I56-2023-005 INSTALLATION AND MAINTENANCE INSTRUCTIONS 3825 Ohio Avenue, St. Charles, Illinois 60174 1.800.SENSOR2; Fax: 630.377.6495 www.systemsensor.com EM-1RI Relay Module SPECIFICATIONS Normal Operating Voltage: Standby Current: Alarm Current: Short Circuit Current, Dry Control Input: Maximum Resistance, Dry Contact Input: Temperature Range: Humidity: Dimensions: Accessories: CURRENT RATING 3A 2A .9 A .9 A .5 A 1A .3 A 1.5 A .7 A 2A 15 to 30 VDC 580 µA max. average (continuous broadcasts) 2.0 mA (red LED on) 30 µA max. average (5VDC) 100 Ω 32°F to 120°F (0°C to 49°C) 10% to 93% RH Non-condensing 4.17˝ H × 4.26˝ W × 1.22˝ D; (106 mm H × 108 mm W × 31 mm D) Wall cover plate (included); SMB500 Surface Mount Electrical Box; CB500 Control Module Barrier MAXIMUM VOLTAGE 30 VDC 30 VDC 110 VDC 125 VDC 30 VDC 30 VDC 125 VAC 25 VAC 70.7 VAC 25 VAC LOAD DESCRIPTION Resistive Resistive Resistive Resistive Inductive (L/R=5ms) Inductive (L/R=2ms) Inductive (PF=.35) Inductive (PF = .35) Inductive (PF=.35) Inductive (PF=.35) APPLICATION Non-Coded Coded Non-Coded Non-Coded Coded Coded Non-Coded Non-Coded Non-Coded Non-Coded NOTE: This module is not approved for use in the European Union, at or above 50VAC or 70VDC. BEFORE INSTALLING This information is included as a quick reference installation guide. Refer to the appropriate control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. WIRING NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. 1.Install module wiring in accordance with the job drawings and appropriate wiring diagrams. NOTE: Separate cable entry openings must be used to maintain required spacing between power limited and non-power limited wiring. Optional EA-CB may be required to separate power limited and non power limited wiring in the electrical box. 2.Set the address on the module per job drawings using the IR configuration tool (model no. EA-CT). 3. Secure module to electrical box (supplied by installer). AUTO ADDRESSING Eclipse Series devices are capable of supporting auto addressing, if the fire alarm control panel is designed to do so. In auto addressing, the control panel, through the use of each device’s on-board isolators, can automatically assign device addresses. NOTICE: This manual should be left with the owner/user of this equipment. GENERAL DESCRIPTION Relay Module, Model EM-1RI, is to be designed for use in activation of the types of products that are generally connected to an intelligent fire alarm system. It provides two sets of form C contacts that switch together (one DPDT relay). There is also an input that is capable of monitoring a dry set of contacts for open or closed conditions. The module also has on-board short circuit isolators to prevent shorts on the signaling line circuit from disabling more than one device on the intelligent loop. COMPATIBILITY REQUIREMENTS To ensure proper operation, this module shall be connected to a listed compatible control panel. MOUNTING The module mounts directly to 4-inch square electrical boxes. The box must have a minimum depth of 21⁄8 inches. Modules must be mounted with the arrow facing upward for proper operation of the IR programming tool. Surface mounted electrical boxes (SMB500) are available from System Sensor. In order to control which devices are addressed first in wiring configurations with branches, a branch marker can be set at a particular device. A branch marker is an electronic value from 0 to 255 stored in the device memory. The branch markers are set with the IR configuration tool, EA-CT. TERMINAL DEFINITIONS LED INDICATOR T1 (+) SLC in/out T7 Normally Closed #1 T2 (–) SLC in/out T8 Common #1 T3 (+) SLC in/out T9 Normally Open #1 T4 (–) SLC in/out T10 Normally Closed #2 T5 (+) Dry Contact Input T11 Common #2 T6 (–) Dry Contact Input T12 Normally Open #2 WARNING All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module. IR RECEIVER C0166-00 D500-61-00 1 I56-2023-005 Figure 2: Wiring Diagram: RELAY CONTACTS { SIGNAL LINE CIRCUIT (SLC) 30 VDC MAX. TWISTED PAIR RECOMMENDED AND IS POWER LIMITED AND SUPERVISED 12 1 11 2 10 3 9 4 8 5 7 6 MODULE DOES NOT SUPERVISE CONTROLLED CIRCUITS. TERMINALS 1-6 ARE POWER LIMITED. TERMINALS 7-12 ARE NON-POWER LIMITED. )+( )+( )–( )–( )+( )+( )–( )–( NOTE: NORMALLY CLOSED OPTION MAY NOT BE USED FOR FIRE APPLICATIONS. FROM PANEL OR PREVIOUS PANEL TO NEXT DEVICE NORMALLY OPEN (T12) COMMON (T11) NOTE: NORMALLY OPEN OR NORMALLY CLOSED CONTACT DEVICE (NOT SUPERVISED). CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY RELAY CONTACT #2 NORMALLY CLOSED (T10) NORMALLY OPEN (T9) COMMON (T8) RELAY CONTACT #1 NORMALLY CLOSED (T7) C0110-02 Three-Year Limited Warranty #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state. System Sensor warrants its enclosed module to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this module. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the module which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns Department, RA FCC Statement This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: – Reorient or relocate the receiving antenna. – Increase the separation between the equipment and receiver. – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help. D500-61-00 2 I56-2023-005 ©2007 System Sensor