4 3 2 1 Micro Data Center Layout, Cable Management, Grounding/Bonding, Power and ID Panduit Multimode Dielectric Conduited Fiber (Uplink) PANDUIT WGSDWL PANDUIT WGSDWL Panduit TM Wyr-grid TM Light Thermal Blanking panels optimize airflow and improve appearance. Perforated and solid blanking panels shown. PANDUIT WGSDWL Cable Management 1RU Fiber enclosure with termination management, bend radius control and protection 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 44 45 45 46 46 47 47 48 48 11 22 33 44 55 66 77 88 99 10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 44 45 45 46 46 47 47 48 48 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 44 45 45 46 46 47 47 48 48 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 CONSOLE MODE MODE CONSOLE FN 2X 2X SYST SYST FN 1X 1X Network Switch 1 1 2 2 1 1 2 2 3 3 4 4 5 5 CONSOLE CONSOLE MODE MODE SYST SYST FN FN XPS XPS S-PWR S-PWR 6 6 STAT STAT MAST MAST 7 7 XPS XPS S-PWR S-PWR 8 8 SPEED SPEED STACK STACK 9 9 STAT STAT MAST MAST DUPLX DUPLX 11X 13X 11X 13X 10 10 SPEED SPEED STACK STACK 11 11 12 12 4 4 5 5 SYST SYST FN FN 6 6 7 7 XPS XPS S-PWR S-PWR 8 8 9 9 STAT STAT MAST MAST 10 10 SPEED SPEED STACK STACK 11 11 12 12 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 2X 2X 2 2 3 3 4 4 5 5 CONSOLE SYST FN 6 6 7 7 8 8 9 9 10 10 XPS STAT SPEED S-PWR MAST STACK Panduit Multimode Fiber Patch Cord 11 11 12 12 2X 2 1 3 4 2 5 6 3 7 8 9 4 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 36X 38X 36X 38X 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 45 46 47 48 44Catalyst 45 3750-X 46 Series 47 48 Catalyst 3750-X Series G1 G1 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 45 46 47 48 44Catalyst 45 3750-X 46 Series 47 48 Catalyst 3750-X Series G1 G1 35X 37X 35X 37X C3KX-NM-10G C3KX-NM-10G NETWORK BLANK MODULE NETWORK MODULE BLANK MODULE MODULE G2/TE1 G2/TE1 G4/TE2 G4/TE2 G3 G3 C3KX-NM-10G C3KX-NM-10G NETWORK BLANK NETWORK BLANK MODULE MODULE MODULE MODULE G2/TE1 G2/TE1 G4/TE2 G4/TE2 36X 38X 36X 38X 23X 25X 23X 25X 35X 37X 35X 37X G3 G3 24X 26X 24X 26X 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 C3KX-NM-10G C3KX-NM-10G NETWORK BLANK NETWORK BLANK MODULE MODULE MODULE MODULE G2/TE1 G2/TE1 G4/TE2 G4/TE2 36X 38X 36X 38X 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 45 46 47 48 44Catalyst 45 3750-X 46 Series 47 48 Catalyst 3750-X Series G1 G1 G3 G3 DUPLX 1X 1 35X 37X 35X 37X 25 25 24X 26X 24X 26X 12X 14X 12X 14X 1 1 24X 26X 24X 26X 23X 25X 23X 25X DUPLX DUPLX 11X 13X 11X 13X MODE 10 11 5 11X 13X 12X 14X 12 23X 25X 24X 26X 13 14 6 15 16 17 7 18 19 20 8 21 22 23 9 NETWORK BLANK MODULE MODULE G2/TE1 G4/TE2 Cable Management Standard patching using a 24 Port Patch Panel with D-Ring (open) or (hidden) Horizontal NetManagerTM (hidden) Horizontal Manager 36X 38X 24 10 C3KX-NM-10G 35X 37X 25 11 26 27 12 28 29 30 31 32 13 33 34 14 35 36 15 37 38 16 39 40 17 41 42 43 44 45 46 47 Catalyst 3750-X Series 18 19 48 G1 20 21 22 G3 23 24 24 # # # # Inside Cabinet 14 14 13 13 12X 14X 12X 14X 3 3 CONSOLE CONSOLE 1X 1X Layout Switches turned around to have ports on same side 23X 25X 23X 25X 13 13 11X 13X 11X 13X 2X 2X 1 12X 14X 12X 14X DUPLX DUPLX 1X 1X MODE MODE # # # Identification Label cords with FROM and TO location. Panduit TurnTell labels makes it easy to view 3 3 2 2 1 2 3 4 5 1 0 1 1 1 X4 2 A 0 X4 1 GbEiSCSI TOE 3 4 5 0 X4 1 3 PCI PCI 2 1 X4 6Gb SAS 5 2 2 6Gb SAS 0 4 0 X4 4 1 3 PCI PCI 2 4 1 3 ATTENTION Power supply filler is required for system cooling Remove only when installing 2nd power supply AC DC ATTENTION Power supply filler is required for system cooling Remove only when installing 2nd power supply AC PCI 2 1 PCI 2 PCI DC 4 3 PCI ATTENTION Power supply filler is required for system cooling Remove only when installing 2nd power supply AC DC 4 1 3 PCI PCI 2 4 1 3 ATTENTION Power supply filler is required for system cooling Remove only when installing 2nd power supply AC DC PCI 2 Servers 3 0 5 0 X4 1 GbEiSCSI TOE Strain Relief Strain Relief Bar and Clip securely hold horizontal cable preventing disconnect 1 0 3 3 4 0 B 2 A 1 GbEiSCSI TOE 3 1 1 X4 2 2 1 X4 6Gb SAS 2 1 GbEiSCSI TOE 6Gb SAS 0 1 0 B PCI ATTENTION Power supply filler is required for system cooling Remove only when installing 2nd power supply AC DC 4 1 3 PCI PCI 2 4 ATTENTION Power supply filler is required for system cooling Remove only when installing 2nd power supply AC DC 1 3 PCI PCI 2 4 ATTENTION Power supply filler is required for system cooling Remove only when installing 2nd power supply AC DC UPS UPS ATTENTION Power supply filler is required for system cooling Remove only when installing 2nd power supply AC DC B Heavy Uninterruptible Power Supply Front View A Rear View Power Verticle Power Outlet Unit (POU) powers devices. Some units have power and environmental monitoring and connected to UPS. A second POU can be added for redundant power. Grounding/Bonding Grounding cable attach to grounding bar. Jumpers attach to ground bar and equipment Use this drawing when: Deploying a new compute, network, and/or storage cabinet or Rack Upgrading or adding devices Expanding the network Addressing Move, Add and Changes maintenance issues B A Micro Data Center Reference Design Y-PCD0007-05AUG2014--ENG.pdf 4 C 3 2 3 3 # Storage Array D PANDUIT WGSDWL Cable Management High Density patching using a 48 Port Angled Patch Panel. Horizontal managers not needed. 1 RU Space for Fiber Shelf Panduit Small Diameter Patch Cord C To Factory Integrated Network Zone Systems or Switches PANDUIT WGSDWL PANDUIT WGSDWL 2 PANDUIT WGSDWL 1 PANDUIT WGSDWL 0 D Panduit CAT 6 Industrial Cable 3 To Enterprise 3 2 1 Bill of Material Panduit Part Number Description 42RU Pre-Configured Industrial Micro Data Center, 78.1" CQSMDC79 (1984mm) height, network cabling, 4 casters, and shock pallet. Net-Access S-Type Cabinet frame. Single hinge perforated S8222B CPPA48FMWBLY CPPL24M6BLY front door. Split perforated rear doors. Dim 79.8"H x 31.5"W x 48.0"D Angled 48-port flush mount patch panel supplied with rear mounted faceplates 24-port patch panel supplied with four factory installed CJ688TGBL CFPLM6BL snap-in faceplates. Cat 6, 8 position, 8 wire universal module. CMPHF1 D-rings installed on panel NMF1 Horizontal Cable Manager High Capacity Front Only 1RU TLBP1R-V Tool-less Blanking Panel for 1RU UTP28SP5GR F52ERLNLNSNM001 FAP6WBLDLC FCE1U CMRPSV20 Cat 6 Performance, 28 AWG UTP patch cord with TX6 Modular Plugs on each end Green 5 ft or FOSM splice modules Power Strip Vertical, 20A, 10 NEMA 5-20R Receptacles, NEMA 5-20P Grounding Busbar Kit, 19" length, 20 holes RGCBNJ660P22 #6 AWG jumper; 60" length; 45° bent lug SRBBRWC-KIT IUC6C04ABL-CEG FSPD508-050M WG12BL10 Server, Switch, Storage, etc. Layout For best stability, heavier equipment like server, UPS and storage should be mounted towards the bottom of a cabinet or rack with lighter components like switch, firewall and patch panel towards the top. Reliable and efficient cabling is best with all equipment ports facing backwards. Equipment like switches may need to be turned around with their port side facing backwards. Cabinet rails may need to be moved forward to line up devices on the front. Ensure cabinet or rack RU holes are compatible with equipment rails and brackets. Cable Management Follow best practices to route and protect cabling to achieve the highest reliability and ease Moves, Adds, and Changes. Reduce interference with ports by placing rack mounted horizontal cable managers like D-Rings and NetManagers above and below equipment or flat patch panels to route cables away from port. Use angled patch panels for high density patching. A fiber enclosure protects exposed fiber cable, termination management (e.g. fusion splice), and bend radius control. Select patch cord lengths that have minimal slack between connections. Use slack spools to take up slack. Bundle cables using Hook & Loop cable ties for easy cable additions and removal. Horizontal cable should have strain relief to prevent jack connection damage like a strain relief bar. OM2 2-fiber patch cord, riser rated, LC duplex to LC duplex Grounding & Bonding Grounding and bonding is essential for reliable communication and equipment with 1.6mm jacket 1M protection. A solid copper grounding conductor is terminated to a lug and LC OM2 FAP loaded with six LC duplex multimode fiber optic then landed on a grounding bar. Jumper cables are attached to equipment adapters (Black) with phosphor bronze split sleeves. ground terminal and then routed to the grounding bar terminated with a lug that is attached to the grounding bar with a screw. Holds up to four QuickNet Cassettes, FAP adapter panels, RGRB19CN R100X150V1T About this Configuration TurnTellThermal Transfer, Vinyl, 1.00" W x 1.50" H, 0.50" Power Reliable power is achieved with redundant power sources via UPS or dual, independent power lines to a Power Outlet Unit (POU). The POU should have a current rating and outlets sized to support current and future equipment. POUs can also come with power and environmental monitoring to provide critical alerts. Identification Clear and intuitive identification eases installation along with Move, Adds and Changes. This includes labeling cables on both ends following TIA-606B standards. Color coding such as cables, color bands, and labels can be Strain relief bar with integrated adjustable clips and pair of used to identify VLANs, areas, media type. quick release brackets. POA, Clear/White, 3" Core Industrial Copper Cable, Cat 6, 4-pair, 24/7 AWG stranded, U/UTP, CM, Black, 1000FT/305m reel 8-fiber OM2 dielectric conduited, Low smoke zero halogen (LSZH)-riser (OFNR) rated, (MM) indoor distr cable 50M 12" Wide Wyr-Grid Straight Section For More Information For more information, contact your local distributor, Panduit Sales rep or Rockwell Automation sales rep. www.panduit.com/ia [email protected]