2W-MOD2 2-Wire Loop Test/ Maintenance Module

2W-MOD2
2-Wire Loop Test/
Maintenance Module
The 2W-MOD2 2-wire loop test/maintenance module
maximizes the benefits of i3™ Series smoke detectors by
enabling detector remote maintenance signaling and
EZ Walk loop testing capabilities.
Features
i3
•Allows all 2-wire detectors to be used on any listed alarm control
panel capable of utilizing this module.
•Interprets the i3 remote maintenance signal
•Provides visual indication and an output relay when a detector on
the loop requires cleaning
•Initiates the EZ Walk loop test
•Provides Style D wiring on IDC loops
•Has green, red, and yellow LEDs that indicate:
– Loop communication status
– Maintenance alert
– Freeze trouble
– Alarm
– EZ Walk test enabled
– Wiring fault
CS308
3015195
7300-1653:166
Intelligence. The 2W-MOD2 allows communication to 2-wire i3
detectors with any listed fire alarm control panel capable of utilizing
this module. When these i3 detectors initiate a remote maintenance
signal for required cleaning, both the 2W-MOD2 and the panel can
provide a visual indication of the signal. The 2W-MOD2 module
also features the EZ Walk loop test for 2-wire i3 detectors. With just
the press of a button, this function verifies the entire initiating loop
wiring.
Instant inspection. The 2W-MOD2 2-wire loop test/maintenance
module's green, red, and yellow LEDs provide status indication
for the loop. These LEDs indicate loop communication status,
maintenance alert, alarm, freeze trouble, EZ Walk test enabled, and
wiring fault.
Agency Listings
S3705
Installation ease. The 2W-MOD2 2-wire loop test/maintenance
module mounts to a 4-inch square back box for quick and easy
installation. Terminal blocks with durable SEMS screws assure a
reliable connection.
4-03-E
2W-MOD2 Specifications
Architectural/Engineering Specifications
Loop test/maintenance module shall be System Sensor i3™ Series model number 2W-MOD2, listed to Underwriters Laboratories UL 864 for Control Units for
Fire Protection Signaling Systems. The module shall include provisions for mounting to 4-inch square back boxes. Wiring connections shall be made by means
of SEMS screws. The module shall provide three LED indicators that blink or illuminate to indicate communication status, maintenance alert, alarm or freeze
trouble conditions, and EZ Walk loop test mode. The module shall allow communication to 2-wire i3 detectors with any UL-listed fire alarm control panel capable
of utilizing this module. The 2W-MOD2 module shall offer provisions for Style D wiring on IDC loops, and shall provide a loop testing capability to verify the
initiating loop wiring.
Physical Specifications
Dimensions
4.5˝ H × 4.0˝ W × 1.25˝ D (114 mm × 101 mm × 32 mm)
Weight
8 oz. (225 grams)
Operating Temperature Range
14°F to 122°F (–10°C to 50°C)
Operating Humidity Range
0% to 95% RH non-condensing
Input Terminals
14 to 22 AWG
Mounting
4-inch square back box
Electrical Specifications
Operating Voltage
Nominal: 12/24 V
Min: 8.5 V power limited
Max: 30 V power limited
Maximum Ripple Voltage
30% of applied voltage (peak to peak)
Maximum Standby Current
30 mA
Maximum Alarm Current
90 mA
Maximum Maintenance Current
53 mA
Alarm Contact Ratings
0.5 A @ 36 VDC, resistive
Maintenance Contact Ratings
2 A @ 30 VDC, resistive
LED Modes
LED Color
Status
Condition
Green
On
Power on. Detectors on loop do not have communication capability.
Blinking 1 sec. on / 1 sec. off
Power on. Detectors on loop are communicating normally.
Off
Power not applied or module not in operation.
Red
On
Detector on loop in alarm.
Blinking 1 sec. on / 1 sec. off
One or more detectors on loop is in need of maintenance or is in freeze trouble.
Yellow
On
Loop wiring fault exists.
Blinking 0.5 sec. on / 0.5 sec. off
Module is in EZ Walk test mode.
Power-Up Sequence for LED Indication
Condition
Duration
Initial LED status indication
2 minutes
EZ Walk test available
6 minutes after reset
Ordering Information
Part No.
2W-MOD2
Description
2-wire loop test/maintenance module for 2-wire i3 series standard, sounder, and Form C relay smoke detectors
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2009 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0349-003 • 6/09 • #2178