Data Sheet - System Sensor

OSY2
Supervisory Switch
The System Sensor OSY2 is used to monitor the open
position of an Outside Screw and Yoke (OS&Y) type
gate valve.
Features
Robust Construction. The OSY2 consists of a rugged housing,
intended for indoor and outdoor use. When installed with the
actuator in the vertical position, the OSY2 is NEMA 3R rated per UL.
•NEMA 3R-rated enclosure
•User-friendly mounting bracket fits newer valve yokes
•Single side conduit entry does not require right angle fittings
•Adjustable length actuator eliminates the need for cutting the shaft
•Accommodates up to 12 AWG wire
•Three position switch monitors vandal and valve close signals
•Two SPDT contacts are enclosed in a durable terminal block for
added strength
•100 percent synchronization activates both alarm panel and local
bell simultaneously
Application Flexibility. The OSY2 features a user-friendly
mounting bracket and adjustable shaft to permit mounting to most
OS&Y valves, ranging in size from 1˝ to 12˝. Its right angle design
and wide bracket span provides maximum clearance for valve
components, to accommodate troublesome valves. Removing the
OSY2’s gate valve bracket allows the unit to monitor side-bracketstyle pressure reducing valves.
Simplified Operation. Installation is made easier with the
OSY2’s single side conduit entrance. By providing a direct conduit
pathway to the electrical source, right angle fittings are not required.
Installation is further simplified by the OSY2’s adjustable length
actuator, which eliminates the need for cutting the shaft.
Reliable Performance. The OSY2 is equipped with tamperresistant cover screws to prevent unauthorized entry. Inside, two sets
of SPDT (Form C) synchronized switches are enclosed in a durable
terminal block to assure reliable performance.
Agency Listings
S739
CS169
OW6A8.AY
167–93–E
7770-1653:118
OSY2 Specifications
Architectural/Engineering Specifications
Model shall be model number OSY2 supervisory switch as manufactured by System Sensor. OSY2 shall be installed on each valve as designated on the drawings
and/or as specified herein. Switches shall be mounted so as not to interfere with the normal operation of the valve and shall be adjusted to operate within
two revolutions of the valve control or when the stem has moved no more than one-fifth of the distance from its normal position. The mechanism shall be
contained in a weatherproof die cast metal housing that provides a side entrance for ½˝ conduit and incorporates the necessary facilities for attachment to
the valve. A grounding provision is provided. The switch assembly shall include two switches each with a rated capacity of 10 Amp @ 125/250VAC and 2.5
Amp @ 24VDC. The cover shall contain tamper-resistant screws for which a security wrench will be provided with each switch. The OSY2 shall be Underwriters
Laboratories listed for indoor or outdoor use. The OSY2 shall be Factory Mutual, CSFM, and MEA approved.
Physical Specifications
Operating Specifications
Overall Switch
5¾˝H x 3½˝W x 3¼˝D
Contact Ratings
Two sets of SPDT (Form C)
Dimensions
(14.6cm x 8.9cm x 8.2cm)
10.0 A @ 125/250VAC; 2.5 @ 6/12/24VDC
Shipping Weight
2.8 lbs. (1.3 kg)
Enclosure Rating
UL indoor/outdoor
NEMA 3R when mounted with the actuator vertical
Operating Temperature
Range
Cover Tamper Switch
Standard with ULC model
Optional for UL model, part no. 546-7000
Maximum Stem Extension 25/8˝ (6.7cm)
Service Use
Bracket Span
Conduit Entrances
Warranty
U.S. Patent Nos.
Automatic Sprinkler: NFPA 13
One or Two Family Dwelling: NFPA 13D
Residential Occupancies up to 4 stories: NFPA 13R
National Fire Alarm code: NFPA 72
3 years
5,478,038; 5,213,205
32°F to 120°F ( 0°C to 49°C)
NOTE: The OSY2 will operate from –40°F to 120°F
(–40°C to 49°C); however UL does not test control valve
supervisory switches below 32°F (0°C).
¼˝H x 6¾˝W x 1˝D (5.7cm x 17.1cm x 2.5cm)
One single side open for ½˝ conduit
Electrical Connections for OSY2
OSY2 Mounting
TOP VIEW
SWITCH 1
CONTACT RATINGS
CO
OM
M
A
125/250 VAC
10 AMPS
24 VDC
2.5 AMPS
NOTE: COMMON AND B CONNECTIONS
WILL CLOSE WHEN VALVE MOVES 1/5 OF
ITS TOTAL TRAVEL DISTANCE.
The
are examples
of acceptable
THEfollowing
FOLLOWING
ARE EXAMPLES
OF
mounting
positions:
ACCEPTABLE
MOUNTING POSITIONS:
THE FOLLOWI
POSITION IS N
C
B
B
A
SWITCH 2
STRIP GAUGE
TYPICAL FACP CONNECTION
SUP. SWITCH
B
TO NONSILENCEABLE
INITIATING ZONE
OF LISTED FACP
COM
SUP. SWITCH
B
B
COM
B
END-OF-LINE
THE FOLLOWING ARE EXAMPLES
OF
RESISTOR
ACCEPTABLE
MOUNTING
POSITIONS:
COM
COM
Actuator
Vertical (Down) Actuator
Horizontal
ACTUATOR
ACTUATOR
VERTICAL
(DOWN)
HORIZONTAL
THE FOLLOWING
MOUNTING
The following
mounting
is not acceptable:
POSITION
IS NOTposition
ACCEPTABLE:
TYPICAL LOCAL BELL CONNECTION
B
TO POWER
SOURCE
COMPATIBLE
WITH BELL
LOCAL
BELL
COM
BREAK WIRE AS SHOWN FOR SUPERVISION
OF CONNECTION. DO NOT ALLOW STRIPPED
WIRE LEADS TO EXTEND BEYOND SWITCH
HOUSING. DO NOT LOOP WIRES.
ACTUATOR
VERTICAL (DOWN)
ACTUATOR
HORIZONTAL
Actuator Vertical
ACTUATOR VERTICAL
(Pointing
Up)UP)
(POINTING
Ordering Information
Part No.
OSY2
OSY2A
Accessories
OSYRK
546-7000
S07-66-XX
Description
Outside Screw and Yoke valve supervisory switch
Outside Screw and Yoke valve supervisory switch (ULC model)
Replacement hardware kit (wrenches, screw pack and J–hooks)
Cover tamper switch kit
Tamper screws for cover
WFDW
HEXW
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
Replacement tamper-proof wrench for cover
Replacement hex wrench
©2009 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0196-010 • 1/09 • #1960
ACTUA