EPS40-1 and EPS40-2 Supervisory Pressure

EPS40-1 and EPS40-2
Supervisory Pressure
Switches
System Sensor EPS40 Series switches are designed
for use in dry pipe systems or pressure tanks and water
pressure supplies of automatic water control valves.
Features
• Sensitivity adjustment wheel, no special tools required
• Reinforced diaphragm resists pressure spikes
• Two conduit entrances
• Both one- and two-switch models available
IO
ER
N C TIFI
TIO
CA
PREVENT
Agency Listings
A
R
SS
N BO
LPCB
The EPS40-1 has a single SPDT switch while the EPS40-2 model
contains two SPDT switches. The EPS40 Series features field
adjustable pressure sensitivity to provide an alarm response between
10 and 100 psi. All models are factory set for use in a nominal
40 psi system. The EPS40-1 is factory set to respond at 30 psi at
decreasing pressure while the EPS40-2 is factory set to respond at
50 psi on rising pressure and 30 psi at decreasing pressure. The
pressure adjustment wheel requires no special tools and does not
affect switch synchronization on the EPS40-2. The EPS40-1 and
EPS40-2 supervisory pressure switches are NEMA 4 rated.
D
LO
118f/01
0X0A7.AY
0D3A3.AY
S739
VdS
G4020027
7770-1653:0117
C5169
Specifications, EPS40-1 and EPS40-2
Architectural/Engineering Specifications EPS40-1 (SPDT), EPS40-2 (2/SPDT)
Model shall be an EPS40-1 or EPS40-2 pressure type waterflow switch as manufactured by System Sensor of St. Charles, IL. They shall be
installed on the sprinkler system with connection as shown on the drawings and/or as specified herein. Pressure switches shall be of the
bellows-activated type. Switches shall have a maximum service pressure rating of 300 psi and shall be adjustable from 10 – 100 psi. There
shall be one (1) or two (2) SPDT contacts rated at 10.0 Amp @ 125/250 VAC and 2.5 Amp @ 6/12/24 VDC. The contractor shall furnish and
install, where indicated on the plans, pressure switches according to appropriate NFPA standards. Switches shall be provided with a ½˝ NPT
male pressure connection to be connected into the air supply line on the system side of any shut-off valve. Switches shall provide 1 knockout
type and 1 open hole for ½˝ conduit fitting attachment and a ground screw provision for electrical grounding.
The switch enclosure shall be weatherproof and carry a UL 4x/NEMA 4 rating when used with proper electrical fittings and conduit. The cover
shall incorporate tamper-resistant screws. The unit shall be listed by Underwriters Laboratories, Inc., the California State Fire Marshal, MEA,
CSFM, LPCB, VdS and approved by Factory Mutual.
Specifications, EPS40-1 and EPS40-2 (continued)
Physical/Operating Specifications
Maximum Operating
300 psi
Pressure
Maximum Adjustment 10 to 100 psi
Pressure Range
Differential
Approximately 3 psi @ 10 psi, 6 psi @ 100
psi
Factory Setting
EPS40-1 operates at decreasing pressure
at 30 psi
EPS40-2 operates at increasing pressure at
50 psi and decreasing pressure at 30 psi
Switch Contact
EPS10-1: One set SPDT (Form C)
Ratings
EPS10-2: Two sets SPDT (Form C)
10.0 A, ½ HP @ 125/250 VAC
2.5 A @ 6/12/24 VDC
Operating Temperature
Range
Cover Tamper Switch
Enclosure
Shipping Weight
Automatic Sprinkler: NFPA 13
One or Two Family Dwelling: NFPA 13D
Residential Occupancies up to 4 Stories:
NFPA 13R
National Fire Alarm Code: NFPA 72
3 years
Service Use
½˝ NPT male
Warranty
5.12˝ H × 3.325˝ W × 4.250˝ L (13.0 cm × 8.4 cm × 10.8 cm)
Pressure Connection
Dimensions
Indoor or outdoor use:
–40°F to 160°F (–40°C to 71°C)
UL Models: Optional P/N 546-8000
ULC Models: Factory Installed
Rated UL 4x, NEMA 4 for indoor or
outdoor use
1.2 lbs. (.54 Kg)
Typical Sprinkler Applications
EPS40
WIRE TO SUPERVISORY
CIRCUIT OF FIRE ALARM
CONTROL PANEL
WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL
EPS40
TO
SPRINKLER
SYSTEM
INSTALL
BLEEDER
VALVE FOR
TESTING
CHECK
VALVE
CHECK
VALVE
DRY
PIPE
VALVE
AIR LINE
SHUT-OFF
VALVE
WATER
MOTOR
GONG
WATER
BY-PASS
TEST
VALVE
OS & Y
VALVE
LOCAL ALARM
SHUT OFF
VALVE
DRY SYSTEM
Electrical Connections
Pressure Switch Basic Dimensions
MODELS EPS40-1
SWITCHES AT 40 P.S.I. (NORMAL)
B
COM
A
SWITCH 1
SW1
B
COM
A
51/8˝
SW2
SWITCHES AT 50 P.S.I. (HIGH TRIP PT.)
B
COM
A
SW1
B
COM
A
M
B
COM
A
SWITCH #2
B
SWITCH AT 30 P.S.I. (LOW TRIP PT.)
GROUND
SCREW
(GREEN)
SWITCHES AT 30 P.S.I. (LOW TRIP PT.)
B
B
COM
COM
A
A
SW1
SW2
A
B
COM
A
CO
SWITCH AT 40 P.S.I. (NORMAL)
41/4˝
MODELS EPS40-2
LOCKING
SCREW
HEX
A DJUSTMENT
SCREW
MA IN A DJUSTMENT
WHEEL
1/2˝
NPT
SW2
Ordering Information
Part No.
EPS40-1
EPS40-2
EPSA40-1
EPSA40-2
Replacement Parts
S07-66-XX
WFDW
546-8000
Description
Low Pressure Supervisory Switch, One SPDT, 10–100 PSI
High/Low Pressure Supervisory Switch, Two SPDT, 10–100 PSI
Low Pressure Supervisory Switch, One SPDT, 10–100 PSI (ULC Model)
High/Low Pressure Supervisory Switch, Two SPDT, 10–100 PSI (ULC Model)
Replacement Tamper Screws for Cover of EPS
Replacement Tamper Proof Wrench for Cover of EPS
Cover Tamper Switch for EPS Series
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
www.systemsensor.com
©2014 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
WFDS51801 • 5/14