EPS40-1 and EPS40-2 Supervisory Pressure Switches System Sensor EPS40 Series switches are designed for use in dry pipe systems or pressure tanks and water pressure supplies of automatic water control valves. Features • Sensitivity adjustment wheel, no special tools required • Reinforced diaphragm resists pressure spikes • Two conduit entrances • Both one- and two-switch models available IO ER N C TIFI TIO CA PREVENT Agency Listings A R SS N BO LPCB The EPS40-1 has a single SPDT switch while the EPS40-2 model contains two SPDT switches. The EPS40 Series features field adjustable pressure sensitivity to provide an alarm response between 10 and 100 psi. All models are factory set for use in a nominal 40 psi system. The EPS40-1 is factory set to respond at 30 psi at decreasing pressure while the EPS40-2 is factory set to respond at 50 psi on rising pressure and 30 psi at decreasing pressure. The pressure adjustment wheel requires no special tools and does not affect switch synchronization on the EPS40-2. The EPS40-1 and EPS40-2 supervisory pressure switches are NEMA 4 rated. D LO 118f/01 0X0A7.AY 0D3A3.AY S739 VdS G4020027 7770-1653:0117 C5169 Specifications, EPS40-1 and EPS40-2 Architectural/Engineering Specifications EPS40-1 (SPDT), EPS40-2 (2/SPDT) Model shall be an EPS40-1 or EPS40-2 pressure type waterflow switch as manufactured by System Sensor of St. Charles, IL. They shall be installed on the sprinkler system with connection as shown on the drawings and/or as specified herein. Pressure switches shall be of the bellows-activated type. Switches shall have a maximum service pressure rating of 300 psi and shall be adjustable from 10 – 100 psi. There shall be one (1) or two (2) SPDT contacts rated at 10.0 Amp @ 125/250 VAC and 2.5 Amp @ 6/12/24 VDC. The contractor shall furnish and install, where indicated on the plans, pressure switches according to appropriate NFPA standards. Switches shall be provided with a ½˝ NPT male pressure connection to be connected into the air supply line on the system side of any shut-off valve. Switches shall provide 1 knockout type and 1 open hole for ½˝ conduit fitting attachment and a ground screw provision for electrical grounding. The switch enclosure shall be weatherproof and carry a UL 4x/NEMA 4 rating when used with proper electrical fittings and conduit. The cover shall incorporate tamper-resistant screws. The unit shall be listed by Underwriters Laboratories, Inc., the California State Fire Marshal, MEA, CSFM, LPCB, VdS and approved by Factory Mutual. Specifications, EPS40-1 and EPS40-2 (continued) Physical/Operating Specifications Maximum Operating 300 psi Pressure Maximum Adjustment 10 to 100 psi Pressure Range Differential Approximately 3 psi @ 10 psi, 6 psi @ 100 psi Factory Setting EPS40-1 operates at decreasing pressure at 30 psi EPS40-2 operates at increasing pressure at 50 psi and decreasing pressure at 30 psi Switch Contact EPS10-1: One set SPDT (Form C) Ratings EPS10-2: Two sets SPDT (Form C) 10.0 A, ½ HP @ 125/250 VAC 2.5 A @ 6/12/24 VDC Operating Temperature Range Cover Tamper Switch Enclosure Shipping Weight Automatic Sprinkler: NFPA 13 One or Two Family Dwelling: NFPA 13D Residential Occupancies up to 4 Stories: NFPA 13R National Fire Alarm Code: NFPA 72 3 years Service Use ½˝ NPT male Warranty 5.12˝ H × 3.325˝ W × 4.250˝ L (13.0 cm × 8.4 cm × 10.8 cm) Pressure Connection Dimensions Indoor or outdoor use: –40°F to 160°F (–40°C to 71°C) UL Models: Optional P/N 546-8000 ULC Models: Factory Installed Rated UL 4x, NEMA 4 for indoor or outdoor use 1.2 lbs. (.54 Kg) Typical Sprinkler Applications EPS40 WIRE TO SUPERVISORY CIRCUIT OF FIRE ALARM CONTROL PANEL WIRE TO ALARM INDICATING CIRCUIT OF FIRE ALARM CONTROL PANEL EPS40 TO SPRINKLER SYSTEM INSTALL BLEEDER VALVE FOR TESTING CHECK VALVE CHECK VALVE DRY PIPE VALVE AIR LINE SHUT-OFF VALVE WATER MOTOR GONG WATER BY-PASS TEST VALVE OS & Y VALVE LOCAL ALARM SHUT OFF VALVE DRY SYSTEM Electrical Connections Pressure Switch Basic Dimensions MODELS EPS40-1 SWITCHES AT 40 P.S.I. (NORMAL) B COM A SWITCH 1 SW1 B COM A 51/8˝ SW2 SWITCHES AT 50 P.S.I. (HIGH TRIP PT.) B COM A SW1 B COM A M B COM A SWITCH #2 B SWITCH AT 30 P.S.I. (LOW TRIP PT.) GROUND SCREW (GREEN) SWITCHES AT 30 P.S.I. (LOW TRIP PT.) B B COM COM A A SW1 SW2 A B COM A CO SWITCH AT 40 P.S.I. (NORMAL) 41/4˝ MODELS EPS40-2 LOCKING SCREW HEX A DJUSTMENT SCREW MA IN A DJUSTMENT WHEEL 1/2˝ NPT SW2 Ordering Information Part No. EPS40-1 EPS40-2 EPSA40-1 EPSA40-2 Replacement Parts S07-66-XX WFDW 546-8000 Description Low Pressure Supervisory Switch, One SPDT, 10–100 PSI High/Low Pressure Supervisory Switch, Two SPDT, 10–100 PSI Low Pressure Supervisory Switch, One SPDT, 10–100 PSI (ULC Model) High/Low Pressure Supervisory Switch, Two SPDT, 10–100 PSI (ULC Model) Replacement Tamper Screws for Cover of EPS Replacement Tamper Proof Wrench for Cover of EPS Cover Tamper Switch for EPS Series 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2014 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. WFDS51801 • 5/14