the SGR 282 Z Series data sheet

SGR 282 Z Series
will be replaced by SGR282ZK
relays
Circuit Diagram (view on relay upper side)
-- PCB Relay with forcibly guided contacts
-- Protective separation between coil and contacts
(leakage and creepage distances >14mm); protective
separation diagonally between left and right contact
side (leakage and creepage distances >5.5mm)
-- EN50205 type B
-- 2 CO contacts
-- Mean coil power 1W
-- Holding coil power 0.31W
Contact Lifetime for NO Contacts
10000
24 14
21 11
22 12
Operations x 1000
Relay Key Data
SGR282Z
Dimensions
30.2
A2
12.7
1000
A1
2.5/2.54
Contact material
AgCuNi
Type of contact
Single contact
Rated switching capacity 250VAC 6A AC1 2‘000VA
Electr. life AC 1(360 cycles/h)
approx.100‘000
Inrush current max.
15A for 20ms
Switching voltage range
5 to 250 VDC/VAC
Switching current range*
20mA to 6A
Switching current range**
10mA to 6A
Switching capacity range*
120mW to 1‘500W(VA)
Switching capacity range**
60mW to 1‘500W(VA)
Contact resistance (as delivered) ≤100mΩ/28V/100mA
**Values for AgCuNi+4-6μm Au
Nominal voltage
VDC
Min. pick-up voltage
at 20 °C
Drop-out voltage at
20 °C
Nominal current
in mA
(other voltages on request)
5
6
12
18
24
48
60
110
3.75
4.5
9.0
13.5
18.0
36.0
45.0
82.5
≥0.5
≥0.6
≥1.2
≥1.8
≥2.4
≥4.8
≥6.0
≥11.0
181.8
166.6
85.7
66.6
33.3
20.8
13.6
11.0
Resistance in Ohm
at 20 °C
Standard coils for direct current
Mechanical endurance
>50x106 operations
Switching frequency, mechanical
15Hz
Response time (all NO closed)
typically 12ms
Drop-out time** (all NC closed)
typically 5ms
Bounce time of NO contact
typically 4ms
Bounce time of NC contact typically 8ms
Shock resistance 16ms
NO > 10g
NC > 2.5g
Vibration resistance
NO > 10g
(10-55Hz)
NC > 1g
Resistance to short circuiting contacts
1‘000A SCPD 6A gG/gL (pre-fuse)
Ambient temperature
-40°C to +70°C
Thermal resistance
50K/W
Temperature limit for coil
120°C
Weight
ca. 20g
Mounting position
any
Type of protection
RT II
Solder bath temperature
270°C/5s
N
ot
*Guided values
de
Additional Data
Contact Data
When switching high voltages and currents the layer of
gold is already destroyed after a few switching operations. Once the gold layer is damaged due to the
switching of high loads, this contact must not be used
anymore for signal and control current circuits.
Then safe contact making is only possible at high loads
with the formation of sparks.
Load Limit Curve with Direct Current
8
6
4
3
2
1
1
0.8
0.6
0.4
0.3
0.2
2
0.1
0
50
100
Switching Current (A)
Tests, Regulations
Excitation Voltage Range
UL File E188953
Insulation class IEC 60664-1
Protection class II
Fire protection requirements
Sec. 1
250VAC
VDE 0106
UL 94 / V1
Options, Accessories
PCB socket, DIN rail socket
Sealed RT III
Dust resistant with O-Ring
Contact material with 4-6μm Au
200
60
80
250
2.5
2.0
1
1.5
1.0
see page 30
on request
O-ring dust resistant
Gold plating 4-6μm
Coil voltage
Type designation
+41 (0)81 303 54 00
+41 (0)81 303 54 01
150
3.0
SGR282Z24VDC AU6 08
Fon:
Fax:
10
Gold contacts with 4-6μm layer thickness
1)Inductive load L/R 40ms
2)Resistive load
Product Key
ELESTA GmbH, Heuteilstrasse 18,
CH - 7310 Bad Ragaz, Switzerland
5.0
Maximal contact load at AC 1 with 230V:
2 contacts with 6A each
**without spark suppression
Approvals
27.5 ± 10%
36 ± 10%
140 ± 10%
270 ± 10%
720 ± 10%
2‘300 ± 10%
4‘400 ± 13%
10‘000 ± 15%
DC 13:24V
10
0.1
0.5
1.0
Switching Current (A)
s
[mm]
Ø1.3
AC 15:230V
Maximal switching characteristics (DIN EN60947-5-1,
Tab. C2)
AC 15: 230V / 3A
DC 13: 24V / 4A
UL 508: C300
Operations x 1000
1
7.5
AC 1:230V
100
gn
2.6
ew
15
rn
5 5
fo
2.6
-- Double or reinforced insulation
at 250VAC
-- Air and creepage distance
>5.5mm
-- Test voltage
4‘000V/50Hz/1min
-- Double or reinforced insulation
at 250VAC
-- Air and creepage distance
>14mm
-- Test voltage
5‘000V/50Hz/1min
Test voltage contact open
1‘500V/50Hz/1min
Creepage resistance
CTI 550
Pollution degree
2
Overvoltage category
III
Insulation resistance at Up 500VDC
>100MΩ
si
3.7
0.3
25.6
Insulation Data
DC 1:24V
0.5
UB
UN 0
2
0
20
40
100
Ambient Temperature °C
1)Max. excitation voltage with contact load: ≤4A
2)Min. excitation voltage (guaranteed values) without
previous operation
No heat accumulation due to intrinsic heating of
other components. Continuous duty 100%.
© Copyright
05/2014