M501M Monitor Module

I56-3857-001
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
M501M Monitor Module
15-32 VDC
350 µA, 1 communication every 5 seconds, 47k EOL; 600 µA Max. (Communicating, IDC Shorted)
47K Ohms
40 Ohms
11 Volts
400µA
32°F to 120°F (0°C to 49°C)
10% to 93% Non-condensing
1.3˝ H × 2.75˝ W × 0.65˝ D
6˝ minimum
Before Installing
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.
Mounting and Wiring
NOTE: This module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordinances, and regulations.
1.Connect the red (+) and black ( – ) wires to the positive and negative
loop power leads of the signaling line circuit.
2.Connect the violet (+) and yellow ( – ) wires to a two-wire, normally
open initiating loop.
3.Install the specified EOL resistor value to terminate the initiating loop.
4. Set the address on the module per job drawings.
5. Install the module in the desired mounting location.
Figure 2. Typical 2-wire style B initiating
circuit configuration:
NOTICE: This manual should be left with the owner/user of this equipment.
General Description
The M501M monitor module can be installed in a single gang junction box
directly behind the monitored unit. Its small size and light weight allow it to
be installed without rigid mounting (see Figure 1). The M501M is intended for
use in intelligent, two-wire systems where the individual address of each module is selected using rotary decade switches. It provides a two-wire initiating
circuit for normally open contact fire alarm and security devices.
UL LISTED
COMPATIBLE
CONTROL
PANEL
Compatibility Requirements
To ensure proper operation, this module should only be connected to a compatible control panel.
SIGNAL LINE CIRCUIT (SLC)
TO
NEXT
DEVICE
(+)
(–)
BLACK
Figure 1:
(–)
ALL WIRING
SHOWN IS
SUPERVISED AND
POWER LIMITED
RED
Specifications
Nominal Operating Voltage:
Average Operating Current:
EOL Resistance:
Maximum IDC Wiring Resistance:
Maximum IDC Voltage:
Maximum IDC Current:
Temperature Range:
Humidity:
Dimensions:
Wire Length:
(+)
67 8 9
5
4
3
2
10
6789
5
4
3
2
10
)+(
)–(
VIOLET
YELLOW
47k EOL
INCLUDED
(ELR-47k)
C0614-03
C0613-04
SS-460-005
1
I56-3857-001
©2007 System Sensor