High-power Solid State Relays

New Product News
High-power Solid State Relays
G3PH
High-power, Load-control SSRs with
High Current of 75 or 150 A and High
Voltage of 240 or 480 VAC
• RoHS compliant.
• Models also available with no zero cross.
• Replaceable power elements.
• Conforms to cULus standards and EN standards (TÜV certification).
Refer to Safety Precautions for All Solid State Relays.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Ordering Information
Solid State Relays
Insulation method
Operation indicator
Zero cross function
Applicable output load*
75 A, 100 to 240 VAC
Yes
150 A, 100 to 240 VAC
75 A, 100 to 240 VAC
150 A, 100 to 240 VAC
No
Photocoupler
Yes (yellow)
75 A, 180 to 480 VAC
Yes
150 A, 180 to 480 VAC
75 A, 180 to 480 VAC
150 A, 180 to 480 VAC
No
Rated input voltage
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
5 to 24 VDC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
5 to 24 VDC
Model
G3PH-2075B DC5-24
G3PH-2075B AC100-240
G3PH-2150B DC5-24
G3PH-2150B AC100-240
G3PH-2075BL DC5-24
G3PH-2150BL DC5-24
G3PH-5075B DC5-24
G3PH-5075B AC100-240
G3PH-5150B DC5-24
G3PH-5150B AC100-240
G3PH-5075BL DC5-24
G3PH-5150BL DC5-24
Note:The Thyristor Module is built in.
*The applicable output load depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering Data on page 2.
Options (Order Separately)
Thyristor Module
Name
Thyristor Module
Applicable output load*
75 A, 75 to 264 VAC
150 A, 75 to 264 VAC
75 A, 150 to 528 VAC
150 A, 150 to 528 VAC
Applicable models
G3PH-2075B(L)
G3PH-2150B(L)
G3PH-5075B(L)
G3PH-5150B(L)
Model
G32A-P2075
G32A-P2150
G32A-P5075
G32A-P5150
*The applicable output load depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering Data on page 2.
Specifications
Ratings
Input (at an Ambient Temperature of 25°C)
Rated voltage
Operating voltage
Impedance
(input current)
5 to 24 VDC
100 to 240 VAC
4 to 30 VDC
75 to 264 VAC
(5 mA max.)*
41 kΩ ±20%
Voltage level
Must operate voltage
Must release voltage
4 VDC max.
1.0 VDC min.
75 VAC max.
20 VAC min.
*A constant-current circuit is used for the input current to the G3PH.
Output
Item
Model
G3PH-2075B(L)
G3PH-2150B(L)
G3PH-5075B(L)
G3PH-5150B(L)
Rated load voltage
100 to 240 VAC
100 to 240 VAC
180 to 480 VAC
180 to 480 VAC
Applicable load
Load voltage range
Load current*
75 to 264 VAC
1 to 75 A (at 40°C)
75 to 264 VAC
1 to 150 A (at 40°C)
150 to 528 VAC
1 to 75 A (at 40°C)
150 to 528 VAC
1 to 150 A (at 40°C)
Inrush current resistance
800 A (60 Hz, 1 cycle)
1,800 A (60 Hz, 1 cycle)
800 A (60 Hz, 1 cycle)
1,800 A (60 Hz, 1 cycle)
*The load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering Data on page 2.
1
G3PH
Characteristics
Item
Model
G3PH-2075B
G3PH-2150B
G3PH-5075B
G3PH-5150B
G3PH-2075BL
G3PH-2150BL
G3PH-5075BL
Operate time
1/2 of load power source cycle + 1 ms max. for DC input
3/2 of load power source cycle + 1 ms max. for AC input
1 ms max.
Release time
1/2 of load power source cycle + 1 ms max. for DC input
3/2 of load power source cycle + 1 ms max. for AC input
1/2 of load power source cycle + 1 ms max.
Output ON voltage drop
1.6 V (RMS) max.
Leakage current
30 mA max. (at 240 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
60 mA max. (at 480 VAC)
30 mA max. (at 240 VAC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
10 to 55 to10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Acceleration of 50 m/s2 for 50 min in X, Y and Z directions (10 sweeps of 5 min each = 50 min total)
Shock resistance
500 m/s2, 3 times in X, Y, and Z directions
Ambient storage temperature
−30 to 100°C (with no icing or condensation)
Ambient operating temperature
−30 to 80°C (with no icing or condensation)
Ambient operating humidity
45% to 85%
Weight
Approx. 1.8 kg
Approx. 3.0 kg
Approx. 1.8 kg
Approx. 3.0 kg
Approx. 1.8 kg
Approx. 3.0 kg
G3PH-5150BL
60 mA max. (at 480 VAC)
Approx. 1.8 kg
Approx. 3.0 kg
Engineering Data
200
150
Inrush Current Resistance: Non-repetitive
G3PH-@075B (L) and G3PH-@150B (L)
Inrush current
Load current (A)
Load Current vs. Ambient Temperature
G3PH-@075B (L) and G3PH-@150B (L)
G3PH-@150B
Mounted on a
vertical surface
2,000
1,600
(A, Peak)
1,200
75
G3PH-@150B
Mounted on a horizontal surface
G3PH-@075B
Mounted on
a vertical surface
800
60
50
37
25
400
Mounted on a
horizontal surface
0
−30 −20
0
20 30 40
60
80
0
10
100
G3PH-@075B
30 50
100
300 500 1,000
Ambient temperature (°C)
3.0
2.0
Input current
100
0.6
0.4
0.3
Input current (mA)
G3PH (75 to 264 VAC)
Input impedance (kΩ)
Input current (mA)
Input Voltage vs. Input Impedance
G3PH (4 to 30 VDC)
1.0
3,000 5,000 10,000
Energized time (ms)
70
7
65
6
Input current
5
60
4
55
3
50
0.2
0.1
10
Impedance
0.06
0.04
0.03
Impedance
0.02
0.01
1
2
3
4 5 6
8 10
20
30 40
Input voltage (V)
2
1
2
45
1
40
0
50
100
150
200
250
300
Input voltage (V)
Input impedance (kΩ)
100
Keep the inrush current to below the inrush
current resistance value (i.e., below the
broken line) if it occurs repetitively.
G3PH
Dimensions
Note:All units are in millimeters unless otherwise indicated.
Solid State Relays
G3PH-2075B (L)
G3PH-5075B (L)
Four, 6.5-dia. holes
13
Two, M6 × 12 screws
Mounting Hole Dimensions
90±0.5
8
120
Terminal Arrangement/Internal
Connections (Top View)
Four, 6.5 dia. or M6
Two, M3 × 8
screws
135±0.5
150
Load
90±0.5
135±0.5
120
G3PH-2150B (L)
G3PH-5150B (L)
Four, 6.5 dia. or M6 holes
Two, M8 × 16 screws
22
Mounting Hole Dimensions
Terminal Arrangement/Internal
Connections (Top View)
126±0.5 156
Load
Four, 6.5 dia. or M6
8
171±0.5
Two, M3 × 8
screws
126±0.5
186
171±0.5
156
3
G3PH
Related Products
Replacement Parts
G32A-P
Thyristor Module
The Thyristor Module can be replaced if the element
is damaged.
● Replacing the Thyristor Module
Always turn OFF the input and load power supplies before performing the following procedure.
(1) Remove the four screws labeled “A,” remove the transparent cover, and remove the wiring.
A
in the electronic components on the PCB.
(5) You should be able to see the Thyristor Module. Remove the
screws labeled “D” and remove the Thyristor Module.
A
D
A
A
(2) Remove the four screws labeled “B” and remove the
nameplate.
B
B
B
B
Nameplate
(3) Remove the screws labeled “C” to free the base assembly.
Pull out the base assembly.
(The base assembly cannot be removed completely due
to the lead wires.)
C
Base
(4) Remove the connectors
that connect the lead
wires to the Thyristor
Module, and remove the
Module.
If there is an abnormality in the electronic components on the PCB, the
Thyristor Module may
fail again after replacement. Consult with your
OMRON representative
if there is an abnormality
4
Protective
Connector
cover groove
Protective cover
PCB To Thyristor Module
D
PCB groove
Heat sink
Reverse the order of the above steps to assemble the
SSR again.
(6) When replacing the Thyristor Module, wipe all silicon grease
off the heat sink and make sure there is no foreign matter on
the contact surfaces of the Thyristor Module and heat sink.
Apply a thin, even coating of new grease (provided) to the
contact surfaces, and tighten the screws labeled "D" tentatively and then tighten them evenly to 2.5 to 4.0 N·m.
The silicon grease should be thin enough so that it does squirt
out from between the contact surfaces when the screws are
tightened.
(7) Connect the Thyristor Module and PCB with the socket.
(The socket can be connected in either direction.) Being
careful not to get the lead wires caught, assemble the
base assembly and heat sink. Align the PCB with the PCB
groove, and the protective cover with the protective cover
groove.
(8) Tighten the screws labeled “C.” A large current flows
through this section. Be sure that there is no foreign matter
present, and tighten the screws to between 4.41 and 4.90
N·m.
(9) Check again to be sure that the lead wires are not caught,
that the protective cover is in its groove, and that the PCB
is in its groove, and then place the nameplate in the original position and tighten the screws labeled “B” to between
0.2 and 0.49 N·m.
(10) Wire the SSR, attach the protective cover, and tighten the
screws labeled “A” to between 0.2 and 0.49 N·m.
(11) Turn ON the power supplies and check operation.
Safety Precautions
● Refer to Safety Precautions for All Solid State Relays.
CAUTION
Minor electrical shock may occasionally occur.
Do not touch the G3PH terminal section (i.e.,
current-carrying parts) while the power is being
supplied. Also, always attach the cover terminal.
The G3PH may rupture if short-circuit current
flows. As protection against accidents due to
short-circuiting, be sure to install protective
devices, such as fuses and no-fuse breakers,
on the power supply side.
Minor electrical shock may occasionally occur.
Do not touch the main circuit terminals on the
G3PH immediately after the power supply has
been turned OFF. Shock may result due to the
electrical charge stored in the built-in snubber circuit.
Minor burns may occasionally occur.
Do not touch the G3PH or the heat sink while
the power is being supplied or immediately after the power supply has been turned OFF. The
G3PH and heat sink become extremely hot.
• Locations subject to shock or vibration.
● Installation and Handling
• Do not block the movement of the air surrounding the G3PH
or heat sink. Abnormal heating of the G3PH may result in
shorting failures of the output elements or burn damage.
• Do not use the G3PH if the heat radiation fins have been
bent by being dropped. Doing so may result in malfunction
due to a reduction in the heat radiation performance.
• Do not handle the G3PH with oily or dusty (especially iron
dust) hands. Doing so may result in malfunction.
● Installation and Mounting
• The SSR must be mounted on a vertical surface. Mount the
G3PH in the specified direction. Otherwise excessive heat
generated by the G3PH may cause short-circuit failures of
the output elements or burn damage.
• Make sure that there is no excess ambient temperature rise
due to the heat generation of the G3PH. If the G3PH is
mounted inside a panel, install a fan so that the interior of
the panel is fully ventilated.
• When using screws to mount the SSR to a control panel or
other surface, tighten the screws securely. Keep the screws
tightened to between 4.41 and 4.90 N·m. If the screws are
not tight enough, the SSR may fall off.
● Installation and Wiring
Precautions for Safe Use
OMRON constantly strives to improve quality and reliability.
SSRs, however, use semiconductors, and semiconductors
may commonly malfunction or fail. In particular, it may not be
possible to ensure safety if the SSRs are used outside the rated ranges.
Therefore, always use the SSRs within the ratings. When using an SSR, always design the system to ensure safety and
prevent human accidents, fires, and social harm in the event
of SSR failure. System design must include measures such as
system redundancy, measures to prevent fires from spreading, and designs to prevent malfunction.
● Transport
Do not transport the G3PH under the following conditions.
Doing so may result in damage, malfunction, or deterioration
of performance characteristics.
• Conditions in which the G3PH may be subject to water or
oil.
• Conditions in which the G3PH may be subject to high temperature or high humidity.
• Conditions in which the G3PH is not packaged.
● Operating and Storage Environments
Do not use or store the G3PH in the following locations. Doing
so may result in damage, malfunction, or deterioration of performance characteristics.
• Locations subject to rainwater or water splashes.
• Locations subject to exposure to water, oil, or chemicals.
• Locations subject to high temperature or high humidity.
• Do not store in locations subject to ambient storage temperatures outside the range −30 to 100°C.
• Do not use in locations subject to relative humidity outside
the range 45% to 85%.
• Locations subject to corrosive gases.
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to direct sunlight.
• Use wires that are suited to the load current. Otherwise, excessive heat generated by the wires may cause burning.
• Do not use wires with a damaged outer covering.
Otherwise, it may result in electric shock or ground leakage.
• Do not wire any wiring in the same duct or conduit as power
or high-tension lines. Otherwise, inductive noise may damage the G3PH or cause it to malfunction.
• When tightening terminal screws, prevent any non-conducting material from becoming caught between the screws and
the tightening surface. Otherwise, excessive heat generated by the terminal may cause burning.
• Do not use the G3PH with loose a terminal screw. Otherwise, excessive heat generated by the wire may cause
burning.
• Tighten each terminal to the torque specified below.
Improper tightening may result in abnormal heat generation
at the terminal, which may cause burning.
(M3: 0.50 to 0.60 N·m, M6: 4.41 to 4.90 N·m M8: 8.82 to
9.80 N·m)
• If a current of 40 A or higher will flow, use M6 or M8 crimp
terminals that are suitable for the wire size. Improper wiring
may result in burning, melted cable coverings, electric
shock, or ground faults.
• Always turn OFF the power supply before performing wiring. Not doing so may cause electrical shock.
● Installation and Usage
• Select a load within the rated values. Not doing so may result in malfunction, failure, or burning.
• Select a power supply within the rated frequencies. Not doing so may result in malfunction, failure, or burning.
• The G3PH contains a circuit that protects the internal circuits from being destroyed by forcing the output element to
fire when there is a surge voltage. The G3PH therefore cannot be used for motor loads. Doing so may result in load motor malfunction.
5
Safety Precautions
Precautions for Correct Use
The SSR in operation may cause an unexpected accident.
Therefore it is necessary to test the SSR under the variety of
conditions that are possible. As for the characteristics of the
SSR, it is necessary to consider differences in characteristics
between individual SSRs.
The ratings in this catalog are tested values in a temperature
range between 15°C and 35°C, a relative humidity range between 25% and 75%, and an atmospheric pressure range between 86 and 106 kPa. It will be necessary to provide the
above conditions as well as the load conditions if the user
wants to confirm the ratings of specific SSRs.
● Causes of Failure
• Do not drop the G3PH or subject it to abnormal vibration or
shock during transportation or mounting. Doing so may result in deterioration of performance, malfunction, or failure.
• Tighten each terminal to the torque specified below. Improper tightening may result in abnormal heat generation at
the terminal, which may cause burning.
Screw terminal
Tightening torque
diameter
Terminals
Input terminals
G3PH-@075B (L)
Output
terminals G3PH-@150B (L)
M3
0.50 to 0.60 N·m
M6
4.41 to 4.90 N·m
M8
8.82 to 9.80 N·m
• Do not supply overvoltage to the input circuits or output circuits. Doing so may result in failure or burning.
• Do not use or store the G3PH in the following conditions.
Doing so may result in deterioration of performance.
• Locations subject to static electricity or noise
• Locations subject to strong electric or magnetic fields
• Locations subject to radioactivity
● Mounting
• The SSR is heavy. Mount it securely to the panel under the
following conditions.
Screw diameter: M6
Tightening torque: 4.41 to 4.90 N·m
Mounted to a
vertical surface
Mounted on a
horizontal surface
Vertical
Direction
Panel
Panel
6
● Wiring
• Make sure that all lead wires are thick enough for the current.
• The output terminal will be charged even when the SSR is
OFF. Touching the terminal may result in electric shock. To
isolate the SSR from the power supply, install an appropriate circuit breaker between the power supply and the SSR.
Always turn OFF the power supply before wiring the SSR.
● Fuses
• Use a quick-burning fuse on the output terminals to prevent
accidents due to short-circuiting. Use a fuse with equal or
greater performance than those given in the following table.
Recommended Fuse Capacity
Rated G3PH
output current
Applicable SSR
Fuse
(IEC 60269-4)
75 A
G3PH-@075B (L) Series
100 A
150 A
G3PH-@150B (L) Series
200 A
Note: For example, FR22UD69V100 (690 V, 100 A) and FR27UD69V200T
(690 V, 200 A) by Ferraz Shawmut.
Safety Precautions
● Compliance with EN (EMC) Standards
● Mounting to Control Panel
The G3PH complies with EN (EMC) standards under the following conditions.
• The output cables may induce noise into other conductors
and should not be installed near or parallel to sensitive cables (input cables, signal wires e.t.c.)
• A capacitor is connected to the input power line.
• A noise filter connected to GND and toroidal core must be
connected to the load power supply.
• The input cable is 3 m or less.
The SSR is heavy. Mount it securely to the panel.
If the panel is airtight, heat from the SSR will build up inside,
which may reduce the current carry ability of the SSR or adversely affect other electrical devices. Be sure to install ventilation holes on the top and bottom of the panel.
SSR Mounting Pitch (Panel Mounting)
Duct or other object blocking airflow
Troidal core
10 mm min.
LOAD
INPUT
G3PH
OUTPUT
60 mm min.
SSR
Noise
filter
Vertical
Direction
3 m Max.
Recommended Capacitor (Film Capacitor)
Input: 0.1 µF, 250 VAC
Recommended Noise filter : COSEL : TAC series or equivalent (G3PH-2@@@B(L))
COSEL : TBC series or equivalent (G3PH-5@@@B(L))
Recommended toroidal core: NEC TOKIN ESD-R-25B or equivalent
30 mm min.
80 mm min.
● EMI
This is a Class A product (for industrial environments). In a domestic environment, the G3PH may cause radio interference,
in which case the user may be required to take appropriate
measures.
● Noise and Surge Effects
If noise or an electrical surge occurs that exceeds the malfunction withstand limit for the G3PH output circuit, the output
will turn ON for a maximum of one half cycle to absorb the
noise or surge. Confirm that turning the output ON for a half
cycle will not cause a problem for the device or system in
which the G3PH is being used prior to actual use. The G3PH
malfunction withstand limit is shown below.
• Malfunction withstand limit (reference value): 500 V
Note: This value was measured under the following conditions.
Noise duration: 100 ns and 1 μs
Repetition period: 100 Hz
Noise application time: 3 min
● Replacing the Thyristor Module
• Always apply the enclosed silicon grease to the contact surfaces when replacing the Thyristor Module.
• Tighten the screws to the following torque to secure the
Thyristor Module to the SSR to enable proper heat dissipation.
Tightening torque: 2.45 to 4.0 N·m
7
Safety Precautions
● Relationship between the G3PH and Ducts or Other Objects Blocking Airflow
Incorrect Example
Countermeasure 1
Duct or other object
blocking airflow
Vertical
Direction
Airflow
SSR
SSR
Mounting surface
120 mm
*(156 mm)
60 mm max.
(78 mm max.)
(Recommend
ed: Half or
less of the
SSR height)
Mounting surface
Mounting surface
120 mm
*(156 mm)
Countermeasure 2
Base
SSR
Duct or other object
blocking airflow
If the depth direction of the
G3PH is obstructed by
ducts, the heat radiation
will be adversely affected.
Use ducts that have a
shallow depth, to provide
a sufficient ventilation
area.
If the ducts cannot be made
lower, place the G3PH on a
metal base so that it is not
surrounded by the ducts.
*Values in parentheses
are for the G3PH-@150B.
● Ventilation Outside the Control Panel
Be aware of airflow
Duct or other object
blocking
airflow
SSR
SSR
Ventilation
outlet
(Axial Fan)
SSR
Air inlet
Note 1. If the air inlet or air outlet has a filter, clean the filter regularly to prevent
it from clogging to ensure an efficient flow of air.
2. Do not locate any objects around the air inlet or air outlet, otherwise
the objects may obstruct the proper ventilation of the control panel.
3. A heat exchanger, if used, should be located in front of the G3PH to
ensure the efficiency of the heat exchanger.
● G3PH Ambient Temperature
The rated current of the G3PH is measured at an ambient
temperature of 40°C.
The G3PH uses a semiconductor to switch the load. This
causes the temperature inside the control panel to increase
due to heating resulting from the flow of electrical current
through the load. The G3PH reliability can be increased by
adding a ventilation fan to the control panel to dispel this heat,
thus lowering the ambient temperature of the G3PH.
(Arrhenius's law suggests that life expectancy is doubled by
each 10°C reduction in ambient temperature.)
SSR rated current (A)
75 A
150 A
Required number of fans per SSR
1.16
2.33
Example: Ten, 75-A SSRs require 1.16 × 10, or 12 fans.
Note 1. Size of fans: 92 mm × 92 mm, Air volume: 0.7 m3/min, Ambient temperature of control panel: 30°C
2. If there are other instruments that generate heat in the control panel in
addition to SSRs, more ventilation will be required.
8
MEMO
9
MEMO
10
Warranty and Application Considerations
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or
other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER
ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET
THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS,
OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,
INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE
MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of
products in the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with
your OMRON representative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
OMRON Corporation
Industrial Automation Company
Authorized Distributor:
Tokyo, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
© OMRON Corporation 2011 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
Printed in Japan
CSM_1_2_0812
Cat. No. J177-E1-01
0711