500 Series Multiple Input and Output Modules

500 Series
Multiple Input and
Output Modules
System Sensor multiple input and output modules
are designed to meet a range of applications in which
numerous single modules are used.
Features
• Removable 12 to 18 AWG plug-in terminal blocks
• Individual LED indicators
• Unused addresses may be disabled
• Rotary address switches
• Class A or B operation
• Mount up to two modules in BB-2 enclosure (optional)
• M
ount up to six modules in BB-6 enclosure with CH-6 chassis
(optional)
• Mounting hardware included
CR-6 SIX RELAY CONTROL MODULE
The CR-6 Six Relay Control module consists of six Form-C relays.
The first address is set from 01 to 94, while the remaining modules
are automatically assigned to the next five higher addresses.
Provisions are included for disabling a maximum of three unused
addresses. A single isolated set of dry relay contacts is provided for
each module address which is capable of being wired for either a
normally open or normally closed operation. The module allows the
control panel to switch these contacts on command. No supervision
is provided for the controlled circuit.
SC-6 SIX SUPERVISED CONTROL MODULE
The SC-6 Six Supervised Control module provides supervised
monitoring of wiring to load devices that require an external power
supply or amplifier to operate, such as horns, strobes, speakers
or bells. Upon command from the control panel, the SC-6 will
disconnect the supervision and connect the external power supply
across the load device. The first module is addressed from 01 to 94,
while the remaining modules are assigned to the next five higher
addresses. Provisions are included for disabling a maximum of
three unused modules. Each module has terminals for connection
to an external supply circuit for powering devices on its notification
appliance circuit. One or multiple power supplies or amplifiers may
be used.
Agency Listings
S7305
CS669
The design of the System Sensor 500 Series multiple input and
output modules allows for installation ease and time savings The
monitor and control modules can be used to supervise and activate
sounders, strobes, door closers, pull stations, waterflow switches,
conventional smoke detectors and more. The conventional zone
interface module is ideal for retrofit applications to monitor zones of
conventional two-wire detectors. Each module has its own address.
Modules are addressed with easy-to-use rotary code switches.
Provisions are included for disabling unused addresses. Up to two
modules mount in a BB-2 enclosure with built-in chassis and up to
six modules mount in a BB-6 enclosure with the CH-6 chassis. Wiring
terminals are easily accessible for trouble-shooting purposes.
3012062
7300-1653:0160
2102
continued
There is a short circuit protection monitor for each module. This
is provided to protect the external power supply against short
circuit conditions on the NAC. When an alarm condition occurs,
the relay which connects the external supply to the NAC will not be
allowed to close if a short circuit condition currently exists on the
NAC. In addition, an algorithm is incorporated to find a short when
the module is active. The module will close all circuits that are not
shorted to find the NAC with the problem.
SYNC-1 ACCESSORY CARD
The SYNC-1 is an optional accessory to the SC-6 and is designed
to provide a means of synchronizing a series of horns, strobes, and
horn/strobes. The SYNC-1 is able to synchronize the temporal-coded
horns, the one second flash timing of the strobe, and silencing the
horns of the horn/strobe combination over a two-wire circuit while
leaving the strobes active. Each SYNC-1 accessory card has the
capability of synchronizing six Class B circuits or three Class A
circuits.
CZ-6 SIX ZONE INTERFACE MODULE
The CZ-6 Six Zone Interface module provides an interface between
the intelligent alarm system and a two-wire conventional detection
zone. A common SLC input is used for all modules, and the initiating
device circuits share a common external supply. Otherwise, each
module operates independently from the others. The first module
is addressed from 01 to 94 while the remaining modules are
assigned to the next five higher addresses. Provisions are included
for disabling a maximum of two unused modules. All two-wire
detectors being monitored must be two-wire compatibility listed
with the modules. The CZ-6 transmits the status of a zone of twowire detectors to the fire alarm control panel. Status conditions are
reported as normal, open or alarm. The interface module supervises
the zone of detectors and the connection of the external power
supply.
IM-10 TEN INPUT MONITOR MODULE
The IM-10 Ten Input Monitor module provides an interface between
a control panel and normally open contact devices such as pull
stations, security contacts, or flow switches. The first address is
set from 01 to 90 and the remaining modules are automatically
assigned to the next nine higher addresses. Provisions are included
for disabling a maximum of two unused addresses. The supervised
state (normal, open or short) of the monitored device is sent back to
the panel.
ISO-6 SIX ISOLATOR MODULE
The ISO-6 Six Isolator Module is an automatic switch that opens
when the line voltage drops below four volts. Isolator modules
should be spaced between groups of sensors or modules in a loop
to protect the rest of the loop. If a short occurs between any two
isolators, then both isolators immediately switch to an open circuit
state and isolate the devices between them. The remaining units on
the loop continue to fully operate.
TWO INPUT / TWO OUTPUT MODULE
The multiple module combines two relay outputs and two monitor
inputs into one device. The module is capable of Class B supervised
wiring to the monitored devices. It also contains Form C relay
contacts allowing the panel to switch the contacts on command.
There is a dedicated LED on the module for each input and output.
The control panel can use these bi-color LEDs to indicate normal,
trouble and alarm conditions.
500 Series Module Specifications
General Specifications
Operating Voltage
Maximum SLC Wiring
Resistance
Temperature Range
Relative Humidity
Wire Gauge
Dimensions
Specifications: CR-6
Standby Current
Alarm Current
Maximum IDC Wiring
Resistance
Relay Current
Relay Contact Ratings
Specifications: CZ-6
Standby Current
Alarm Current
Maximum IDC Wiring
Resistance
External Supply Voltage
Compatible Detectors
Specifications: SC-6
Standby Current
Alarm Current
15 to 32 VDC
40 Ohms
32°F to 120°F (0° to 49°C)
10% to 85% noncondensing
12 to 18 AWG
6.8 in H × 5.8 in W × 1.25 in D
1.45 mA maximum
32 mA maximum (assumes all six relays
have been switched once and all six
LEDs solid on)
40 Ohms
30 mA/Relay Pulse (15.6 mS pulse
duration) pulse under panel control
See product installation manual
2 mA maximum
40 mA maximum
(assumes all six LEDs solid on)
25 Ohms
DC Voltage: 18 to 28 volts power limited
Ripple Voltage: 0.1 volts RMS maximum
Current: 90 mA per circuit
Contact System Sensor for a current list
2.25 mA maximum
35 mA maximum (assumes all six relays
have been switched once and all six
LEDs solid on)
40 Ohms
Maximum NAC Circuit
Wiring Resistance
Power Rating Per Circuit 50 W @ 70.7 VAC
Specifications: IM-10
Standby Current
Alarm Current
3.5 mA maximum
60 mA maximum
(assumes all ten LEDs solid on)
40 Ohms
Maximum IDC Wiring
Resistance
Maximum IDC Voltage
12 VDC
Maximum IDC Current
1 mA
Specifications: ISO-6
Standby Current
2.7 mA
Maximum Current Draw
102 mA
Specifications: Two Input and Two Output Module
Dimensions
4.675 in H x 4.275 in W x 1.4 in D
Standby Current
1.3 mA (one communication every
5 sec. with 47k EOL)
End-of-Line Resistance
47 kOhms (two included)
Specifications: SYNC-1
Operating Voltage
11 to 30 VDC
Maximum Load on a Loop
Class A/Style Z: 3A
Class A/Style Y: 3A per pair
Standby Current
+0 Position: 15 mA
+2 or +4 Position if connected to
supply: 2.5 mA
Specifications: BB-2 Enclosure
Dimensions
12˝H × 9˝W × 3.67˝D
Specifications: BB-6 Enclosure
Dimensions
24˝H × 12.55˝W × 6.47˝D
Accessories
SYNC-1 Accessory Card
BB-6 Enclosure with CH-6 Chassis
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
www.systemsensor.com
©2014 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
MDDS37101 • 4/14