IM-10 Ten Input Monitor Module

I56-1797-007
INSTALLATION AND MAINTENANCE INSTRUCTIONS
IM-10
Ten Input Monitor Module
SPECIFICATIONS
Normal Operating Voltage:
Stand-By Current:
Alarm Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Wire Gauge:
Maximum IDC Wiring Resistance:
Maximum IDC Voltage:
Maximum IDC Current:
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
15–32 VDC
3.5 mA
60 mA (assumes all ten LEDs solid on)
32°F to 120°F (0°C to 49°C)
10 to 93% Non-condensing
6.8˝H x 5.8˝W x 1.25˝D
CH-6 Chassis; BB-6 Cabinet; BB-2 Cabinet
12-18 AWG
40 Ohms
12 VDC
1 mA
BEFORE INSTALLING
Shipped on Board:
This information is included as a quick reference installation
guide. Refer to the appropriate control panel installation manual
for detailed system information. If the modules will be installed in
an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect the power to the control panel before installing the modules.
This system contains static sensitive components. Always ground
yourself with a proper wrist strap before handling any circuits so
that static charges are removed from the body. The housing cabinet should be metallic and suitably grounded.
(1)
Shunt in Class A/B position
(Shipped in Class B position, remove shunt for Class A)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a
listed compatible system control panel.
COMPONENTS
Following are descriptions of the IM-10 mounting frameworks.
There are two mounting options for IM-10 modules:
NOTICE: This manual should be left with the owner/user of this
equipment.
• Up to six IM-10 modules can be installed on a CH-6 in a
BB-6 cabinet
• One or two IM-10 modules can be installed in a BB-2 cabinet
GENERAL DESCRIPTION
The IM-10 Ten Input Monitor Module is intended for use in an intelligent alarm system. Each monitor module is intended to interface between a control panel and normally open contact devices,
such as pull stations. A common SLC input is used for all modules, and the initiating device loops share a common supervisory
supply and ground. Otherwise, each monitor operates independently from the others. Each module has its own unique address.
Chassis
The CH-6 chassis is used to mount IM-10 modules in a BB-6 cabinet. It accommodates up to six IM-10 modules in a single cabinet
row three modules wide and two modules deep.
Figure 1. CH-6 Chassis:
A pair of rotary code switches is used to set the address of the
first module from 01 to 90. The remaining modules are automatically assigned to the next nine higher addresses. Provisions are
included for disabling a maximum of two unused modules to release the addresses to be used elsewhere. Each module also has
panel controlled green LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
Included:
(6) 1 x 4 Terminal Blocks
C0206-00
1
(2) 1 /4″ (32mm) Stand offs
The BB-2 cabinet has a built-in chassis that will accommodate
one or two IM-10 modules.
(4) Machine Screws (2) Nuts (3) Shunts (10) 47k Ohm
End of Line Resistors
C0202-00
D500-47-00
1
I56-1797-007
Figure 2. BB-2 Cabinet:
BASE ADDRESS
6789
67 8 9
5
10
5
11 4
4
12 3
3
13 2
2
1
10
14
0 15
BASE ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
6789
67 8 9
5
10
5
11 4
4
12 3
3
13 2
2
1 0 1514
10
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
3. Module Installation
There are two methods for installing a module in the rear position of a chassis. Method one is for installation of a rear module only, when no module will be installed in front of it. Refer
to Figure 5 for instructions. Method two is for installation of
a rear module when another module will be installed in the
chassis position in front of it. Refer to Figures 6a and 6b for
method two. All necessary screws and standoffs are supplied
with the modules.
Figure 5. Installation of rear module only, method one:
C0885-00
The front IM-10 module positions of each chassis are offset below
the rear IM-10 module positions so that all of the status indicators
are visible.
2
Cabinets
3
1
A BB-6 cabinet will house the CH-6 chassis with up to six IM-10
modules installed on it. Refer to cabinet installation documents
for dimensions.
The BB-2 cabinet houses one or two IM-10 modules on the internal chassis that is part of the cabinet. Refer to cabinet installation
documents for dimensions.
C0237-00
Step 1:Insert the bottom of the IM-10 module down into a rear
slot on the chassis.
Step 2: Carefully swing the upper edge of the board back
towards the back of the chassis until it touches the
two standoffs.
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4:Address and wire the modules according to the instructions in this manual.
INSTALLATION STEPS
1. Cabinet Mounting
In a clean, dry area, mount the backbox using the four holes
provided in the back surface of the cabinet (Figure 3).
2. Chassis Installation
The CH-6 chassis is mounted in the BB-6 cabinet. It is shipped
with two self-threading screws, which are used to fasten the
chassis to the back wall of the cabinet (see Figure 4).
The steps in Figures 6a and 6b describe and illustrate module installation when the rear chassis position and the position in front
of it will be filled. Front position installation is possible only if the
rear position is filled with another module.
Figure 3. Typical mounting hole locations:
Figure 6a. Installation of IM-10 module in a rear
chassis position, method two:
Backbox
Mounting
Holes
1
C0235-00
Figure 4. Mounting the CH-6 chassis:
C0225-00
Step 1:Insert the bottom edge of the IM-10 module down into a
rear slot of the chassis.
Step 2:Carefully swing the upper edge of the board towards the
back of the chassis until it touches the short standoff attached to the chassis.
Step 3:Align the long standoff with the short standoff and tighten.
Mount with self-threading screws
to back of cabinet
C0236-00
The BB-2 cabinet comes with the chassis already installed, so no
mounting is necessary.
D500-47-00
2
I56-1797-007
Figure 6b. Installation of IM-10 module in front chassis position:
In Class B operation, the remaining modules are automatically assigned to the next nine higher addresses. For example, if the base address switch is set to 28, the next nine
modules will be addressed to 29, 30, 31, 32, 33, 34, 35, 36,
and 37.
3
The module is shipped in Class B position, remove shunt for
Class A. When operating in Class A, alternate modules are
paired together (+0/+1, +2/+3, +4/+5, +6/+7, +8/+9),
resulting in a total of five modules. For example, if the base
address switch is set to 28, then 30, 32, 34 and 36 will be automatically assigned to the modules while 29, 31, 33, 35 and 37
are available to be used for other modules on the SLC. For Class
A and B operation, DO NOT set the lowest address above 90, as
the other modules will be assigned to nonexistent addresses.
2
1
C0226-00
4.A shunt is provided to disable a maximum of two unused modules in Class B operation and one unused module in Class A
operation. Modules are disabled from the highest address and
work downward. If two modules are disabled, the lowest eight
addresses will be functional, while the highest two will be disabled. For example, in Class B operation, if the shunt for Address Disable is placed on “two” and the base switch is set to
28, the modules will be assigned to 28, 29, 30, 31, 32, 33, 34
and 35 while disabling the highest two positions.
Step 1:Insert the bottom edge of the IM-10 module down into a
front slot of the chassis.
Step 2: Carefully swing the upper edge of the board towards the
back of the chassis until it touches the 11/4˝ (31.75mm)
standoffs installed on the rear module.
Step 3:Align two 4-40 screws with the two standoffs and tighten.
Step 4:Address and wire the modules according to the instructions in this manual.
WIRING
NOTE: Place unused shunts on single pin to store on board for
future use.
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations.
NOTE: Power must not be applied to the unit when changing
functionality of the shunts.
1.Install module wiring in accordance with the job drawings and
appropriate wiring diagrams.
2.All wiring to the IM-10 is done via terminal blocks. In order to
properly make electrical connections strip approximately 1/4˝
of insulation from the end of wire, sliding the bare end of the
wire under the clamping plate screw.
3.Set the address on the modules per the job drawing. Use the
rotary code switches to set the address of the first module (between 01 and 90).
WIRING NOTES
• Power-limited circuits must employ type FPL, FPLR, or
FPLP cable as required by Article 760 of the NEC.
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device
must accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
D500-47-00
3
I56-1797-007
ADDRESS
BASE ADDRESS
6789
5
4
3
2
10
ADDRESS
SLC
+ —
C0886-01
—
TO NEXT
DEVICE
STATUS
INDICATORS
+
+
–
+
–
FROM PANEL OR
PREVIOUS DEVICE
A/B SLCT
COM LOSS
DISABLE 1
DISABLE 2
—
POWER LIMITED
AND SUPERVISED
IDC
ADDRESS
IDC
+ —
+
+1
+0
—
CLASS B IDC (TYPICAL)
ADDRESS
ADDRESS
IDC
+ —
+
+3
+2
—
+4
+ —
+5
47K
EOL
RESISTOR
A2143-00
6789
5
4
3
2
10
IDC
+
—
+6
+ —
+7
+
—
+8
+ —
+9
CONNECT MODULES TO
LISTED COMPATIBLE
CONTROL PANELS ONLY
IDC
+
Figure 7. Typical Initiating Device Circuit Configuration – Class B, Style B:
SIGNAL LINE CIRCUIT 32 VDC MAX.
TWISTED PAIR IS RECOMMENDED.
NOTE: Any number of UL listed contact closure devices may be
used. DO NOT mix fire alarm initiating and supervisory devices
on the same initiating device circuit.
Install contact closure devices per manufacturer’s installation
instructions.
Figure 8: Typical Fault Tolerant Initiating Device Circuit Configuration – Class A, Style D
ADDRESS
BASE ADDRESS
IDC
6789
5
4
3
2
10
ADDRESS
IDC
ADDRESS
ADDRESS
IDC
—
+
+3
+2
ADDRESS
IDC
—
+
STATUS
INDICATORS
SLC
+ —
TO NEXT
DEVICE
+
–
+
–
—
FROM PANEL OR
PREVIOUS DEVICE
IDC 5
A/B SLCT
COM LOSS
DISABLE 1
DISABLE 2
—
POWER LIMITED
AND SUPERVISED
+ —
+
+1
+0
CLASS A IDC (TYPICAL)
SIGNAL LINE CIRCUIT 32 VDC MAX.
TWISTED PAIR IS RECOMMENDED.
6789
5
4
3
2
10
IDC
+ —
IDC 4
+4
IDC 3
+ —
+5
+
—
+6
IDC 2
+ —
+7
+
—
+8
+ —
+9
+
CONNECT MODULES TO
LISTED COMPATIBLE
CONTROL PANELS ONLY
C0887-01
*Remove shunt for Class A operation.
NOTE: Any number of UL listed contact closure devices may be
used. DO NOT mix fire alarm initiating and supervisory devices
on the same initiating device circuit.
Install contact closure devices per manufacturer’s installation
instructions.
Three-Year Limited Warranty
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.
System Sensor warrants its enclosed product to be free from defects in
Please include a note describing the malfunction and suspected cause
materials and workmanship under normal use and service for a period
of failure. The Company shall not be obligated to replace units which
of three years from date of manufacture. System Sensor makes no other
are found to be defective because of damage, unreasonable use, modiexpress warranty for the enclosed product. No agent, representative,
fications, or alterations occurring after the date of manufacture. In no
dealer, or employee of the Company has the authority to increase or alter
case shall the Company be liable for any consequential or incidental
the obligations or limitations of this Warranty. The Company’s obligadamages for breach of this or any other Warranty, expressed or implied
tion of this Warranty shall be limited to the replacement of any part of
whatsoever, even if the loss or damage is caused by the Company’s
the product which is found to be defective in materials or workmannegligence or fault. Some states do not allow the exclusion or limitaship under normal use and service during the three year period comtion of incidental or consequential damages, so the above limitation or
mencing with the date of manufacture. After phoning System Sensor’s
exclusion may not apply to you. This Warranty gives you specific legal
toll free number 800-SENSOR2 (736-7672) for a Return Authorization
rights, and you may also have other rights which vary from state to state.
number, send defective units postage prepaid to: System Sensor, Returns
D500-47-00
4
I56-1797-007