SYSTEMSENSOR 4WITAR-B

Smoke Detectors with
Sounder and Relay Option
System Sensor i3™ sounder and relay smoke detectors
apply the guiding principles of installation ease,
intelligence, and instant inspection in a series of
specialty conventional devices.
Installation ease. Throughout the i3 series, installation is simple
with its installer-friendly base and plug-in design. The base
accommodates a broad range of back box and direct mounting
options and provides ample space for pre-wiring the device. To
complete the installation, the i3 detector plugs into its base with a
simple Stop Drop ’N Lock action.
Features
• 85 dB sounder
• Form C relay
• Isolated thermal sensor
• Plug-in design – base included
Intelligence. To reduce the likelihood of nuisance alarms, all
i3 detectors are equipped with both drift compensation and
smoothing algorithms. These capabilities minimize both short- and
long-term causes of nuisance alarms such as RF interference and
dust accumulation. When connected to the 2W-MOD2 loop test/
maintenance module or an i3 Ready™ panel, 2‑wire i3 detectors can
generate a remote maintenance signal when in a maintenance or
freeze trouble condition. To measure the sensitivity of any i3 detector,
the SENS-RDR displays the reading, in terms of percent-per-foot
obscuration, within seconds.
Instant inspection. The i3 line’s red and green LEDs simplify local
status indication during power-up, standby, alarm, maintenance and
freeze trouble conditions. When in alarm, i3 sounder models generate
an 85 dB temporal tone. If connected to the RRS-MOD reversing
relay/synchronization module, all i3 sounders on the loop will
activate when one detector is in alarm. Additionally, the RRS-MOD
synchronizes the output of all i3 sounders to ensure a clear audible
signal.
Should the application call for differentiating between a local and
a general alarm, the i3 line offers an isolated thermal model, which
initiates a local alarm when smoke is detected, and a general alarm
when the thermal sensor is activated.
• In-line terminals
• Flexible mounting options
• Stop-Drop ’N Lock™ attachment to the base
• Removable cover and chamber
• Remote maintenance signaling
• Drift compensation and smoothing algorithms
• Simplified sensitivity measurement
• Dual color LEDs
Agency Listings
S911
3015195
7272-1653:164
372-02-E
2133
Smoke Detector Specifications
Electrical Specifications
Operating Voltage
Maximum Ripple Voltage
Standby Current
Peak Standby Current
Maximum Alarm Current
Alarm Contact Ratings
Form C Contact Ratings
Physical Specifications
Operating Temperature
Range
Operating Humidity
Range
Thermal Sensor
Freeze Trouble
Sensitivity
Input Terminals
Dimensions (including
base)
Approximate Weight
Sound Pressure Output
Mounting
LED Modes
Nominal: 12/24 V non-polarized
2-wire: 8.5 V - 35 V
4-wire: 10 V - 35 V
30% of applied voltage (peak to peak)
2-wire: 50 µA maximum average
4-wire: 50 µA maximum average
2-wire: 100 µA
4-wire: n/a
2-wire: 2WTR-B: 130 mA limited by control
panel
2WTA-B: 130 mA**
4-wire: 4WTA-B, 4WTR-B: 35 mA
4WTAR-B, 4WITAR-B: 50 mA
**Direct Power (Non-reverse Polarity): 130
mA limited by panel. Reverse Polarity Power:
30 mA for the 2WTA-B in alarm; 12 mA for all
other 2WTA-B units on the loop. Add 25 mA
for the RRS-MOD reversing relay alarm current.
2-wire: n/a
4-wire: 0.5 A @ 30V AC/DC
2A @ 30V AC/DC
32°F–100° F (0°C–37.8° C)
0 to 95% RH non-condensing
135° F (57.2° C) fixed
41° F (5° C)
2.5%/ft. nominal
14–22 AWG
5.3 inches (134 mm) diameter, 2.0 inches (51
mm) height
7.1 oz. (200 grams)
85 dBA (models 2WTA-B, 4WTA-B, 4WTAR-B,
and 4WITAR-B only)
3½-inch octagonal back box, 4-inch octagonal
back box, Single gang back box, 4-inch square
back box with a plaster ring, Direct mount to
ceiling
LED Mode
Power up
Green LED
Blink every
10 seconds
Red LED
Condition
Blink every 10 Initial LED
seconds
status
indication
Normal
Blink every 5 off
(standby)
seconds
Out of
off
Blink every 5
sensitivity
seconds
Freeze
off
Blink every 10
trouble
seconds
Alarm
off
Solid
Power Up Sequence for LED Indication
Condition
Duration
Initial LED
80 seconds
status
indication
Architect/Engineer Specifications
Duration
80 seconds
Smoke detector shall be a System Sensor i3 Series model number_______,
listed to Underwriters Laboratories UL 268 for Fire Protection Signaling
Systems. The detector shall be a combination photoelectric/thermal
equipped with a sounder (model 2WTA-B, 4WTA-B), a Form C relay (model
2WTR-B), a combination sounder/relay (model 4WTAR‑B) or an isolated
thermal/sounder/relay (model 4WITAR-B). The detector shall include a
mounting base for mounting to 3½-inch and 4-inch octagonal, single gang,
and 4-inch square back boxes with a plaster ring, or direct mount to the
ceiling using drywall anchors. Wiring connections shall be made by means
of SEMS screws. The detector shall allow pre-wiring of the base and the
head shall be a plug-in type. The detector shall have a nominal sensitivity
of 2.5% per foot nominal as measured in the UL smoke box. The detector
shall be capable of automatically adjusting its sensitivity by means of drift
compensation and smoothing algorithms. The detector shall provide dual
color LED indication which blinks to indicate power-up, normal standby, out
of sensitivity, alarm, and freeze trouble conditions. When used in conjunction
with the 2W-MOD2 module, 2-wire models shall include a maintenance
signal to indicate the need for maintenance at the alarm control panel, and
shall provide a loop testing capability to verify the circuit without testing each
detector individually. When used in conjunction with the RRS-MOD module,
all i3 sounder models on a loop shall sound when one alarms, all shall be
synchronized, and all sounders may be silenced from the panel.
Ordering Information
Model
2WTA-B
Thermal
Yes
Wiring
2-wire
2WTR-B
Yes
2-wire
4WTA-B
4WTR-B
4WTAR-B
4WITAR-B
Yes
Yes
Yes
Yes
4-wire
4-wire
4-wire
4-wire
Alarm Current
130 mA max. limited by
control panel
130 mA max. limited by
control panel
35 mA
35 mA
50 mA
50 mA
Model
RRS-MOD
2W-MOD2
SENS-RDR
RT
A77-AB2
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
Description
Reversing relay/synchronization module
2-wire loop test/maintenance module
Sensitivity reader
Removal/replacement tool
Retrofit adapter bracket
©2006 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-0348-003 • 7/06 • #1676