phase heaters: Two inputs
Start-stop synchronization
Maximum heater current
50 A AC
Protocol
CompoWay/F or Modbus
Input current indication
accuracy
±5% FS ±1 digit max.
Baud rate
1200, 2400, 4800, 9600, 19200, 38400, or 57600
bps
Heater burnout alarm setting
range *1
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
Transmission code
ASCII (CompoWay/F)
RTU (Modbus)
SSR failure alarm setting
range *2
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms
Data bit length *
7 or 8 bits
Stop bit length *
1 or 2 bits
Heater overcurrent alarm
setting range *3
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
Error detection
Vertical parity (none, even, odd)
Block check character (BCC) with CompoWay/F or
CRC-16 Modbus
Flow control
None
Interface
RS-485, RS-422, or RS-232C
Retry function
None
Communications
buffer
217 bytes
Communications
response wait time
0 to 99 ms
Default: 20 ms
Current Transformer (Order Separately)
Ratings
Electrical Life Expectancy Curve for
Relays (Reference Values)
Dielectric strength
1,000 VAC for 1 min
Vibration resistance
50 Hz, 98 m/s2
Weight
E54-CT1: Approx. 11.5 g,
E54-CT3: Approx. 50 g
Accessories (E54-CT3 only)
Armatures (2)
Plugs (2)
No. of operations ( × 104)
* The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
*1. For heater burnout alarms, the heater current will be measured
when the control output is ON, and the output assigned to the
alarm 1 function will turn ON if the heater current is lower than the
set value (i.e., heater burnout detection current value).
*2. For SSR failure alarms, the heater current will be measured when
the control output is OFF, and the output assigned to the alarm 1
function will turn ON if the heater current is higher than the set
value (i.e., SSR failure detection current value).
*3. For heater overcurrent alarms, the heater current will be
measured when the control output is ON, and the output assigned
to the alarm 1 function will turn ON if the heater current is higher
than the set value (i.e., heater overcurrent detection current
value).
500
300
E5AN-HT/E5EN-HT
250 VAC, 30 VDC
(resistive load)
cosφ = 1
100
50
30
10
5
3
1
0
1
2
3
4
5
6
Switching current (A)
10
E5AN-HT/E5EN-HT
External Connections
Control output 1 and control output 2 are functionally isolated from the internal circuits.
Controllers
Option Units
Communications
The Temperature Controller is set
for a K-type thermocouple (input
type = 5) by default. An input error
(s.err) will occur if the input type
setting does not agree with the
temperature sensor. Check the
input type.
E53-EN01
RS-232C
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
Input power
supply
1
21
11
2
22
12
3
23
13
Control output 1
24
SD
11
RDB
11
B (+)
11
12
RD
12
RDA
12
A (−)
12
13
SG
13
SG
13
DO NOT USE
13
21
DO NOT USE
21
SDB
21
B (+)
21
22
DO NOT USE
22
SDA
22
A (−)
22
15
6
26
16
7
27
17
8
28
18
9
29
19
10
30
20
EV1
EV1
Potentiometer
Control output 2
O
CT2
Auxiliary output 2
EV2
EV2
CT1
25
Event Inputs
Event Inputs *
14
5
E53-AKB
E53-EN03
RS-485
11
CT2
4
E53-EN02
RS-422
14
Auxiliary output 3
W
15 Auxiliary output 3
C
16
DO NOT DO NOT
USE
USE
A
DO NOT
DO NOT V
USE
USE
B
Auxiliary output 1
B
DO NOT
USE
DO NOT
USE
mA
DO NOT
USE
Relay output
SPDT, 250 VAC, 3 A
(resistive load)
A heater burnout alarm, SSR
failure, heater overcurrent
alarm, input alarm, or Remote
SP Input Error is sent to the
output to which the alarm 1
function is assigned.
* EV3 and EV4 are assigned to event inputs in controllers with two event inputs.
Control Output Unit
Control outputs 1, 2
Control Output Unit
Control outputs 1, 2
Refer to page 4
Models with Positionproportional Control
Relay output
250 VAC, 1 A
(including inrush
current)
Auxiliary outputs 1, 2, 3
Relay output
SPST-NO,
250 VAC, 3 A
(resistive load)
1
Input power
supply
2
+
−
+
3
Open
4
21
22
EV3
4
23
24
EV4
5
Output unit
−
1
Input power
supply
2
3
Output unit
Event input */
Transfer output/
Remote SP
Models with Positionproportional Control
5
25
Closed
6
6
7
7
Auxiliary output 2
Auxiliary output 2
8
9
9
Auxiliary output 1
10
+
Transfer output
8
Auxiliary output 1
DO NOT USE
−
+
26
27 4 to 20 mA DC
(Load: 600 Ω max.)
28
29
4 to 20 mA DC
Remote SP input
10
−
30
Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly.
11
E5AN-HT/E5EN-HT
Isolation/Insulation Block Diagrams
Temperature input/Analog input/CT input/
Potentiometer input/Remote SP input
Communications/Event inputs
Voltage pulse output/Linear current output/
Linear voltage output/Transfer output
Power
supply
Relay output
Auxiliary output 1
Auxiliary output 2
: Reinforced insulation
: Functional insulation
Nomenclature
E5AN-HT
E5EN-HT
Temperature unit
Operation indicators
No.1 display
Operation indicators
Temperature unit
No.1 display
No.2 display
No.3 display
No.2 display
No.3 display
Operation indicators
Up Key
Programmable
Function Key/
Auto/Manual Key
Mode Key
Up Key
Programmable
Function Key/
Auto/Manual Key
Level Key
Down Key
Level Key
Mode Key
Infrared communications reception port
Down Key
Infrared communications reception port
12
E5AN-HT/E5EN-HT
Dimensions
(Unit: mm)
E5AN-HT
Group Mounted *
Mounted Separately
92
+1.0
0
+0.8
0
(96 × number of units − 3.5)
+0.8
0
92
Group mounting does not
allow waterproofing.
120 min.
+0.8
0
92
6
79.2
2
96 × 96
112
91
• Recommended panel thickness is 1 to
8 mm.
• Group mounting is not possible in the
vertical direction. (Maintain the specified
mounting space between Controllers.)
• To mount the Controller so that it is
waterproof, insert the waterproof
packing onto the Controller.
• When two or more Controllers are
mounted, make sure that the
surrounding temperature does not
exceed the allowable operating
temperature specified in the
specifications.
* Group mounting is not possible if an E53-C3N or E53-C3DN
Output Unit is used for control output 1 or 2. For these
combinations, maintain the following mounting space between
Controllers.
110 min.
92
Waterproof
Packing
(Accessory)
Mounting Bracket
(Accessory)
+0.8
0
Terminal Cover
(E53-COV16)
(Accessory)
92
Crimp terminal size: M3.5
+0.8
0
120 min.
13
E5AN-HT/E5EN-HT
E5EN-HT
Group Mounted *
Mounted Separately
(48 × number of units − 2.5)
+0.6
45 0
+1.0
0
+0.8
0
92
Group mounting does not
allow waterproofing.
120 min.
6
48
+0.8
92 0
79.2
2
• Recommended panel thickness is 1 to 8 mm.
• Group mounting is not possible in the vertical direction.
(Maintain the specified mounting space between
Controllers.)
• When two or more Controllers are mounted, make
sure that the surrounding temperature does not
exceed the allowable operating temperature specified
in the specifications.
* Group mounting is not possible if an E53-C3N or E53-C3DN Output
Unit is used for control output 1 or 2. For these combinations,
maintain the following mounting space between Controllers.
96
112
91
60 min.
45
Waterproof
Packing
(Accessory)
Mounting Bracket
(Accessory)
+0.6
0
+0.8
0
Terminal Cover
(E53-COV16)
(Accessory)
92
Crimp terminal size: M3.5
120 min.
14
E5AN-HT/E5EN-HT
Accessories (Order Separately)
USB-Infrared Conversion Cable
E58-CIFIR
USB-Infrared Conversion Cable
54
(2,000)
35.8
4.6 dia.
USB connector (type A plug)
LED indicator: RD
LED indicator: SD
17.8
With Mounting Adapter Connected
Mounting Adapter
39
16
18.5
Mounting Adapter
(Accessory)
99.2
23.1
21.8
(75)
USB-Serial Conversion Cable
E58-CIFQ1
(2,100)
LED indicator: SD
250
USB connector (type A plug)
1,765
LED indicator: RD
Serial connector
Terminal Covers
1.2
E53-COV16 (Six Covers provided.)
3.2
10
44.8
15
E5AN-HT/E5EN-HT
Waterproof Packing
Y92S-P4 (for DIN 96 × 96)
Y92S-P5 (for DIN 48 × 96)
Order the Waterproof Packing separately if it becomes lost or
damaged.
The Waterproof Packing can be used to achieve an IP66 degree of
protection.
(Deterioration, shrinking, or hardening of the waterproof packing may
occur depending on the operating environment. Therefore, periodic
replacement is recommended to ensure the level of waterproofing
specified in IP66. The time for periodic replacement depends on the
operating environment. Be sure to confirm this point at your site.
Consider one year a rough standard. OMRON shall not be liable for
the level of water resistance if the customer does not perform periodic
replacement.)
The Waterproof Packing does not need to be attached if a waterproof
structure is not required.
Current Transformers
E54-CT1
21
15
E54-CT1
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
2.8
5.8 dia.
7.5
3
Output voltage (Eo) V (r.m.s.)
25
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400±2
Winding resistance: 18±2 Ω
10.5
40
Two, 3.5 dia.
10
30
100 V
50 Hz
∞
10
Distortion
factor 10%
1 kΩ
1
3%
1%
100 mV
100 Ω
10
E54-CT3
RL = 10 Ω
1
2.36 dia.
30
12 dia.
100 μV
9
10
1
10
100 mA
1
40 × 40
Two, M3 (depth 4)
E54-CT3 Accessory
Connection Example
Armature
Plug
Lead
18
E54-CT3
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Output voltage (Eo) V (r.m.s.)
30
Approx. 3 dia.
100 1,000 A
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for an OMRON
Temperature Controller is 50 A.)
Number of windings: 400±2
Winding resistance: 8±0.8 Ω
15
• Armature
10
Thru-current (Io) A (r.m.s.)
100 V
50 Hz
Distortion
factor
10%
3%
1%
∞
10
1 kΩ
500 Ω
1
100 mV
100 Ω
50 Ω
10
RL = 10 Ω
• Plug
1
100 μV
Approx. 6 dia.
(22)
10
1
10
100 mA
1
10
100 1,000 A
Thru-current (Io) A (r.m.s.)
16
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2015.8
In the interest of product improvement, specifications are subject to change without notice.