B501BhT Temporal Tone Sounder Base

I56-1367-005R
INSTALLATION AND MAINTENANCE INSTRUCTIONS
B501BHT
Temporal Tone Sounder Base
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Specifications
Base Diameter:
6.0 inches (15.2 cm)
Base Height (less sensor):
2.3 inches (5.9 cm)
Weight:
0.4 lb. (181 gm)
Operating Temperature Range:
32° to 120°F (0° to 49°C)
Operating Humidity Range:
10% to 93% Relative Humidity
Electrical Ratings
External Supply Voltage:
17 to 32 VDC
Standby Current:
1.0 mA maximum
Alarm Current:
15 mA maximum
Maximum Ripple Voltage:
10% of supply voltage
Start-up Capacitance:
200 µF
Communication/Initiating Loop Supply
Current Draw from Remote Output
of Sensor to turn on Horn:
700 µA maximum
Sound Output:
Greater than 90 dBA measured in anechoic room at 10 feet, 24 volts. 85 dBA minimum
measured in UL reverberant room.
Before Installing
Please read the System Smoke Detector Application Guide,
which provides detailed information on sensor spacing. placement, zoning, wiring, and special applications. Copies of this
manual are available from System Sensor. NFPA 72 and NEMA
guidelines should be observed.
NOTE: When not used as a supplementary evacuation system
the external 24 VDC supply shall be treated as a component of
the main power supply system and shall fall under the requirements of the main power supply system per NFPA 72.
B501BHT Terminals
No.
Function
NOTICE: This manual should be left with the owner/user of
this equipment.
1
2
3
4
5
IMPORTANT: The detector used with this base must be tested
and maintained regularly following NFPA 72 requirements.
The detector should be cleaned at least once a year.
General Description
The B501BHT sounder base is used with System Sensor 200
and 500 Series sensor heads. Refer to the appropriate manual
for more information on sensors.
External Supply Positive (+)
External Supply Negative (–)
Negative (–) Comm. Line In and Out
Positive (+) Comm. Line In and Out
Sounder Base Interconnect
Terminals 3 and 4 are used for the communication circuit.
Mounting
Mount the B501BHT directly to an electrical box, using the
mounting kit, supplied (see Figure 2).
The B501BHT incorporates the distinctive three-pulse temporal pattern fire alarm evacuation signal now required by NFPA
72 for commercial and residential applications.
The sounder base is 1.1-inches deep. Electrical boxes must
be 4-inches square by at least 11⁄2 inches deep - 21⁄8 inches is
recommended.
The sounder base is intended for use with intelligent systems.
Refer to the panel manual for the maximum allowable number of units per loop. The sounder base requires an external
24VDC supply with reverse polarity capability or a relay module configured to reverse the power as in Figure 5. The connections for the external supply (terminals 1 and 2) and the
communication loop (terminals 3 and 4) are isolated to prevent electrical interaction between them.
NOTE: A maximum space of 1⁄8 inch from the outside edge of
the electrical box to the inside edge of the drywall or ceiling
tile is allowable.
Wiring Guidelines
All wiring must be installed in compliance with the National
Electrical Code and the local codes having jurisdiction and
must not be of such length or wire size which would cause
the base to operate outside of its published specifications. The
conductors used to connect smoke sensors to control panels
and accessory devices should be color coded to reduce the
likelihood of wiring errors. Improper connections can prevent
a system from responding properly in the event of a fire.
When the sensor’s visible LEDs are latched on for approximately 10 seconds, the associated horn sounds. A loop of
horns can be made to sound by reversing the polarity of the
external supply when configured as in Figure 4 and 5. When
configured as in Figure 5, a loop of horns can also be made to
sound by turning on the Intelligent Relay Module.
D550-06-00
1
I56-1367-005R
For signal wiring (the wiring between interconnected sensors
or modules), it is recommended that the wire be no smaller
than 18 gauge (1.0 square mm). Wire sizes up to 12 gauge (2.5
square mm) may be used with the base. For best system performance, the power (+ and –) wires and the communication
circuit wires should be twisted pair or shielded cable installed
in separate grounded conduit to protect the communication
loop from electrical interference.
Figure 1. Terminal layout:
1
2
Make wire connections by stripping about 3⁄8” of insulation
from the end of the wire. Then, slide the bare end of the
wire under the clamping plate, and tighten the clamping
plate screw. Do NOT loop the wire under the clamping plate
(See Figure 3).
5
4
The zone wiring of the sensor base should be checked before
the sensor heads are installed. Check the wiring for continuity
and polarity in the base.
3
C0736-00
See the individual sensor manual for the maximum sensor installation temperature.
Figure 2. Mounting:
Wiring Instructions
NOTE: External supply shown in normal standby configuration in Figure 4 and 5.
The wiring diagram for a typical 2-wire intelligent system is
shown in Figure 4 and 5 (the monitor module is supervising
the external supply).
Testing
Sensors and bases must be tested after installation and as an integral part of periodic maintenance. Test the B501BHT as follows:
MOUNT B501BHT
TO ELECTRICAL BOX
NOTE: Before testing, notify the proper authorities that the
smoke sensor system is undergoing maintenance and, therefore, will be temporarily out of service. Disable the system undergoing maintenance to prevent unwanted alarms.
4 INCH SQUARE BOX
1.If configured as in Figure 4 or 5, reverse the polarity of the
external 24VDC supply. If configured as in Figure 5, turn
on the Intelligent Relay Module. All B501BHT bases on the
loop should sound in approximately 10 seconds.
2.Latch the sensor LED on from the control panel. That unit’s
B501BHT should sound in approximately 10 seconds.
NOTES:
1.There is approximately a 10 second delay built into the
B501BHT before sounding. This delay is present whether
the control signal comes from the sensor or from the external power supply polarity being reversed.
2.During automatic testing cycles, the horn may sound if
the associated sensor is left in the test mode with LEDs
latched on for more than 4 seconds. Therefore, it is necessary to complete testing of each sensor within this 4-second limit to prevent the horn from sounding.
C0472-00
Figure 3:
C0473-00
D550-06-00
2
I56-1367-005R
Figure 4. Wiring diagram:
Detector Activates Sounder Base(s) - (Complies with UL268)
gether using terminal 5, Sounder Base Interconnect, as shown
in the diagram.
UL has approved grouping for up to six B501BHT base with
horn units. When wired as a group, any detector in the group
that has its LED’s latched on by the panel will cause other
B501BHT units in the group to sound. This type of “local”
grouping is accomplished by wiring the grouped devices to-
NOTE: Since a local grouping of horns is not supervised, the
groups can only be used as a supplementary evacuation system.
It is not acceptable to group horns for primary alarm signaling.
INTELLIGENT
MONITOR MODULE
(+) SLC
OPTIONAL SOUNDER INTERCONNECT*
(–) SLC
(+) COMM.
4 5
3
4 5
2 1
4 5
3
2 1
3
SUP (+)
SUP (–)
U.L. LISTED COMPATIBLE
CONTROL PANEL
CLASS A OPTIONAL WIRING
U.L.
LISTED
EOL
RESISTOR
47K
2 1
(–) COMM.
U.L.
LISTED
EOL
RELAY
24V
EXTERNAL
24V SUPPLY
(–) POWER
(+) POWER
CLASS A OPTIONAL WIRING
C0474-04
*GROUPING OF UP TO 6 MODEL B501BHT TEMPORAL TONE SOUNDER BASES.
Figure 5. Wiring diagram:
Detector Activates Sounder Base(s); Intelligent Relay Module Activates All Sounder Bases - (Complies with UL 268 and UL 464)
grouping is accomplished by wiring the grouped devices together using terminal 5, Sounder Base Interconnect, as shown
in the diagram.
UL has approved grouping of up to six B501BHT bases with
horn units. When wired as a group, any detector in the group
that has its LED’s latched on by the panel will cause other
B501BHT units in the group to sound. This type of “local”
NOTE: Since a local grouping of horns is not supervised, the
groups can only be used as a supplementary evacuation system. It is not acceptable to group horns for primary alarm
signaling.
OPTIONAL SOUNDER INTERCONNECT
SLC
(+) SLC
(–) SLC
COMM 2
(–) SLC
NC 2
(+) SLC
UL LISTED
24V SUPPLY
(+) SLC
LAST
SOUNDER
BASE
FIRST
SOUNDER
BASE
COMM 1
NO 1
SUP (+)
(–) SLC
NO 2
NC 1
INTELLIGENT
MONITOR MODULE
SUP (–)
INTELLIGENT †
RELAY
MODULE
UL LISTED
COMPATIBLE
CONTROL
PANEL
*
UL LISTED
EOL
RESISTOR
47k
UL
LISTED
EOL
RELAY
24V
(–) POWER
(+) POWER
IS A STANDARD RELAY
† THIS
MODULE CONFIGURED TO
REVERSE THE POWER
C0968-01
*GROUPING OF UP TO 6 MODEL B501BHT TEMPORAL TONE SOUNDER BASES.
D550-06-00
3
I56-1367-005R
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a
note describing the malfunction and suspected cause of failure. The Company shall not
be obligated to repair or replace units which are found to be defective because of damage,
unreasonable use, modifications, or alterations occurring after the date of manufacture.
In no case shall the Company be liable for any consequential or incidental damages for
breach of this or any other Warranty, expressed or implied whatsoever, even if the loss
or damage is caused by the Company’s negligence or fault. Some states do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation
or exclusion may not apply to you. This Warranty gives you specific legal rights, and you
may also have other rights which vary from state to state.
System Sensor warrants its enclosed smoke detector base to be free from defects in materials and workmanship under normal use and service for a period of three years from date
of manufacture. System Sensor makes no other express warranty for this smoke detector
base. No agent, representative, dealer, or employee of the Company has the authority to
increase or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of the smoke
detector base which is found to be defective in materials or workmanship under normal
use and service during the three year period commencing with the date of manufacture.
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: System Sensor, Returns
D550-06-00
4
I56-1367-005R
©2009 System Sensor